ITEM A | CURRENT TRANSFORMER FOR MEDIUM VOLTAGE THREE PHASE TYPE BLOCK SUPPORT FOR MEASURE | |||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | MANUFACTURER | INDICATE | HEMG | |
2 | MODEL | INDICATE | LZW-12 | |
3 | TYPE | BLOCK - SUPPORT | BLOCK - SUPPORT | |
4 | POWER | VA | 15 | 15 |
5 | RELATION OF TRANSFORMATION | A | 600-300/5 | 600-300/5 |
VOLTAGE OF OPERATION | KV | 10 | 10 | |
6 | TYPE OF CONNECTION | STAR | STAR | |
7 | PRECISION CLASS | 0.2S (EXTENDED RANGE) | 0.2S | |
8 | FREQUENCY | HZ | 60 | 60 |
9 | NUMBER OF FASES | 1 | 1 | |
10 | INSULATION CLASS | "F" ( EPOXY RESIN) | "F" ( EPOXY RESIN) | |
11 | COOLING. | AN | AN | |
12 | LEVEL OF INSIDE INSULATION ON THE PRIMARY SIDE. | KV | 17.5 | 28 |
13 | LEVEL OF INSIDE INSULATION ON THE SECONDARY SIDE. | KV | 1.1 | 3 |
14 | APPLICATION. | MEASURE | MEASURE | |
15 | MOUNTING. | OUTDOOR | OUTDOOR | |
16 | SERVICE. | CONTINUE | CONTINUE | |
17 | MANUFACTURING STANDARD. | IEC PUB. 61869 -2 | IEC PUB. 61869 -2 | |
18 | THERMAL CURRENT (Ith). | 100 X IN | 100 X IN | |
19 | DYNAMIC CURRENT (Idyn). | 2.5 X Ith | 2.5 X Ith | |
20 | INSULATION SIDE OF HIGH VOLTAGE-VOLTAGE. | MOHM | 10,000 | 10,000 |
21 | ISOLATION HIGH VOLTAGE SIDE - EARTH. | MOHM | 10,000 | 10,000 |
22 | INSULATION LOW VOLTAGE SIDE - EARTH. | MOHM | 1,000 | 1,000 |
23 | TERMINAL FOR GROUNDING CONNECTION. | YES | YES | |
24 | NAMEPLATE. | YES | YES | |
25 | METAL BASE FOR FIXING. | YES | YES | |
26 | OUTPUT TERMINALS ON CURRENT CIRCUITS. | YES | YES | |
27 | INSTALLATION MANUAL AND MANUFACTURER TEST REPORT ON EACH EQUIPMENT AT DELIVERY MOMENT. | YES | YES |
ITEM B | CURRENT TRANSFORMER FOR HIGH VOLTAGE THREE PHASE TYPE BLOCK SUPPORT FOR MEASURE | |||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | MANUFACTURER | INDICATE | HEMG | |
2 | MODEL | INDICATE | LZW-36 | |
3 | TYPE | BLOCK - SUPPORT | BLOCK - SUPPORT | |
4 | POWER | VA | 15 | 15 |
5 | RELATION OF TRANSFORMATION | A | 150-100/5 | 150-100/5 |
VOLTAGE OF OPERATION | KV | 33 | 33 | |
6 | TYPE OF CONNECTION | STAR | STAR | |
7 | PRECISION CLASS | 0.2S (EXTENDED RANGE) | 0.2S | |
8 | FREQUENCY | HZ | 60 | 60 |
9 | NUMBER OF FASES | 1 | 1 | |
10 | INSULATION CLASS | "F" ( EPOXY RESIN) | "F" ( EPOXY RESIN) | |
11 | COOLING. | AN | AN | |
12 | LEVEL OF INSIDE INSULATION ON THE PRIMARY SIDE. | KV | 38 | 70 |
13 | LEVEL OF INSIDE INSULATION ON THE SECONDARY SIDE. | KV | 1.1 | 3 |
14 | APPLICATION. | MEASURE | MEASURE | |
15 | MOUNTING. | OUTDOOR | OUTDOOR | |
16 | SERVICE. | CONTINUE | CONTINUE | |
17 | MANUFACTURING STANDARD. | IEC PUB. 61869 -2 | IEC PUB. 61869 -2 | |
18 | THERMAL CURRENT (Ith). | 100 X IN | 100 X IN | |
19 | DYNAMIC CURRENT (Idyn). | 2.5 X Ith | 2.5 X Ith | |
20 | INSULATION SIDE OF HIGH VOLTAGE-VOLTAGE. | MOHM | 10,000 | 10,000 |
21 | ISOLATION HIGH VOLTAGE SIDE - EARTH. | MOHM | 10,000 | 10,000 |
22 | INSULATION LOW VOLTAGE SIDE - EARTH. | MOHM | 1,000 | 1,000 |
23 | TERMINAL FOR GROUNDING CONNECTION. | YES | YES | |
24 | NAMEPLATE. | YES | YES | |
25 | METAL BASE FOR FIXING. | YES | YES | |
26 | OUTPUT TERMINALS ON CURRENT CIRCUITS. | YES | YES | |
27 | INSTALLATION MANUAL AND MANUFACTURER TEST REPORT ON EACH EQUIPMENT AT DELIVERY MOMENT. | YES | YES | |
ITEM B | CURRENT TRANSFORMER FOR HIGH VOLTAGE THREE PHASE TYPE BLOCK SUPPORT FOR MEASURE | |||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | MANUFACTURER | INDICATE | HEMG | |
2 | MODEL | INDICATE | LZW-36 | |
3 | TYPE | BLOCK - SUPPORT | BLOCK - SUPPORT | |
4 | POWER | VA | 15 | 15 |
5 | RELATION OF TRANSFORMATION | A | 150-100/5 | 150-100/5 |
VOLTAGE OF OPERATION | KV | 33 | 33 | |
6 | TYPE OF CONNECTION | STAR | STAR | |
7 | PRECISION CLASS | 0.2S (EXTENDED RANGE) | 0.2S | |
8 | FREQUENCY | HZ | 60 | 60 |
9 | NUMBER OF FASES | 1 | 1 | |
10 | INSULATION CLASS | "F" ( EPOXY RESIN) | "F" ( EPOXY RESIN) | |
11 | COOLING. | AN | AN | |
12 | LEVEL OF INSIDE INSULATION ON THE PRIMARY SIDE. | KV | 38 | 70 |
13 | LEVEL OF INSIDE INSULATION ON THE SECONDARY SIDE. | KV | 1.1 | 3 |
14 | APPLICATION. | MEASURE | MEASURE | |
15 | MOUNTING. | OUTDOOR | OUTDOOR | |
16 | SERVICE. | CONTINUE | CONTINUE | |
17 | MANUFACTURING STANDARD. | IEC PUB. 61869 -2 | IEC PUB. 61869 -2 | |
18 | THERMAL CURRENT (Ith). | 100 X IN | 100 X IN | |
19 | DYNAMIC CURRENT (Idyn). | 2.5 X Ith | 2.5 X Ith | |
20 | INSULATION SIDE OF HIGH VOLTAGE-VOLTAGE. | MOHM | 10,000 | 10,000 |
21 | ISOLATION HIGH VOLTAGE SIDE - EARTH. | MOHM | 10,000 | 10,000 |
22 | INSULATION LOW VOLTAGE SIDE - EARTH. | MOHM | 1,000 | 1,000 |
23 | TERMINAL FOR GROUNDING CONNECTION. | YES | YES | |
24 | NAMEPLATE. | YES | YES | |
25 | METAL BASE FOR FIXING. | YES | YES | |
26 | OUTPUT TERMINALS ON CURRENT CIRCUITS. | YES | YES | |
27 | INSTALLATION MANUAL AND MANUFACTURER TEST REPORT ON EACH EQUIPMENT AT DELIVERY MOMENT. | YES | YES | |