Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 8000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
A.- THREE PHASE RECLOSER 33 KV | ||||
ITEM | DESCRIPTION | UNIT | REQUIRED | GUARANTEED |
1 | RECLOSER | |||
1.01 | COUNTRY | TO INDICATE | CHINA | |
1.02 | MANUFACTURER | TO INDICATE | HEMG | |
1.03 | MODEL | TO INDICATE | CHZ4 | |
1.04 | STANDARD | ANSI C-37.60 | ANSI-37.60 | |
1.05 | TYPE | OUTDOOR | OUTDOOR | |
1.06 | SYSTEM | THREE PHASE | THREE PHASE | |
1.07 | OPERATION TYPE | AUTOMATIC AND MANUAL | AUTOMATIC AND MANUAL | |
1.08 | ALTITUDE OF OPERATION | MO.S.L | 2500 OR MORE | 4500 |
ELECTRIC CHARACTERISTICS | ||||
1.09 | OPERATION VOLTAGE | KV | 33 | 33 |
1.10 | MAX, VOLTAGE OF THE EQUIPMENT | KV | 38 | 38 |
1.11 | NOMINAL FREQUENCY | HZ | 60 | 60 |
1.12 | NOMINAL CURRENT | A | 630 | 630 |
1.13 | NOMINAL SYMETRIC INTERRPTION CURRENT | KA | 12.5 | 12.5 |
1.14 | SPECIFIC LEAKAGE DISTANCE | mm/KV | 31 | 31 |
1.15 | BIL | KV | 170 | 170 |
1.16 | DISCHARGE VOLTAGE, DRY, 60 HZ, 1 MINUTE | KV | 70 | 70 |
1.17 | DISCHARGE VOLTAGE, WET, 60 HZ, 10 SECONDS | KV | 60 | 60 |
1.18 | CYCLE OF WORK ACCORD ANSI C-37.60 | YES | YES | |
1.19 | INTERRUPTIION WAY | VACUUM | VACUUM | |
1.20 | INSULATION WAY | SOLID DIELECTRIC OR GAS SF6 | SOLID DIELECTRIC | |
1.21 | NUMBER OF ELECTRIC OPERATIONS | 10000 | 10000 | |
1.22 | CURRENT MEASURE | WITH CURRENT SENSORS | WITH CURRENT SENSOR | |
INSTALLATION | INDOOR | INDOOR | ||
SYSTEM | SINGLE PHASE | SINGLE PHASE | ||
1.23 | RELATION OF TRANSFORMATION | A | 400/1. | 400/1 |
1.24 | PRECISION | % | 1% | 1% |
1.25 | VOLTAGE MEASURE | VOLTAGE SENSORS INTERNAL | VOLTAGE SENSORS INTERNAL | |
1.26 | TYPE | CAPACITIVE | CAPACITIVE | |
1.27 | INSTALLATION | IN BUSHING | IN BUSHING | |
1.28 | PRECISION | % | 2.5 | 2.5 |
1.29 | QUANTITY | 6 | 6 | |
1.3 | SENSITIVE GROUND FAULT CURRENT DETECTION. | CURENT TRANSFORMER | CURRENT TRANSFORMER | |
INSTALLATION. | IN THE TANK (INSIDE THE TANK ) | IN TANK | ||
QUANTITY. | 1 | 1 | ||
TRANSFORMATION RELATION. | Ma | 200/1.5 | 200/1.5 | |
MECHANIC CHARACTERISTICS | ||||
1.3 | METALLIC HARDWARE | |||
MATERIAL | STAINLESS | STAINLESS | ||
STANDARD OF THE MATERIAL | ASTM A575 | ASTM A575 | ||
STANDARD OF HOT GALVANIZED | ASTM A 153 | ASTM A 153 | ||
THICKNEES OF GALAVANIZATION MIN | gr/CM2 | 800 | 800 | |
1.31 | MOUNTING | ON CIRCULAR POLE | ON CIRCULAR POLE | |
1.32 | MECHANISM OF OPERATION | MAGNETIC ACTUATOR | MAGNETIC ACTUATOR | |
1.33 | POSITION INDICATOR | VISIBLE FROM THE SOIL | VISIBLE FROM THE SOIL | |
1.34 | OPERATION BETWEEN POLE WITH HOOK | YES | YES | |
1.35 | MANUAL LOCKING EMERGENCY (ATTACHED DRAWING) | YES | YES | |
1.36 | TOOL PROVIDED WITH MANUAL CONTROL | YES | YES | |
1.37 | WITH LIFTING HOOKS | YES | YES | |
1.38 | INDICATES THE LIFE OF CONTACTS | YES | YES | |
1.39 | NUMBER OF MECHANICS OPERATION | 10000 OR MORE | 10000 OR MORE | |
1.40 | FULLY ASSEMBLED | YES | YES | |
1.41 | WEIGHT | |||
PRINCIPAL TANK | KG | TO INDICATE | 135 | |
CONTROL BOX | KG | TO INDICATE | 35 | |
2 | TANK | |||
2.01 | MATERIAL | STAINLESS STEEL | STAINLESS STEEL | |
CONSTRUCTION REQUIREMENTS | INDICATE THE STANDARD | INDICATE THE STANDARD | ||
2.02 | COATING OF TIN IN TERMINALS AND CONDUCTIVE PARTS. | 8 um | 8 um | |
2.03 | PROTECTION DEGREE | Able to withstand pressure fresh water cleaning insulators. | Able to withstand pressure fresh water cleaning insulators. | |
3 | BUSHINGS | |||
3.01 | COUNTRY | TO INDICATE | CHINA | |
3.02 | MANUFACTURER | TO INDICATE | HEMG | |
3.03 | STANDARD | ASTM D624, DIN 63504,IEC 60587,ASTM G154, AST G 155. | ASTM D624, DIN 63504,IEC 60587,ASTM G154, AST G 155. | |
3.04 | CHARACTERISTICS OF MANUFACTURE | |||
MATERIAL OF CORE | FIBER GLASS OR RESYN | RESYN | ||
INSULATION MATERIAL OF COVER HOUSING AND SHEDS | Cycloaliphatic EPOXY RESIN | Cycloaliphatic EPOXY RESIN | ||
ELONGATION AT BREAK | % | 450 ( ACCORD STANDARD DIN 53504 ) | 450 | |
3.05 | TEAR RESISTANCE. | N/M | MAJOR OF 20 ( Standard ASTM D624) | 20 |
3.06 | TRACKING AND EROSION RESISTANCE. | CLASS 2A,4.5 ( IEC 60587 ) | CLASS 2A,4.5 ( IEC 60587 ) | |
3.07 | TESTING OF RESISTANCE TO UV RAYS. | ACCORDING ASTM G154 AND ASTM G155 | ACCORDING ASTM G154 AND ASTM G155 | |
3.08 | RANGE OF SECTION OF DRIVERS. | 16 TO 120 MM2 | 16 TO 120 MM2 | |
3.09 | CONDUCTOR MATERIAL OF ELIGIBLE. | CU/AL , CU/CU , AL/AL | CU | |
4 | SYSTEM OF CONTROL AND PROTECTION | |||
4.01 | COUNTRY | SAME COUNTRY INDICATE POINT 1.1 | China | |
4.02 | STANDARD OF MANUFACTURE | ANSI / IEEE 37.90 | ANSI / IEEE 37.90 | |
4.03 | INSTALLATION | OUTDOOR | OUTDOOR | |
4.04 | MANUFACTURER | SAME MANUFACTURER INDICATE POINT 1.2 | HEMG | |
4.05 | CATALOGUE | TO INDICATE | English Version | |
4.06 | MODEL OF ELECTRONIC SYSTEM | TO INDICATE | CHZ4 | |
CONTROL BOX | ||||
4.07 | MATERIAL | STAINLESS STEEL | Stainless Steel | |
4.08 | THICKNESS | 2 MM | 2mm | |
4.09 | SURFACE | BRIGHT PASSIVATING | Bright Passivating | |
4.10 | COLOUR | TO INDICATE | RAL7035 | |
4.11 | PROTECTION DEGRE OF THE BOX | |||
CLOSE OPEN | IP65 | IP65 | ||
INSULATION VOLTAGE TO 1 MINUTE | 2 KV | 2KV | ||
INSULATION VOLTAGE TO IMPULSE | 6 KVp | 6 KVp | ||
SUPPORT TO INTERFERENCE TESTING ACCORDING TO STANDARDS: | SWC ANSI C37.90.1, IEC 61000-4-4- | IEC 61000-4-4 | ||
IMMUNITY TO INTERFERENCE RADIO WAVES. | IEC 255-22-3 CLASS, ANSI C37.90.2 | IEC 255-22-3 CLASS | ||
4.12 | WITH NAMEPLATE | YES | Yes | |
CHARACTERISTICS | ||||
4.13 | FUNCTION | WITH MICROPROCESSOR | Yes | |
4.14 | PRINCIPAL PROTECTIONS | 50/51,50N/51N,SEF,25,27,59,59N, 67 | 50/51,50N/51N,SEF,25,27,59,67 | |
4.15 | SECONDARY PROTECTIONS | 46.81 | 46/81 | |
4.16 | ADJUSTEMENT GROUPS | 2 MIN | 3 Groups | |
4.17 | MIN CURRENT OF SHOOT | |||
FAILURE BETWEEN PHASES | A | 20 or minor | ≤20A | |
FAILURE TO GROUND | A | 10 or minor | ≤10A | |
SENSITIVY FAILURE | A | 1 or minor | ≤1A | |
4.18 | SETTING ALLOWS PARAMETERS PROTECTION | YES | Setting can Parameter | |
IEC STANDARD CURVES | YES | IEC and IEEE curves | ||
CUSTOM CURVES | YES | IEC and IEEE curves | ||
4.19 | FAILURE TO GROUND | YES | Yes | |
4.20 | MINIMUN VOLTAGES | YES | 27 | |
4.21 | OVER VOLTAGE | YES | 59 | |
4.22 | STATUS INDICATOR OF RECLOSERS | |||
PARAMETERS | YES | Yes | ||
POSITION OF THE EQUIPMENTS | YES | Yes | ||
4.23 | ALLOWS STORAGE OPERATING EVENTS | |||
OPEN OR CLOSE | YES | Yes | ||
LOSS VOLTAGE | YES | Yes | ||
OPERATION CURRENT | YES | Yes | ||
4.24 | REPORT FUNCTIONS | |||
EVENT REGISTRATION NUMBER SYSTEM | 2048 | 4096 | ||
EVENT REGISTRATION NUMBER OF DIAGNOSIS | 512 | 1024 | ||
EVENT OF PERFIL LOAD REGISTRATION | 512 | 1024 | ||
REGSITER OF NUMBER OF SHOOTS | YES | Yes | ||
REGISTER OF COUNTER OF FAILURES | YES | Yes | ||
NUMER OF REGISTER WAVE FORM | 32 | 32 | ||
REGISTRATION FORM | COMTRADE or software application | Comtrade type | ||
4.25 | REPORT FUNCTIONS | |||
ERROR IN THE MEASUREMENT | Yes | |||
BEFORE FAILURE | 1% OR MINOR | ≤1% | ||
AFTER FAILURE | 3% OR MINOR | ≤1% | ||
MEASSUREMENTS OF INSTANTANEOUS VALUES | V,I,F,P,Q | V,I,F,PF,P,Q | ||
ACTIVE AND REACTIVE POWER | YES | Active and Reactive Counter | ||
4.26 | THE CONTROL MUST HAVE TO DISPLAY DATA AND ADJUSTMENT | YES | 4.3 inch Color LCD touch screen | |
4.27 | COMMUNICATIONS PROTOCOL (READY FOR INTEGRATION WITH SYSTEMS SCADA) | DNP 3.0 | DNP3.0 | |
4.28 | COMMUNICATION PORTS | |||
ETHERNET | YES | RJ45 | ||
COMMUNICATION WITH PERSONAL COMPUTER | RS232, ETHERNET | RJ45,Wi-Fi,Ethernet | ||
COMMUNICATION READ DATA | RS232, ETHERNET, RS485 | Ethernet and RS485 | ||
4.29 | OPTION be commanded remotely WITH RADIO MODEM OR GSM MODEM. | YES | GSM Modem | |
EFFORTS TO SAFE OPERATION. | YES | Yes | ||
INPUT AND OUTPUT NEEDED FOR THIS EFFECT. | YES | Yes | ||
4.3 | CONFIURATION SOFTWARE | |||
ENVIROMENT | WINDOWS | Windows | ||
SECURITY SYSTEM | WITH PASSWORD | With Password | ||
INFORMATION DISCHARGE | YES | Yes | ||
PROGRAMMING IN REMOTELY | YES | By Ethernet | ||
5 | AUXILIAR ENERGY FEEDER SYSTEM | |||
SYSTEM | SINGLE PHASE | |||
INCLUDE AUXILIAR TRANSFORMER FOR CONTROL BOX | YES | |||
5.01 | BATTERY | |||
COUNTRY | TO INDICATE | China | ||
MANUFACTURER | TO INDICATE | HEMG | ||
TYPE | TO INDICATE | NP7-12 | ||
NOMINAL VOLTAGE | TO INDICATE | DC24V | ||
NUMBER OF UNIT OPERATING VOLTAGE TO FAILURES. | 10 OR MORE | 2 | ||
MEASURING THE CONDITION OF THE BATTERY. | YES | Yes | ||
BATTERY LIFE IN FAILURE OF LACK OF VOLTAGE. | 48 HOURS | 48 Hours | ||
INCLUDED IN THE CABINET OF CONTROL | YES | Yes | ||
5.02 | SYSTEM OF CHARGE OF THE BATTERIES | |||
COUNTRY | TO INDICATE | China | ||
MANUFACTURER | TO INDICATE | HEMG | ||
AUXILIAR VOLTAGE | 220 VAC | AC 220V | ||
SYSTEM | SINGLE PHASE | Single Phase | ||
COMPATIBLE WITH SPECIFIED BATTERIES | YES | Yes | ||
INCLUDED IN THE CABINET OF CONTROL | YES | Yes |