Basic Info.

Model NO.
GW1A
Installation
Outdoor High-voltage
Operation
Manual
Certification
ISO, IS9001
Transport Package
Wooden
Specification
400A, 600A, 1250A
Trademark
HEMG
Origin
China
Production Capacity
50000

Product Description






15kv/27kv/38kv 400A/600A/1200A Extinction Isolator Switch for Pole Mounted
15kv/27kv/38kv 400A/600A/1200A Extinction Isolator Switch for Pole Mounted

GW1A-12KV/24KV/33KV-4001/600A/1250A
 Outdoor Pole Mounted Disconnector
1 ,Product overview
1.1 Application
    GW1A type outdoor AC high voltage isolation switch is AC 50Hz/60Hz outdoor device, is used in below 33 kv the supply network, for high voltage line and under the situation with voltage, as well as on the maintenance of high voltage bus, circuit breakers and other electrical equipment with high voltage line charged electrical isolation. But also switch small capacitance current and inductive current.
This product is divided into regular and anti-pollution type two kinds.
CJ6 Motor or CS8-5 rainproof type manual.
This product can be with Arc Extinction Horn or Chamber
This product can be with Conductor in Cable or Soft Busbar
This product cab be with Fuse or without Fuse
1.2 Environmental
  1. Altitude≤2000m,more higher ,should be redesigning by sea level
  2. Ambient air temperature:-40≤T≤ +50ºC;
  3. Wind pressure ≤700Pa;
  4. Seismic intensity ≤8 degree;
  5. Radial thickness of ice≤10mm;

2 ,Main technical parameters                                      Pic 1
Technical sheet
 
Item
GW2-12W GW1-24W GW1-38W
Ur  kV 10 20 33
  Volts RMS  kV  12 24 38
Rated insulation level 1Min power frequency withstand voltage kV(RMS) to earth 40 50 70
Fracture 47 60 80
lightning impulse withstand voltage kV(peak value) to earth 105 125 170
Fracture 120 145 195
Rated frequency Hz 50/60
Rated current A 200,400,630,1250
The thermal stability of current 4 seconds kA(RMS) 6.3,12.5,20,31.5
Dynamic current kA(peak value)  16,31.5,50,80
operating mechanism   CJ6 Motor or CS8-5 rainproof type manual
With Fuse 50A,100A,200A OR NONE
Conductor CABLE OR SOLF BUSBAR
3, Construction
    This disconnector(Size as shown in figure 1)is the three-phase on one chassis  knife switch, or made up of three single phase.As shown, can be divided into the chassis, insulator and conductive parts, chassis by the rotor and the bending of plate and Angle steel welded frame, chassis fixed six porcelain insulator, and every two composition, mounted on the rotating shaft three-phase insulator to operate, and close movement used to operating three-phase knife, conductive part is composed of contactor, knife and contact, with the spring pressure.
    Break-brake in turn by the operating arm shaft rotates, operating insulator up divide the knife and contact with the knife, knife touch the revolving around, contact also in knife leads up to the gate location.