SCHEDULE (H)
TECHNICAL PARTICULARS AND GUARANTEES
VOLTAGE REGULATOR
The tender shall complete this schedule, and the particulars and guarantees will be binding on the contractor.
|
|
|
|||
Frequency |
Hz |
50 |
|||
Type of cooling |
|
ONAN |
|||
Type of V.R ratio control. |
|
TAPCON 230 |
|||
Number of tapping |
33 |
||||
Regulation step range. |
% |
+/-10% |
|||
Oil type |
|
Petro-China |
|||
PARTICULARS AND GUARANTEES |
|||||
Impedance at 75ºC on principal tapping |
% |
8 |
|||
|
TESLA |
1.80 |
|||
|
|
Silicon Steel, 30Q130 |
|||
|
|
Copper winding |
|||
Short circuit current |
KA |
4.2 |
|||
Type of paper insulation on conductors |
|
Electrical insulation paper |
|||
No load losses at normal ratio and 50 Hz |
KW |
10 |
|||
Load losses at CMR, 75ºC at normal ratio |
KW |
58 |
|||
R.M.S. Exciting current at normal voltage on principal tap |
Amps |
|
|||
-R.M.S Fundamental current |
Amps |
0.559 |
|||
-R.M.S 3rd harmonic current |
Amps |
0.052 |
|||
-R.M.S 5th harmonic current |
Amps |
0.12 |
|||
-R.M.S 7th harmonic current |
Amps |
0.062 |
|||
Temperature rise of windings at CMR above specified design ambient temp. |
ºC |
55 |
|||
Temperature rise of top oil at CMR above specified design ambient |
ºC |
50 |
|||
Temperature rise of core at CMR and rated voltage |
ºC |
70 |
|||
Min duration at 40°C of over loading of rating 133% |
In min |
120 |
|||
Min duration at 40°C of over loading of rating 150% |
In min |
100 |
|||
Impulse withstand voltage of VR |
kV |
|
|||
Phase connections |
|
|
|||
(I) 1.2 /50 Microsecond full wave |
kV(peak) |
170 |
|||
(II) 1.2 /50 Microsecond chopped wave |
kV (peak) |
187 |
|||
Total oil required |
Liters |
6180 |
|||
Weight of complete VR (including oil) |
Kg |
23500 |
|||
M.V. BUSHING INSULATORS |
|
|
|||
Make
|
|
PUKO |
|||
Type |
|
BW-40/630-4 |
|||
Voltage rating |
KV |
40 |
|||
Current rating |
Amps |
630 |
|||
Length of insulator(Overall) |
mm. |
875 |
|||
Weight of insulator |
Kg |
18 |
|||
Total creepage distance of bushing |
mm |
1256 |
|||
Protected creepage distance of bushing |
mm. |
485 |
|||
Dry withstand power frequency voltage |
KV |
95 |
|||
Routine power frequency test voltage (1 minute) (A) Positive (B) Negative |
KV |
95 95 |
|||
Wet withstand power Frequency voltage |
KV |
80 |
|||
Maximum diameter of bushing when passing through tank top |
mm. |
155 |
|||
Penetration of bushing into tank measured from bottom of fixing flange |
mm. |
210 |
|||
Overall dimensions of complete VR:- |
mm |
4900*3800*3800 |
|||
Manufacturer name and place |
|
HEMG |
|||
Testing Authority name and Place
|
|
HEMG |