Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Still deciding? Get samples of US$ 300000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Mobile substation for outdoor use 132 KV, 50 Hz system. |
General data |
- Trailer Type |
- Ambient temperature 55Co |
- 25 MVA |
- 132/33 KV |
- No. of out going feeder: four |
- Type and rating of 132 KV circuit breaker : SF6, 40KA, 1250A spring change operating mechanism. |
- Rating of 132 KV Isolator: 1250A. |
- Rating of 132 KV lighting arrester 120 KV, 10KA. |
- Main Transformer vector group: ynd 11 |
- Auxiliary transformer rating and vector group: 250 KVA, Zigzag/star. Znyn11, 33/.4 KV: |
- Type of 4 feeder circuit breaker and rating: vacuum or SF6, 31.5 KA spring change mechanism, CT ratio 300-600/5A. |
- Control voltage for (Closing, tripping, alarm, protection, motor circuit) 110 VDC.( ) |
- Type of batteries: Nickel Cadmium |
- Battery charger: input : 380V AC Out put : 110V DC. |
- H.V Disconnector with fitting from mobile to line. |
- With earthing mesh material. |
- With gantry towers, with lightening protection device steel Plate and jacks. |
- With schematic wiring and manual instructions, with all accessories for erection and maintenance. |