33kv out Door Pole Mounted Epoxy Resin Current Transformer

Product Details
Customization: Available
Application: Instrument
Type: Current Transformer
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 33kv out Door Pole Mounted Epoxy Resin Current Transformer
  • 33kv out Door Pole Mounted Epoxy Resin Current Transformer
  • 33kv out Door Pole Mounted Epoxy Resin Current Transformer
  • 33kv out Door Pole Mounted Epoxy Resin Current Transformer
  • 33kv out Door Pole Mounted Epoxy Resin Current Transformer
Find Similar Products

Basic Info.

Model NO.
LZZBW
Operation Condition
Outdoor
Usage
Protection, Measurement
Winding Form
Small Fixed Type
Insulating Medium
Epoxy Resin
Installation
Extension Type
Transport Package
Wooden Case
Specification
33KV
Trademark
HEMG
Origin
China
Production Capacity
50000

Product Description

33kv out Door Pole Mounted Epoxy Resin Current Transformer




 
  CURRENT  TRANSFORMER 36 KV      
         
         
         
ITEM SPECIFICATION UNIT REQUIRED GUARANTEED
1 GENERAL DATA      
1.1 MANUFACTURER   INDICATE HEMG
1.2 COUNTRY   INDICATE CHINA
1.3 TYPE   SINGLE PHASE SINGLE PHASE
      COLUMN COLUMN
1.4 MODEL   INDICATE LZW-35
1.5 ALTITUDE OF INSTALLATION M.O.S.L 1000 1000
1.6 STANDARD OF MANUFACTURE   IEC 60044-1 IEC 60044-1
1.7 INSTALLATION   OUTDOOR OUTDOOR
1.8 QTY EACHS 12 12
         
2 NOMINAL DATA AND CHARACTERISTICAS      
2.1 FREQUENCY HZ 60 60
2.2 CHARACTERISTICS OF VOLTAGE      
  NOMINAL VOLTAGE OF THE SYSTEM KV 33 33
  MAX. VOLTAGE OF THE SYSTEM KV 33 33
  VOLTAGE OF THE EQUIPMENT KV 36 36
2.3 INSULATION LEVEL      
  WITHSTAND VOLTAGE INDUSTRIAL VOLTAGE  1 MINUTE   KV 70 70
  IMPULSE VOLTAGE 1.2/50 us KVp 170 170
2.4 CHARACTERSITICS OF CURRENT      
  SHORT TIME CURRENT ( Ith) 3 seconds   KA 25 25
  DYNAMIC CURRENT (Idyn) KA 62.5 62.5
  FACTOR OF CONTINUE CURRENT   1.2 1.2
2.5 RELATION OF TRANSFORMATION      
  CURRENT OF PRIMARY A 300 - 600 300 - 600
  CURRENT OF THE SECONDARY A 5 5
2.6 NUMBER OF CORES SECONDARY SIDE      
  CORES OF MEASURE EACH 1 1
  CORES OF PROTECTION EACH 1 1
2.7 CONSUMPTION / PRECISION CLASS.      
  MEASUREMENT CORE VA 0.2,20 0.2,20
  PROTECTION CORE VA 5P20,20 5P20,20
  CONSTRUCTIVE DETAILS.      
  INSULATION WAY   EPOXY RESIN EPOXY RESIN
         
3 INSULATOR      
  TYPE   OUTDOOR OUTDOOR
  MATERIAL   EPOXY RESIN EPOXY RESIN
  COLOR   INDICATE GRAY/RED
  TOTAL LEAKAGE DISTANCE(1116MM) MM INDICATE 1280
         
4 WEIGHT AND DIMENSIONS      
  TOTAL WEIGHT OF THE TRANSFORMER KG INDICATE 60
  HEIGHT OF THE TRANSFORMER MM INDICATE 700
  SCHEME DETAILED WITH DIMENSIONS   YES YES