• 11kv (15KV) 50Hz/60Hz Outdoor Pole Mounted Capacitor Bank with Arrester and with Drop out Fuse
  • 11kv (15KV) 50Hz/60Hz Outdoor Pole Mounted Capacitor Bank with Arrester and with Drop out Fuse
  • 11kv (15KV) 50Hz/60Hz Outdoor Pole Mounted Capacitor Bank with Arrester and with Drop out Fuse
  • 11kv (15KV) 50Hz/60Hz Outdoor Pole Mounted Capacitor Bank with Arrester and with Drop out Fuse

11kv (15KV) 50Hz/60Hz Outdoor Pole Mounted Capacitor Bank with Arrester and with Drop out Fuse

Type: Polypropylene Capacitor
Application: Power
Packaging Type: Through Hole
Capacitance: >100uf
Structure: Fixed Capacitor
Manufacturing Material: Polypropylene
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
TBB
Electrolyte
Electrolytic
Usage
High Frequency Coupling
Transport Package
Wooden
Specification
11KV 100KVAR
Trademark
HEMG
Origin
China
Production Capacity
500000

Product Description

11kv (15KV) 50Hz/60Hz Outdoor Pole Mounted Capacitor Bank with Arrester and with Drop out Fuse
 
  1. Capacitor Unit for installing at 11kV Existing Overhead Feeder (3x100 KVAR)
 
Sl. No. Description Unit                    Requirement Manufacturers Particulars
  General Information
  1.  
Reference standard - IEC 60871 IEC60871
  Operational Data
  1.  
Rated System Voltage kV 11 11
  1.  
Maximum System Voltage kV 12 12
  1.  
Rated Frequency Hz 50 50
  1.  
System neutral - Effectively earth EFFECTIVELY EARTH
  Capacitor Unit      
  1.  
Name of the manufacturer - To be mentioned HEMG
  1.  
Address of manufacturer - To be mentioned NINGBO
  1.  
Country of origin - To be mentioned CHINA
  1.  
Country of manufacture - To be mentioned CHINA
  1.  
Year of manufacture of the devices to be supplied - not before 2018 2018
  1.  
Type - Naturally cooled static type shunt Power Capacitors NATURALLY COOLED STATIC TYPE SHUNT POWER CAPACITORS
  1.  
Model No. - To be mentioned  
  1.  
Rated voltage of individual capacitor kV 12 12
  1.  
Design overvoltage withstand rating (Phase to Phase) kV 13.8 13.8
  1.  
Rated capacity of individual capacitor KVAR 100 100
  1.  
Maximum permissible capacity of individual capacitor at 13.8 kV KVAR To be mentioned 121
  1.  
Capacitance of individual capacitor F To be mentioned 7.9uF
  1.  
Capacity of each bank (Consisting of three individual units) KVAR 300 300
  1.  
Rated current of individual capacitor Ampere 15.74 15.74
  1.  
Maximum current rating Ampere 1.3 time of rated current 1.3
  1.  
Minimum Basic Insulation Level
(Full wave 1.2 x 50 micro sec. wave)
kV 75 75
  1.  
Power frequency withstand voltage (wet, 60 sec.) of each capacitor kV 28 28
  1.  
Over voltage rating at Power frequency - 1.15 times rated voltage continuously 1.15
  1.  
Switching voltage under Transient over voltage rating and condition kV 3.25 times rated voltage for 4000 transient/ year 3.25
  1.  
Switching current under Transient over voltage rating and condition Ampere 400 times rated current for 4000 transient/ year 400
  1.  
Built in Discharge Resistor - Yes YES
  1.  
Value of the discharge resistor ohm To be mentioned 10MOhm
  1.  
Maximum time required for capacitor-unit internal discharge devices alone (without the aid of external discharge paths) to discharge the capacitor per phase voltage from rated voltage to 50 V. minutes 5 5
  1.  
Maximum total losses per KVAR W/ KVAR 0.10 0.1
  1.  
Type of electrode - Aluminium Foil ALUMINIUM FOIL
  1.  
Dielectric - Polypropylene film POLYPROPYLENE FILM
  1.  
Impregnating medium
Type
- non PCB, non toxic, biodegradable NON PCB,NON TOXIC BIOGEGRADABLE
  1.  
Installation - Outdoor, Pole mounted, on existing 11kV Overhead feeder. OUTDOOR ,POLE MOUNTED ON EXISTING 11KV OVERHEAD FEEDER
  1.  
Mode of connection - Delta DELTA
  1.  
Weight of each capacitor unit kg to be mentioned 30
  1.  
Ingress Protection   IP 66 IP66
  1.  
Overall dimensions of each capacitor
i. height mm to be mentioned 207
ii. depth mm to be mentioned 207
iii. width mm to be mentioned 380
  1.  
Protection - Fuse cut-out, Dropout type and Lightning arrester (LA) FUSE CUT-OUT ,DROPOUR TYPE AND LIGHTNING ARRESTER
  1.  
3 years of minimum Warranty period   Yes YES
  1.  
Mounting   On single pole (SPC or Steel Pole) ON SINGLE POLE
  Bushing
  1.  
Material - Polymer, glazed POLYMER
  1.  
Creepage distance mm/kV 50 50
  1.  
Rated current Ampere 25 26
  1.  
No. of Bushings for each capacitor nos. 2 2
  Structure
(Complete in all respect for installation in existing SPC or  Steel Pole)
  1.  
List of hardware item to be supplied for installation of each set of      
i. Capacitor bank (Consisting of three individual capacitor units) - List down the name and quantity of necessary hardware material YES
ii. Protection unit (3 nos. of DOFC and 3 nos. of LA) - List down the name and quantity of necessary hardware material YES
  Connection Cable with Lugs
  1.  
Type - PVC insulated Copper cable YES
  1.  
Size - To be mentioned 25mm2
  1.  
Quantity for      
i. Connection between 11kV line and Each capacitor unit through DOFC meter 3
(i.e, 9 meter for each capacitor bank)
YES
ii. Connection between each DOFC and each LA meter 0.5
(i.e, 1.5 meter for each capacitor bank)
YES

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now