SPECIFICATION OF RECLOSERS 22,9 Kv |
Nº |
DESCRIPTION |
UNIT |
REQUIRED |
GUARANTEED |
1 |
GENERAL DATA |
|
|
|
|
|
1.1 |
MANUFACTURER |
|
|
INDICATE |
|
HEMG |
1.2 |
MODEL |
|
|
INDICATE |
|
CHZ4 |
1.3 |
COUNTRY |
|
|
INDICATE |
|
CHINA |
1.4 |
STANDARD OF MANUFACTURE AND TESTS |
|
ANSI / IEEE 37,60 |
|
ANSI/IEEE37.80 |
1.5 |
MOUNTING |
|
Outdoor |
|
Outdoor |
1.6 |
SYSTEM |
|
Threephase |
|
Threephase |
1.8 |
ALTITUDE |
mosl |
|
3400 |
|
3500 |
1.9 |
Temperature of operation |
ºC |
-10 a 40 |
|
-10 a 40 |
2 |
CARACTERISTICAS DEL RECONECTADOR: |
|
|
|
|
|
2.1 |
Frequency |
Hz |
60 |
|
60 |
2.2 |
Nominal Current |
A |
600 |
|
600 |
2.3 |
Nominal Symmetric Interruption Current (3 Sec) |
kA |
16 |
|
16 |
2.4 |
Nominal Voltage of the system |
kV |
22.9 |
|
22.9 |
2.5 |
Voltage max of service |
kV |
24 |
|
24 |
2.6 |
Voltage of the Equipment |
kV |
28 |
|
28 |
2.7 |
BIL 1,2/50 us |
kVp |
|
200 |
|
200 |
2.8 |
Withstand voltaje industrial frequency. 1 minute.Dry |
kVef |
|
95 |
|
95 |
2.9 |
Withstand voltaje industrial frequency, 10 sec . Wet |
kVef |
|
60 |
|
60 |
2.1 |
Arc interruption way |
|
Vacuum |
|
Vacuum |
2.1 |
Insulation type of arc interruption way. |
|
Solid Dieléctric or resyn HCEP |
|
Solid Dielectric |
2.1 |
Current transformer , for protection |
|
125-250/1A,15VA, 5P20 |
|
125-250/1ª,15va,5p20 |
2.1 |
Current transformer , for measure |
|
125-250/1A,15VA, cl 0,2 |
|
125-250/1ª,15va,cl0.2 |
2.1 |
Six capacitive voltage sensors for voltage measurement per phase (Incorporated in the epoxy insulation), at the input and output of the Recloser |
|
Yes |
|
Yes |
|
- Accuracy of voltage amplitude |
|
± 2% |
|
±2% |
|
- Accuracy of angle of phase |
|
± 1% |
|
±1% |
2.2 |
Insulators |
|
Yes |
|
yes |
|
Manufacture |
|
|
|
|
hemg |
|
Material |
|
Resyn |
|
resin |
|
Type |
|
|
|
|
zsw |
|
Leakage distance / Voltage of Line |
mm/kV |
>=25 |
|
25 |
2.2 |
Max. Open time |
seg |
0.06 |
|
0.06 |
2.2 |
Max. Close time |
seg |
0.05 |
|
0.06 |
2.2 |
Pole operation |
|
SI |
|
yes |
2.2 |
Number of electric operations |
|
>=10000 |
|
10000 |
2.2 |
Number of mechanicall operations |
|
>=10000 |
|
10000 |
2.2 |
Indicator of position OPEN-CLOSE visible from the soil. |
|
Yes |
|
yes |
2.2 |
Equipment with lifting hook |
|
Yes |
|
yes |
2.2 |
Type of operation mechanism |
|
Magnétic |
|
Magnetic |
3 |
CHARACTERISTICS OF ELECTRONIC CONTROL |
|
|
|
|
|
3.1 |
Manufacturer |
|
|
|
|
HEMG |
3.2 |
Model |
|
|
|
|
CHZ4 |
3.3 |
Country |
|
|
|
|
CHINA |
3.4 |
Standards |
|
ANSI / IEEE 37,90 |
|
ANSI/IEEE37.90 |
3.5 |
Operation principle |
|
Microprocessor |
|
NICROPROCESSOR |
3.6 |
Functions of protection (*) |
|
|
|
|
|
|
-Overcurrent of phases |
50/51 |
Yes |
|
50/51 |
|
- Overcurrent phase to ground |
50N/51N |
Yes |
|
50N/51N |
|
- Overcurrent directional |
67/67N |
Yes |
|
60/67N |
|
- Sensitive ground fault |
SEF |
Yes |
|
SEF |
|
- Función de sobre tensión |
59 |
Yes |
|
59 |
|
- Function of homopolar voltage |
59N |
Yes |
|
59N |
|
- Functions failure of the breaker |
51BF |
Yes |
|
51BF |
|
- Function of frequency |
81 O/U |
Yes |
|
81O/U |
|
- Reclose |
79 |
Yes |
|
79 |
3.7 |
Minimum trips currents |
|
|
|
|
|
- Failure between phases |
Amp |
25 |
|
25 |
|
- Failure to ground |
Amp |
5 |
|
5 |
3.6 |
Recloser Status Indicator |
|
Yes |
|
YES |
3.7 |
Oscillographic record in Contrade format.
|
|
Yes |
|
YES |
3.8 |
Fault locator |
|
Yes |
|
YES |
3.9 |
Event storage |
|
Yes |
|
YES |
3.1 |
Parameter display template |
|
Yes |
|
YES |
3.1 |
Digital imputs |
|
Yes |
|
YES |
3.1 |
Digital outputs |
|
Yes |
|
YES |
3.1 |
IRIG-B port time synchronization. |
|
Yes |
|
YES |
3.1 |
Elements of protection and blocking of harmonic currents |
|
Yes |
|
YES |
3.2 |
Monitoring of the 3 voltage inputs |
|
Yes |
|
YES |
3.2 |
Sag / Swell voltage recording for power quality analysis |
|
Yes |
|
YES |
3.2 |
Auxiliary Source of Energy and Autonomy |
|
Battery (24 V) |
|
YES |
4 |
COMUNICATIONS |
|
|
|
|
|
4.1 |
Communications protocol for sending to the Scada |
|
DNP3 (TCP/IP) and IEC 61850 |
|
DNP AND IEC61850 |
|
4.2 |
RS232 and RS485 communication port (**) |
|
Yes |
|
YES |
4.3 |
Sending of digital signals through communications port at protection speed |
|
Yes |
|
YES |
4.4 |
RS232 communication port independent of the port for SCADA sending that allows communication between reclosers in a protocol in order to allow quick restoration schemes in the event of a fault between two consecutive reclosers. |
|
Yes |
|
RJ45 |
4.5 |
Communication protocol that allows communication between reclosers in order to allow quick restoration schemes in the event of a fault between two consecutive reclosers (Include protocol characteristics) |
|
Attach the documents of the test report
|
|
YES ,BEFORE SHIPMENT |
5 |
ACCESORIES |
|
|
|
|
|
5.1 |
Metallic structure for mounting on electric station,include the anchor bolts. |
|
Yes |
|
YES |
5.2 |
04 Interface cables for PC configuration |
|
Yes |
|
YES |
5.3 |
Configuration software (unlimited licenses), event analysis and management of electronic control |
|
Yes |
|
YES |
5.4 |
Surge arresters 21kV 10kAmp |
|
Yes |
|
YES |
5.5 |
Groundind to earth <10 ohm guaranteed |
|
Yes |
|
YES |
|
Spare parts |
|
|
|
|
|
5.6 |
Battery |
|
1 |
|
1 |
5.7 |
Front panel face masks |
each |
2 |
|
2 |
(*) Protection curves according to ANSI, IEC, own and user-defined standards
(**) The electronic control shall have an RS-485 or higher communication port for data transmission to the SCADA. |