TECHNICAL SPECIFICATIONS SWITCH SOLID POLYMER INSULATION THREEPHASE, 27 KV, BIL: 150 KV, 400 A, SF6, WITH ELECTRICAL CONTROL |
|||
Item | Feature / description / parameter | Specification requested | Specification Offered |
1 | Quantity | 3 | 3 |
2 | Mark | Indicate | HEMG |
3 | Model | Indicate | FLW-27 |
4 | Year of manufacture | Not less 2015 | 2016 |
5 | Origin | Indicate | CHINA |
6 | Manufacturing Standards | IEC60129 IEC62271-103 IEC62271-1 ANSI/IEEEC IEC-265-137.71 | IEC |
7 | Certifications | Certificates of conformity of product or of compliance with standards required, in Spanish and/or English | IN ENGLISH |
8 | Operating Voltage | Greater than or equal to 27kV | 27KV |
9 | Operating Current | Greater than or equal to 400A | 400A |
10 | Frequency of Operation | 60Hz | 60HZ |
11 | Means of insulation | Solid Polymer | SOLID POLYMER |
12 | Means of interruption | SF6 | SF6 |
13 | BIL | 150kV for a voltage level of 27kV to 2800masl | YES |
14 | Suitable to operate (opening and closing) with load current | If | YES |
15 | Close current asymmetric crest | 31.0 kA RMS | 31KA |
16 | Close current, effective asymmetrical | 20.0 kA RMS | 20KA |
17 | Operations Counter | If | YES |
18 | VISUAL INDICATOR OF CONTACT | If | YES |
19 | Short-circuit current 1 | Must withstand a minimum 12.5kA for at least 3s | 12.5KA |
20 | Protection | IP 65 or higher | PI65 FOR TANK |
21 | Number of Open/Close Operations | Greater than or equal to 10 000 | 10000 |
22 | Type of Installation | With all the necessary accessories for mounting in concrete post | POLE MOUNTED |
23 | Use | Weather | OUTDOOR |
24 | Operating Temperature | -40 to 65°C | (-40ºC TO 65ºC) |
25 | Type of Operation | Manual and remote, through SCADA system | YES |
26 | Engine | Power to 48V | 48VDC |
27 | CONTROL CABINET | Stainless steel housing. With all the necessary accessories for mounting in concrete post. Protection to IP55 or higher. | YES |
Long battery life, with the backing of at least 48hs, and power to 48V. Battery status indicator. | YES | ||
Power 110…250V AC/DC. | 125VDC/AC | ||
Relay designed for remote control and monitoring, protection, failure indication, Power quality analysis and automation, fulfilling the protocols requested in item 24. You must have at least 6 voltage sensors (immersed in the tank) to measure voltage and Fase-Tierra Fase-Fase both in the load side as on the source; 3 current transformers with ability to measure currents of phase and waste. Language of visual inspection: Spanish and/or English. | YES,IN ENGLISH | ||
28 | Weight | Greater than or equal to 136kg | 150KG |
29 | Counter of useful life. | You must indicate the total number of open/close operations and wear of the contacts | YES |
30 | Native COMMUNICATION INTERFACE | Module or port to 10/100Mbps Ethernet TCP/IP RJ-45 Connector native to the computer (without converters assets or liabilities or similar) | RJ45 |
31 | Communication protocol for telecontrol and/or automation on the native communications interface | DNP3i (TCP/IP), and optionally IEC 60870-5-104 | DNP3.0 |
32 | Integration Services to the SCADA system available to the EEQ | If | N/A |
33 | Training | 2 days for installation, operation and maintenance for 20 people, and 3 days in processes of configuration and integration of SCADA protocols for 10 people | N/A |
34 | Technical Warranty | 4 Years | YES |
35 | Catalog | Attach catalog in Spanish and/or English | IN ENGLISH |
36 | Delivery Time | 90 days from the date of signature of the contract | YES |
37 | Test protocol type (Suppliers) | The bidders appended to its offer by (the) test protocols type of material offered. | YES |