66kv/132kv 60Hz/60Hz Hybrid Gas Insulated Swithgear (HGIS)

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 66kv/132kv 60Hz/60Hz Hybrid Gas Insulated Swithgear (HGIS)
  • 66kv/132kv 60Hz/60Hz Hybrid Gas Insulated Swithgear (HGIS)
  • 66kv/132kv 60Hz/60Hz Hybrid Gas Insulated Swithgear (HGIS)
Find Similar Products

Basic Info.

Model NO.
HGIS
Speed
High-Speed Circuit Breaker
Arc-extinguishing Medium
SF6
Installation
Open Frame
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification
ISO9001-2000, CE, CB
Transport Package
Wooden
Specification
72.5KV HGIS
Trademark
HEMG
Origin
China
Production Capacity
1000

Product Description

66kv/132kv 60Hz/60Hz Hybrid Gas Insulated Swithgear (HGIS)
L.T. 50 kV: S.E ANTUQUITO - S.E ARIANA INGENIERÍA BÁSICA
No. DESCRIPCIÓN REQUERIDO OFERTADO/ GARANTIZADO UNIDAD
1.0 GENERAL
1.1 IDENTIFICACIÓN DEL PROVEEDOR      
1.1.1 Proveedor Por el proveedor HEMG -
1.1.2 País Por el proveedor CHINA -
1.1.3 Dirección Por el proveedor NINGBO ,CHINA -
1.1.4 Teléfono Por el proveedor 008613805895904 -
1.1.5 Fax/Correo electrónico Por el proveedor 008657488079270 -
1.1.6 Persona de contacto Por el proveedor TAILICHEN -
1.1.7 Propuesta Nº Por el proveedor HGIS20180704 -
1.1.8 Fecha de propuesta Por el proveedor 2018-07-04 -
1.2 DATOS DEL FABRICANTE      
1.2.1 Fabricante Por el proveedor HM -
1.2.2 País Por el proveedor CHINA -
1.2.3 Dirección Por el proveedor SHANGHAI, CHINA -
1.2.4 Teléfono Por el proveedor 008613805895904 -
1.2.5 Fax/Correo electrónico Por el proveedor 008657488079260 -
1.2.6 Persona de contacto Por el proveedor TAILICHEN -
1.2.7 Certificaciones ISO 9002 /
ISO 14000
ISO9001/ISO14000 -
2.0 CONDICIONES AMBIENTALES DE LUGAR DE OPERACIÓN
2.1 LUGAR DE INSTALACIÓN SE's Antuquito / Ariana -
2.2 ALTITUD 4100 / 4695 m.s.n.m.
2.3 TEMPERATURA DEL MEDIO AMBIENTE    
2.3.1 Temperatura promedio 15 °C
2.4 POLUCIÓN    
2.4.1 Nivel de contaminación según IEC Alto -
2.4.2 Distancia de fuga 25 mm/kV
3.0 CÓDIGOS Y REGLAMENTOS APLICABLES
3.1 IEC 60056 - HIGH-VOLTAGE ALTERNATING CURRENT CIRCUIT BREAKERS Requerido COMPLY -
3.2 IEC 60060 - HIGH-VOLTAGE TEST TECHNIQUES Requerido COMPLY -
3.3 IEC 60129 - ALTERNATING CURRENTE EARTHING SWITCHES Requerido COMPLY  
3.4 IEC 60185 - CURRENT TRANSFORMER Requerido COMPLY -
3.5 IEC 60267 - GUIDE TO THE TESTING OF CIRCUIT BREAKERS WITH RESPECT TO OUT OF PHASE SWITCHING Requerido
COMPLY
-
3.6 IEC 60376 - SPECIFICATION AND ACCEPTANCE OF NEW SULPHUR HEXAFLUORIDE Requerido COMPLY -
3.7 IEC 60694 - COMMON CLAUSES FOR HIGH VOLTAGE SWICHGEAR AND CONTROL GEAR STANDARS Requerido
COMPLY
-
3.8 DIN 50976 - HOT DIP GALVANIZED Requerido COMPLY  
3.9 ASTM - AMERICAN SOCIETY FOR TESTING AND MATERIALS Según Aplique COMPLY -
3.10 ASME - AMERICAN SOCIETY OF MECHANICAL ENGINEERS Según Aplique COMPLY -
3.11 OSHA - OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION Según Aplique COMPLY -
3.12 NFPA - NATIONAL FIRE PROTECTION ASSOCIATION Según Aplique COMPLY -
4.0 CARACTERÍSTICAS DEL SISTEMA ELÉCTRICO
4.1 TENSIÓN NOMINAL DEL SISTEMA 50 50 kV
4.2 TENSIÓN MÁXIMA DE OPERACIÓN 55 55 kV
4.3 FRECUENCIA DE OPERACIÓN 60 60 Hz
4.4 SISTEMA DE ATERRAMIENTO Directo a tierra DIRECTLT0 EEARTH -
4.5 NÚMERO DE FASES 3 3 -
4.6 CAPACIDAD DE RUPTURA POR CORTOCIRCUITO 25 25 kA
4.7 TIEMPO DE DESPEJE DE FALLA 0.5 0.5 Seg
4.8 DESIGNACIÓN DE FASES R,S, T RST -
5.0 CARACTERÍSTICAS POR BAHÍA HÍBRIDA COMPACTA
5.1 GENERAL      
5.1.1 Operación A Intemperie OUTDOOR -
5.1.2 Servicio Continuo CONTINUOUS -
5.1.3 Accionamiento Tripolar THREE POLES -
5.1.4 Tipo Conexión a barra simple CONNECTION TO SINGLE BAR -
5.1.5 Cantidad 4 4 Unidades
5.2 EQUIPOS COMPONENTES      
5.2.1 Interruptor inmerso en SF6 Requerido COMPLY -
 
HOJA DE DATOS TÉCNICOS GARANTIZADOS BAHÍA HÍBRIDA COMPACTA EN SF6


ETEC
L.T. 50 kV: S.E ANTUQUITO - S.E ARIANA INGENIERÍA BÁSICA
No. DESCRIPCIÓN REQUERIDO OFERTADO/ GARANTIZADO UNIDAD
a Tensión máxima de operación 72.5 72.5 kV
b Tensión de sostenimiento a frecuencia industrial 140 140 kV
c Tensión de sostenimiento al impulso 325 325 kVp
d Corriente nominal continua 2000 2000 A
e Rated short time withstand current 25 25 kA
f Rated sorht circuit duration 3 3 seg.
g Rated peak withstand 65 65 kA
h Subida de temperaturas de partes activas en corriente nominal continua < 65 65 °C
i Subida de temperaturas de terminales en corriente nominal continua < 65 65 °C
j Subida de temperaturas de recinto en corriente nominal continua < 30 30 °C
k Accionamiento Tripolar THREE POLES -
l Tiempo de apertura 50 50 ms
m Tiempo de cierre 60 60 ms
n Acumulador de energía Resorte SPRING -
o Motor de Operación      
  Tensión de Alimentación 125-13%,+10% 125(-13%, +10%) VCC
  Potencia Nominal ≤ 500 ≤500 W
  Corriente Nominal ≤ 4 ≤4 A
  Potencia Absorvida en el arranque Por el proveedor 600 W
  Corriente de arranque Por el proveedor 5 A
p Bobinas de apertura      
  Cantidad 2 2 Unidades
  Tensión de Alimentación 125-13%,+10% 125(-13%, +10%) VCC
  Potencia Nominal ≤ 100 ≤100 W
  Corriente Nominal ≤ 1 ≤1 A
  Potencia Absorvida en la energización Por el proveedor 600 W
  Corriente de energización Por el proveedor 5 A
q Bobinas de cierre      
  Cantidad 1 1 Unidad
  Tensión de Alimentación 125-13%,+10% 125(-13%,+10%) VCC
  Potencia Nominal ≤ 250 ≤250 W
  Corriente Nominal ≤ 2 ≤2 A
  Potencia Absorvida en la energización Por el proveedor 330 W
  Corriente de energización Por el proveedor 3.3 A
r Contactos auxiliares 8 NO+ 8NC 8NO+8NC -
5.2.2 Seccionador de tres posiciones del lado de la fuente inmerso en SF6 Requerido INCLUDED -
a Tensión máxima de operación 72.5 72.5 kV
b Tensión de sostenimiento a frecuencia industrial 140 140 kV
c Tensión de sostenimiento al impulso 325 325 kVp
d Corriente nominal continua 2000 2000 A
e Rated short time withstand current 25 25 kA
f Rated sorht circuit duration 3 3 seg.
g Rated peak withstand 65 65 kA
h Subida de temperaturas de partes activas en corriente nominal continua < 65 65 °C
i Subida de temperaturas de terminales en corriente nominal continua < 65 65 °C
j Subida de temperaturas de recinto en corriente nominal continua < 30 30 °C
k Accionamiento Tripolar TRIPOLAR -
l Motor de Operación      
  Tensión de Alimentación 125-13%,+10% 125(-13%, +10%) VCC
  Potencia Nominal ≤ 240 ≤240 W
  Corriente Nominal ≤ 2 ≤2 A
  Potencia Absorvida en el arranque Por el proveedor 600 W
  Corriente de arranque Por el proveedor 5 A
  Tiempo de operación del motor < 10 10 seg.
m Contactos auxiliares 8 NO+ 8NC 8NO+8NC -
5.2.3 Seccionador de tres posiciones del lado de la fuente inmerso en SF6 Requerido INCLUEDE -
a Tensión máxima de operación 72.5 72.5 kV
b Tensión de sostenimiento a frecuencia industrial 140 140 kV
c Tensión de sostenimiento al impulso 325 325 kVp
d Corriente nominal continua 2000 2000 A
e Rated short time withstand current 25 25 kA
 
HOJA DE DATOS TÉCNICOS GARANTIZADOS BAHÍA HÍBRIDA COMPACTA EN SF6


ETEC
L.T. 50 kV: S.E ANTUQUITO - S.E ARIANA INGENIERÍA BÁSICA
No. DESCRIPCIÓN REQUERIDO OFERTADO/ GARANTIZADO UNIDAD
f Rated sorht circuit duration 3 3 seg.
g Rated peak withstand 65 65 kA
h Subida de temperaturas de partes activas en corriente nominal continua < 65 65 °C
i Subida de temperaturas de terminales en corriente nominal continua < 65 65 °C
j Subida de temperaturas de recinto en corriente nominal continua < 30 30 °C
k Accionamiento Tripolar TRIPOLAR -
l Motor de Operación      
  Tensión de Alimentación 125-13%,+10% 125(-13%, +10%) VCC
  Potencia Nominal ≤ 240 240 W
  Corriente Nominal ≤ 2 2 A
  Potencia Absorvida en el arranque Por el proveedor 600 W
  Corriente de arranque Por el proveedor 5A A
  Tiempo de operación del motor < 10 10 seg.
m Contactos auxiliares 8 NO+ 8NC 8NO+8NC -
5.2.4 Transformadores de corriente montados en los bushigns del lado de la carga Requerido COMPLY -
a Cantidad 3 (uno por fase) 3 Unidades
b Tipo Toroidal TOROIDAL -
c Relación de transformación 150-300/1/1/1 150-300/1/1 A
d Clase de precisión      
  Núcleo 1 Cl. 0.2 (Medición) CL0.2 -
  Núcleo 2 5P20 (Protección) 5P20 -
  Núcleo 3 5P20 (Protección) 5P20 -
e Consumo      
  Núcleo 1 20 20 VA
  Núcleo 2 20 20 VA
  Núcleo 3 20 20 VA
5.3 OTRAS CARACTERÍSTICAS      
5.3.1 Sistema de aislamiento - Gas SF6      
a Nivel de pérdida o escape anual < 0.5 0.5 %
b Presión de llenado a 20 °C 600 600 kPA
c Mínima presión de servicio a 20°C 540 540 kPA
d Nivel de alarma 1 a 20°C 560 550 kPA
e Nivel de alarma 2, lock or trip 540 500 kPA
f Enclosure      
  Presión de diseño 700 700 kPA
  Presión de prueba de rutina 1050 1050 kPA
  Presión de ruptura > 3000 3000 kPA
  Presión de ruptura del disco de alivio > 1050 1050 kPA
5.3.2 Bushings      
a Material Goma siliconada SILICON GUM -
b Distancia de fuga total desarrollada (fase - tierra) 1375 1375 mm
c Distancia de fuga especificada (fase - tierra) 25 25 mm/kV
d Cantilever Por el proveedor 6000 N
e Capacitancia Por el proveedor 0.05 PF
5.3.3 Circuito de mando y señalización      
a Tensión de alimentación del circuito de mando 125-13%,+10% 125(-13%,+10%) VCC
b Consumo permanente del circuito de mando Por el proveedor 50 W
c Corriente permanente del circuito de mando Por el proveedor 0.5 A
d Tensión de alimentación del sistema de señalización 125-13%,+10% 125(-13%,10%) VCC
e Consumo permanente del sistema de señalización Por el proveedor 50 W
f Corriente permanente del sistema de señalización Por el proveedor 0.5 A
5.3.4 Caja de mando      
a Modelo Por el proveedor HDZ -
b Material de la caja de mando Acero Inoxidable STAINLESS STEEL -
c Grado de protección IP55 IP55 -
d Altura de Instalación sobre el nivel mas bajo de la estructura soporte 1.2 1.2 m
e Tratamiento anticorrosivo Requerido YES -
f Detalle del tratamiento anticorrosivo Por el proveedor YES -
g Mando local manual Requerido YES -
h Señalización del mando local Requerido YES -
i Bloqueos mecánicos para mantenimiento Requerido YES -
 
HOJA DE DATOS TÉCNICOS GARANTIZADOS BAHÍA HÍBRIDA COMPACTA EN SF6


ETEC
L.T. 50 kV: S.E ANTUQUITO - S.E ARIANA INGENIERÍA BÁSICA
No. DESCRIPCIÓN REQUERIDO OFERTADO/ GARANTIZADO UNIDAD
j Calefacción Requerido YES -
  Tensión de alimentación 220, 1Ø 220 VAC
  Máxima Potencia (Consumo) ≤ 100 100 W
  Rango del termostato Por el proveedor (15,35) ºC-
k Iluminación Requerido YES -
  Tensión de alimentación de luminarias interiores 220, 1Ø 220 VAC
  Potencia (Consumo) ≤ 80 ≤80 W
5.3.5 Distancias de aislamiento      
a Distancia entre polos Por el proveedor 1850 -MM
b Distancia a tierra Por el proveedor 4765 -MM
c Distancia entre contactos abiertos Por el proveedor 1805 -MM
5.3.6 Enclavamientos      
a Enclavamientos mecánicos Requerido YES -
b Enclavamientos Eléctricos Requerido YES -
5.3.7 Requerimientos sísmicos      
a Amortiguadores Requerido YES  
b Frecuencia 0.2 0.2 Ciclos/seg.
c Esfuerzo horizontal 0.5 0.5 g
d Esfuerzo vertical 0.3 0.3 g
5.3.8 Soporte metálico      
a Cantidad 1 1 Unidad
b Tipo de soporte Por el proveedor OUTDOOR -
c Galvanizado en caliente Requerido YES -
d Espesor de galvanizado de perfiles y planchas 120 120 micrones
e Espesor de galvanizado de tuercas y pernos 70 70 micrones
f Altura del soporte metálico hasta base del aislador Por el proveedor 2500 m
g Pernos de anclaje Requerido YES -
5.3.9 Pesos      
a Peso del equipo Por el proveedor 2540 kg
b Peso del soporte Por el proveedor 640 kg
c Peso de la caja de mando Por el proveedor 120 kg
d Peso Total Por el proveedor 3300 kg
5.3.10 Diagramas, planos y otros      
a Planos de disposicion física Requerido INCLUDED -
b Diagramas de control Requerido INCLUDED -
c Certificados y miscelaneos Requerido INCLUDED -
d Accessorios Requerido INCLUDED -
e Lista de repuestos para 5 años de operación normal Requerido INCLUDED -

Send your message to this supplier