Basic Info.

Model NO.
LB6
Cooling Method
Oil-immersed Type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001
Usage
Single-phase Transformer, Combined Transformer, Power Transformer
Frequency Characteristics
Power Frequency
Transport Package
Wooden
Specification
110KV
Trademark
HEMG
Origin
China
Production Capacity
100000

Product Description

 
 1             Designation
Standard
Outdoor single phase Oil-paper hairpin type
IEC60044-1:2003
 2             Type LB6-110
 3             Manufacturer HEMG
 4             Designation test certificate:
)  Issuing institute
)  Number and data
Attached in the bid
) KEMA
) 07-1007,2007-06-19
 5             Rated voltage
Rated continuous over voltage
110 kV
110kV
 6             Rated frequency, 50 Hz
 7             Rated nominal primary current, 200-400A 400-800A
 8             Rated secondary current,
Ratio adjustable is done in
1-1-1-1A
Primary
1-1-1-1-1A
Primary
 9             Rated secondary output
)  Core (1)
)  Core (2)
)  Core (3)
)  Core (4)
)  Core (5)
 
)  30VA
)  30VA
)  30VA
)  30VA
) 
 
)  30VA
)  30VA
)  30VA
)  30VA
)  30VA
10           Accuracy Class
)  Core (1)
)  Core (2)
)  Core (3)
)  Core (4)
)  Core (5)
 
)  0.2
)  5P20
)  5P20
)  5P20
)
 
)  0.2
)  0.2
)  0.2
)  5P20
)  5P20
11           Accuracy limit factor 20 20
12           Continuous thermal current ratings factor 120% 120%
13           Short time current ratings,
)  Thermal (Ith)
)  Dynamic (Idyn)
 
)  20-40kA
)  50-100kA
 
)  31.5-45kA
)  80-115kA
14           Instrument security factor    
15           Power frequency withstand voltage 230kV 230kV
16           Impulse withstand voltage 650kV,peak 650kV,peak
17           Impulse wave 1.2/50μs 1.2/50μs
18           Rated secondary winding power frequency withstand voltage
)  Winding to ground
)  Between winding
 
 
)  3kV
)  3kV
 
 
)  3kV
)  3kV
19           Mechanical load on primary terminals:
)  Dynamic load
)  Static load
 
)  2000N
)  2000N
 
)  2000N
)  2000N
20           Material of bellows, if applicable Stainless steel Stainless steel
21           Minimum height As per drawing As per drawing
22           Minimum phase spacing 2500mm 2500mm
23           Minimum clearance 1305mm 1305mm
24           Minimum creepage distance 3850mm 3850mm
25           Size and section of terminal bolt (attach drawing) As per drawing As per drawing
26           Weight per pole 680 kg
27           Weight of oil per pole 140 kg
28           Type of oil and reference specifications IEC 60296
29           Oil density at 25ºC 0.895 g/ml
30           Oil viscosity at 25ºC ≤13 cs (40ºC)
31           Partial discharge level ≤5 pC  (under 1.2Um/√3kV)