• 27kv Line Surge Arrester for Distribution and Overhead Line
  • 27kv Line Surge Arrester for Distribution and Overhead Line
  • 27kv Line Surge Arrester for Distribution and Overhead Line

27kv Line Surge Arrester for Distribution and Overhead Line

Type: Power Source Arrester
Structure: Zinc Oxide Arrester
Installation: Tandem Arrester
Application: AC/DC System
Size: Meidum
Operation Voltage: High Voltage
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
Y10W
Material
ZnO
Certification
ISO9001
Transport Package
Wooden
Specification
66KV/132KV
Trademark
HEMG
Origin
China
Production Capacity
50000

Product Description

27kv Line Surge Arrester for Distribution and Overhead Line
  1. TABLE OF MINIMUM TECHNICAL DATA
    ZINC 27 KV METALLIC OXIDE LINE ARRESTOR
    ITEM DESCRIPTION UNIT REQUIRED GUARANTEED
    1 1 GENERAL DATA      
    1.1 Manufacturer   INDICATE HEMG
    1.2 Country of Origin   INDICATE CHINA
    1.3 Model   INDICATE YH10W-27
    1.4 Type   OZN ZNO Lightning arrester
    1.5 Standard   IEC 60099-4 IEC 60099-4
    1.6 Mounting   OUTDOOR OUTDOOR
    1.7 Class 2   2 2
    1.8 Installation altitude m.s.n.m. MOSL MAJOR THAN 4000 4000
    1.9 Type of conductor of the  line   OUTDOOR OUTDOOR
    1.10. Line conductor section (*)  MM2 25 TO 120 25 TO 120
    2 NOMINAL DATA AND CHARACTERISTICS      
    2.1 Rated frequency (fr)  HZ 60 60
    2.2 System voltage kV  KV 22.9 22.9
    2.3 Rated voltage (Ur)  KV 27 27
    2.4 Continuous operating voltage (MCOV) KV 22 22
    2.5 Temporary overvoltage at 1 s. KV 30 30
    2.6 Rated discharge current KA 10 10
    2.7 Energy dissipation capacity (double pulse) kJ / kV KJ/KV 4.5@UR MIMIMUM 4.75
    2.8 Maximum residual voltage to the maneuver type impulse at 500 A KV 57 57
    2.9 Maximum residual voltage to the atmospheric discharge impulse to:      
      5kA  KV 67 67
      10kA  KV 72 72
      20kA  KV 80 80
    2.10. Body Isolator Silicone Rubber   SILICON RUBBER SILICON RUBBER
    2.11 The BIL of the equipment to be protected KV 170 170
    2.12 Permissible static and dynamic load According to IEC 60099-4 Second Edition (2004-5) Nm INDICATE 500
    2.13 LEAKAGE  DISTANCE MM 1000 1000
    2.14 Metal parts protected against corrosion by hot dip galvanizing   YES YES
    2.15 Type test (delivery of similar lightning conductor certificate   YES YES
    2.16 Integrated Disconnector with Impeller Cartridge according to IEC   YES YES
    2.17 Connection terminal to conductor type staple suspension for live line work with installation with shotgun type   YES YES
    2.18 Grounding accessories that should include: 25 mm2 copper wire, shackles and connectors suitable for grounding.   YES YES
    3 COMPLEMENTARY INFORMATION      
    3.1 Dimensional plane equipment   YES YES
    3.2 Drawing of the rating plate   YES YES
    3.3 Complete connection and metering plan from the clamp to the ground connection.   YES YES
      (*) You should consider 30 staples from 70 to 120 mm2 and the rest from 35 to 70 mm2     YES
  2.  
  3.  
  4.  
  5.  
  6. Specification of MCOV 106/290,10KA LINE Lightning arrestor
1 GENERAL DATA Unit Data
1.1 MODEL   Y10W
1.2 TYPE   OZN METALLIC
1.3 STANDARD   IEC 60099-4
1.4 INSTALLATION   OUTDOOR
1.5 ALTITUDE OF INSTALLATION m.s.n.m. 1600
1.6 TYPE OF CABLE OF LINE   AAAC
1.7 SECTION OF THE CABLE mm2 185, 211 and 240
2 CHARACTERISTICS    
2.1 Frequency (f) Hz 60
2.2 Voltage of the system kV 145
2.3 Nominal Voltage (Ur) kV 132
2.4 Continuous operating voltage (MCOV). kV 106
2.5 Temporary overvoltage at 1s. KV (minimum) 149
2.6 Nominal discharge current. kA 10
2.7 Energy dissipation capacity (double impulse). KJ/KV (minimum) 4.5 @ Ur
2.8 Maximum residual voltage to the maneuver type impulse at 1000A. kV 290
2.9 Maximum residual voltage to the atmospheric discharge impulse to:    
  5 kA kV(maximum) 330
  10 kA kV(maximum) 355
  20 kA kV(maximum) 390
2.10 Housing of the insulator (body)   Silicon rubber
2.11 Insulation level of the surge arrester kV(minimum) 650
2.12 Permissible static and dynamic load according to IEC 60099-4. Nm 6000
2.13 Leakage distance mm (minimum) 3800
2.14 Metal parts protected against corrosion by hot galvanizing.   Yes
2.15 Type test (delivery of similar lightning conductor certificate).   Yes
2.16 Disconnection device between the lightning arrestor and earth in case of failure of the lightning conductor, acting according to the inverse time curve current vs time (presenting curve).   Yes
2.17 Complete accessory for the installation of the lightning conductor from the arrester to the grounding.   Yes
2.18 Connection terminal to phase conductor type suspension clamp.   Yes
  Brand.   HEMG
  Manufacturer's catalog number (this number should be engraved in high relief on the clamp).   CT2018XXXX
  Tinned copper flexible cable   YES
  Material.   AAAC
  Section of the line cable mm2 185-240
  Range of angle of use. ° 30
  Burst load and minimum slip Kn 111
  Standard of manufacture ASTM 153, IEEE C135.61 or similar   IEEE C135.61
2.19 Downhill hardware and grounding accessories that should include: shackles and connectors suitable for grounding.   YES
  Brand.   HEMG
2.20 Flexible tinned copper cable.   YES
  Brand.   HEMG
  Cable for grounding (section) mm2 (minimum) 25MM2
  Cable length per surge arrester  m (minimum) 5M
 
  1. Specification of MCOV 57/156,10KA LINE Lightning arrestor
ITEM DESCRIPCION UNIT DATA
1 GENERAL DATA    
1.1 Model.   Y10W
1.4 Kind.   OZN
1.5 Standard   IEC60099-4
1.6 Installation   OUTDOOR
1.8 Altitude of Installation. m.o.s.l 4500
1.9 Type of line cable   AAAC
1.1 Line conductor section. mm2  70-120
2 NOMINAL DATA AND CHARACTERISTICS.    
2.1 Assigned frequency (f). hz 60
2.2 System Voltage kv 60
2.3 Rated voltage (Ur). kv 72
2.4 Continuous operating voltage (MCOV). kv 57
2.5 Temporary overvoltage at 1s. kv (minimum) 81
2.6 Nominal discharge current. ka 10
2.7 Energy dissipation capacity (double impulse). kj/kv (minimum) 4.5@UR
2.8 Maximum residual voltage to the maneuver type impulse at 1000A. kv 157
2.9 Maximum residual stress to the atmospheric discharge impulse to:    
  - 5 kA. KV (max) 178
  -10 kA. KV (max) 192
2.1 -20 kA. KV (max) 211
2.11 Body isolator.   SILICON RUBBER
2.12 Isolation level of the lightning conductor. N-m 6000
Permissible static and dynamic load according to IEC 60099-4.
2.13 leakage distance mm 2300
2.14 Metal parts protected against corrosion by hot galvanizing   YES
2.15 Type test (delivery of similar lightning rod certificate)   YES
2.16 Disconnection device between the lightning arrestor and earth in case of failure of the lightning conductor, acting according to the inverse time curve current vs time (presenting curve).   YES
2.17 Complete accessory for the installation of the lightning conductor from the driver to the grounding.   YES
2.18 Connection terminal to suspension type staple phase conductor   YES
  Brand   HEMG
  Manufacturer's catalog number (this number must be engraved in high relief on the staple)   CT2018XXXX
  Material   ALUMINUM ALLOY
  cable section   70-120
  Usage angle range   30
  Breakage load and minimum slip   76
  Manufacturing standard   ASTM153/IEEEC135.61
   
2.19 Downhill hardware and grounding accessories that should include: shackles and connectors suitable for grounding   YES
  Brand   HEMG
2.2 Tinned copper flexible cable   YES
  BRAND   HEMG
  SECTION OF THE CABLE MM2 MINIMUM 25
  LENGHT OF THE CABLE FOR EACH SURGE ARRESTER MTS (MINIMUM) 5
3.3 Plate of characteristics plate   YES