| Customization: | Available |
|---|---|
| Application: | Power, Instrument, Rectifier |
| Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| ÍTEM | CHARACTERISTICS | UNITY | REQUIRED VALUE | OFFERED VALUE |
| 1 | General | |||
| Country | Specify | China | ||
| Manufacturer | Specify | HEMG | ||
| Manufacturing standards | IEC 60076-6 Acapite 10 IEC 60296 |
IEC 60076-6 Acapite 10 IEC 60296 |
||
| Type |
Submerged in oil or other superior insulation. | Submerged in oil | ||
| Main Nominal Voltage | kV | 22.9 | 22.9 | |
| Short-term neutral current | A | 300 | 300 | |
| Duration of neutral current of short duration | S | 10 | 10 | |
| Frequency | Hz | 60 | 60 | |
| Permanent neutral current | A | 10 | 10 | |
| Short time current to ground for 60 sec | KA | 25 | 25 | |
| Conservation system | Airtight with gas mattress | Airtight with gas mattress | ||
| Connection | Zigzag | Zigzag | ||
| Type of liquid | Natural Ester | mineral oil | ||
| Insulation system |
120° C (TUP Thermally enhanced paper)TUP | 120° C (TUP Thermally enhanced paper)TUP | ||
| Cooling Mode | ONAN | ONAN | ||
| 2 | Conditions of service | |||
| Altitude | msnm | <1000 | <1000 | |
| Air temperature |
°C |
28°C anytime | 28°C anytime | |
| 25°C Monthly average of the warmest month | 25°C Monthly average of the warmest month | |||
| 20°C Annual average | 20°C Annual average | |||
| 5°C minimum | 5°C minimum | |||
| Degree of pollution | mm/kV | 25 | 25 | |
| Seismic disturbance | g | Specify | 0.2 | |
| 3 | Temperature limits | |||
| Thermal class | °C | 105 | 105 | |
| Heating of the upper liquid | °C | 60 | 60 | |
| Average warming of windings | °C | 65 | 65 | |
| Warmest spot heating | °C | 78 | 78 | |
| 4 | Insulation level inside | |||
| Higher Material Voltage | kV | 24 | 24 | |
| Primary impulse voltage | kVpico | 50 | 50 |
| Applied voltage | kV | 125 | 125 | |
| 5 | External Insulation Level | |||
| Higher Material Voltage | kV | 36 | 36 | |
| Primary impulse voltage | kVpico | 170 | 170 | |
| Applied voltage | kV | 70 | 70 | |
| 6 | Guaranteed Parameters | |||
| Lost in vacuum | W | 500 | 500 | |
| Excitation current | % | 0.3 | 0.3 | |
| Homopolar impedance | /fase | 45 | 45 | |
| 7 | Weights and dimensions | |||
| Dielectric liquid weight | kg | Specify | 550 | |
| Total weight | kg | Specify | 1700 | |
| Length x Width x Height | mm | According to design | 1600x950x1300 | |
| 8 | Classification of atmosphere and coating | |||
| Class (NBR 11388) | Class II | Class II | ||
| system | Epoxi | Epoxi | ||
| 9 | Accessories | |||
| Oil level indicator without contacts | 1 Pz | Yes | Yes | |
| Contactless overpressure valve | 1 Pz | Yes | Yes | |
| Drain valve | 1 Pz | Yes | Yes | |
| Contactless bimetallic thermometer | 1 Pz | Yes | Yes | |
| Earthing bar (5x30mm) | 1 Pz | Yes | Yes | |
| Sudden pressure relay with a contact | 1 Pz | Yes | Yes | |
| Grounding Terminals | 1 Pz | Yes | Yes | |
| 10 | Testing | IEC | IEC | |
| 11 | Neutral Resistance | |||
| Insulation | Air | Air | ||
| Service | Exterior | Exterior | ||
| Nominal Voltage | kV | 22.9/√3 | 22.9/√3 | |
| Intensity of continuous service | A | 10 | 10 | |
| Short-term Intensity | A | 300-10 s | 300-10 s | |
| Resistance | ohm | 12 | 12 | |
| Metal enclosure |
AISI-304 stainless steel painted interior and exterior | AISI-304 stainless steel painted interior and exterior | ||
| Degree of protection | IP | IP23 | IP23 | |
| Resistive material |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto304 |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto |
||
| Normative | IEEE Std- 32 | IEEE Std- 32 | ||
| Construction |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws304,,. |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws |
||
| Application | Neutral Residence Zig Zag Z | Neutral Residence Zig Zag |
| Equipped with current transformer |
Toroidal current transformer 300/1A, 1.5 VA | Toroidal current transformer 300/1A, 1.5 VA | ||
| 12 | Protection System | |||
| Removable switch | kV | 24 kV | 24 kV | |
| Monitoring relay and fault detection with 50/51 and 50N / 51N function | GLB | Specify | satisfy | |
| Monitoring relay neutral resistance and resistance sensor.. | kV | Specify | satisfy |
| ÍTEM | CHARACTERISTICS | UNITY | REQUIRED VALUE | OFFERED VALUE |
| 1 | General | |||
| Country | Specify | China | ||
| Manufacturer | Specify | HEMG | ||
| Manufacturing standards | IEC 60076-6 Acápite 10 IEC 60296 |
IEC 60076-6 Acápite 10 IEC 60296 |
||
| Type |
Submerged in oil or other superior insulation. | Submerged in oil | ||
| Primary Nominal Voltage | kV | 20 | 20 | |
| Short-term neutral current | A | 300 | 300 | |
| Duration of the neutral current of short duration | S | 10 | 10 | |
| Frequency | Hz | 60 | 60 | |
| Permanent neutral current | A | 10 | 10 | |
| Short time current ground for 60 sec 60 | KA | 25 | 25 | |
| Conservation system | Airtight with gas mattress | Airtight with gas mattress | ||
| Connection | Zigzag | Zigzag | ||
| Type of liquid | Natural Ester | mineral oil | ||
| Insulation system |
120° C (TUP Thermally enhanced paper) | 120° C (TUP Thermally enhanced paper) | ||
| Cooling Mode | ONAN | ONAN | ||
| 2 | Conditions of service | |||
| Altitude | msnm | < 1000 | < 1000 | |
| Air temperature |
°C |
28°C anytime | 28°C anytime | |
| 25°C Monthly average of the warmest month | 25°C Monthly average of the warmest month | |||
| 20°C Annual average | 20°C Annual average | |||
| 5°C minimum | 5°C minimum | |||
| Degree of pollution | mm/kV | 25 | 25 | |
| Seismic disturbance | g | Specified | 0.2 | |
| 3 | Temperature limits | |||
| Thermal class | °C | 105 | 105 | |
| Heating of the upper liquid | °C | 60 | 60 | |
| Average warming of windings | °C | 65 | 65 | |
| Warmest spot heating | °C | 78 | 78 |
| 4 | Insulation level inside | |||
| Higher material Voltage | kV | 24 | 24 | |
| Primary impulse voltage | kVpico | 50 | 50 | |
| Applied voltage | kV | 125 | 125 | |
| 5 | External Insulation Level | |||
| Higher material Voltage | kV | 36 | 36 | |
| Primary impulse voltage | kVpico | 170 | 170 | |
| Applied voltage | kV | 70 | 70 | |
| 6 | Guaranteed Parameters | |||
| Lost in vacuum | W | 500 | 500 | |
| Excitation current | % | 0.3 | 0.3 | |
| Homopolar impedance | /fase | 40 | 40 | |
| 7 | Weights and dimensions | |||
| Dielectric liquid weight | kg | Specify | 500 | |
| Total weight | kg | Specify | 1600 | |
| Length x Width x Height ** | mm | According to design | 1600x900x1300 | |
| 8 | Classification of atmosphere and coating | |||
| Class(NBR 11388) | Class II | Class II | ||
| System | Epoxi | Epoxi | ||
| Surface Preparation | Sa 2 1/2 | Sa 2 1/2 | ||
| 9 | Accessories s | |||
| Oil level indicator without contacts | 1 Pz |
Yes | Yes | |
| Contactless overpressure valve | 1 Pz | Yes | Yes | |
| Drain valve | 1 Pz | Yes | Yes | |
| Contactless bimetallic thermometer | 1 Pz | Yes | Yes | |
| Earthing bar | 1 Pz | Yes | Yes | |
| Sudden pressure relay with a contact | 1 Pz | Yes | Yes | |
| Grounding Terminals | 1 Pz | Yes | Yes | |
| 10 | TESTING | IEC | IEC | |
| 11 | Neutral Resistance | |||
| Insulation | Air | Air | ||
| Service | Exterior | Exterior | ||
| Nominal Voltage | kV | 20/ √ 3 | 20/ √ 3 | |
| Intensity of continuous service | A | 10 | 10 | |
| Short-term current | A | 300-10 s | 300-10 s | |
| Resistance | ohm | 12 | 12 | |
| Metal enclosure |
Stainless steel AISI- 304 Painted inside and out 304 | Stainless steel AISI- 304 Painted inside and out | ||
| Degree of protection | IP | IP23 | IP23 | |
| Resistive material |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto304 |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto |
||
| Normative | IEEE Std- 32 | IEEE Std- 32 | ||
| Construction |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screwsAISI‐304(Fe‐Cr18 Ni10),,. |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws |
| Application | Neutral Resistance Zig Zag Z | Neutral Resistance Zig Zag Z | ||
| Equipped with current transformer |
Toroidal current transformer 300/1A, 1.5 VA | Toroidal current transformer 300/1A, 1.5 VA | ||
| 12 | Protection System | |||
| Removable switch | kV | 24 kV | 24 kV | |
| Monitoring relay and fault detection with 50/51 and 50N / 51N function | GLB | Specify | satisfy | |
| Neutral resistance monitoring relay and resistance sensor. | kV | Specify | satisfy |