• 22.9kv 60Hz/50Hz Zigzag Transformer with Netural Grounding Resistor
  • 22.9kv 60Hz/50Hz Zigzag Transformer with Netural Grounding Resistor

22.9kv 60Hz/50Hz Zigzag Transformer with Netural Grounding Resistor

Application: Power, Instrument, Rectifier
Phase: Three
Core: Core-type Transformer
Cooling Method: Oil-immersed Type Transformer
Winding Type: Two-winding Transformer
Certification: ISO9001-2000, ISO9001
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
ZIGZAG
Usage
Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer
Transport Package
Carton with Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description


 
 
TECHNICAL CHARACTERISTICS.
TABLE OF TECHNICAL DATA TRANSFORMER ZIG ZAG 22.9 KV - SET NUEVA CAJAMARCA.
ÍTEM CHARACTERISTICS UNITY REQUIRED VALUE OFFERED VALUE
1 General      
  Country   Specify    China
Manufacturer   Specify HEMG
Manufacturing standards   IEC 60076-6 Acapite 10
IEC 60296
 IEC 60076-6 Acapite 10
IEC 60296
 
Type
  Submerged in oil or other superior insulation.   Submerged in oil  
Main Nominal Voltage kV 22.9  22.9
Short-term neutral current A 300 300
Duration of neutral current of short duration S 10 10
Frequency Hz 60 60
Permanent neutral current A 10 10
Short time current to ground for 60 sec KA 25 25
Conservation system   Airtight with gas mattress Airtight with gas mattress
Connection   Zigzag Zigzag
Type of liquid   Natural Ester mineral oil
 
Insulation system
  120° C (TUP Thermally enhanced paper)TUP 120° C (TUP Thermally enhanced paper)TUP
Cooling Mode   ONAN ONAN
2 Conditions of service      
  Altitude msnm <1000 <1000
 
 
Air temperature
 
 
°C
28°C anytime 28°C anytime
25°C Monthly average of the warmest month 25°C Monthly average of the warmest month
20°C Annual average 20°C Annual average
5°C minimum 5°C minimum
Degree of pollution mm/kV 25 25
Seismic disturbance g Specify  0.2
3 Temperature limits      
  Thermal class °C 105 105
Heating of the upper liquid °C 60 60
Average warming of windings °C 65 65
Warmest spot heating °C 78 78
4 Insulation level inside      
  Higher Material Voltage  kV 24 24
Primary impulse voltage kVpico 50 50
 
33
 
 
  Applied voltage kV 125 125
5 External Insulation Level      
  Higher Material Voltage kV 36 36
Primary impulse voltage kVpico 170 170
Applied voltage kV 70 70
6 Guaranteed Parameters      
  Lost in vacuum W 500 500
Excitation current % 0.3 0.3
Homopolar impedance /fase 45 45
7 Weights and dimensions      
  Dielectric liquid weight kg Specify 550
Total weight kg Specify 1700
Length x Width x Height mm According to design 1600x950x1300
8 Classification of atmosphere and coating      
  Class (NBR 11388)   Class II Class II
system   Epoxi Epoxi
9 Accessories      
  Oil level indicator without contacts 1 Pz Yes Yes
Contactless overpressure valve 1 Pz Yes Yes
Drain valve 1 Pz Yes Yes
Contactless bimetallic thermometer 1 Pz Yes Yes
Earthing bar (5x30mm) 1 Pz Yes Yes
Sudden pressure relay with a contact 1 Pz Yes Yes
Grounding Terminals 1 Pz Yes Yes
10  Testing   IEC IEC
11 Neutral Resistance      
  Insulation   Air Air
  Service   Exterior Exterior
  Nominal Voltage kV 22.9/√3 22.9/√3
  Intensity of continuous service A 10 10
  Short-term Intensity A 300-10 s 300-10 s
  Resistance ohm 12 12
   
Metal enclosure
  AISI-304 stainless steel painted interior and exterior AISI-304 stainless steel painted interior and exterior
  Degree of protection IP IP23 IP23
   
Resistive material
  Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%;
Fe resto304
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%;
Fe resto
  Normative   IEEE Std- 32 IEEE Std- 32
   
 
 
 
 
Construction
  Stainless steel stamped grills AISI304 (FeCr18
Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws304,,.
Stainless steel stamped grills AISI304 (FeCr18
Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws
  Application   Neutral Residence Zig Zag Z Neutral Residence Zig Zag
 
 

 
 
 
   
Equipped with current transformer
  Toroidal current transformer 300/1A,  1.5 VA Toroidal current transformer 300/1A,  1.5 VA
12 Protection System      
  Removable switch kV 24 kV 24 kV
  Monitoring relay and fault detection with 50/51 and 50N / 51N function GLB Specify  satisfy
  Monitoring relay neutral resistance and resistance sensor.. kV Specify satisfy
 
 
TABLE OF TECHNICAL DATA TRANSFORMER ZIG ZAG 20KV - SET RIOJA.
ÍTEM CHARACTERISTICS UNITY REQUIRED VALUE OFFERED VALUE
1 General      
  Country   Specify China
 Manufacturer   Specify HEMG
Manufacturing standards   IEC 60076-6 Acápite 10
IEC 60296
IEC 60076-6 Acápite 10
IEC 60296
 
Type
  Submerged in oil or other superior insulation. Submerged in oil
Primary Nominal Voltage kV 20 20
Short-term neutral current A 300 300
Duration of the neutral current of short duration S 10 10
Frequency Hz 60 60
Permanent neutral current A 10 10
Short time current ground for 60 sec 60 KA 25 25
Conservation system   Airtight with gas mattress Airtight with gas mattress
Connection   Zigzag Zigzag
Type of liquid   Natural Ester mineral oil
 
Insulation system
  120° C (TUP Thermally enhanced paper) 120° C (TUP Thermally enhanced paper)
Cooling Mode   ONAN ONAN
2 Conditions of service      
  Altitude msnm < 1000 < 1000
 
 
Air temperature
 
 
°C
28°C anytime 28°C anytime
25°C Monthly average of the warmest month 25°C Monthly average of the warmest month
20°C Annual average  20°C Annual average
5°C minimum  5°C minimum
Degree of pollution mm/kV 25 25
Seismic disturbance g Specified             0.2
3 Temperature limits      
  Thermal class °C 105 105
Heating of the upper liquid °C 60 60
Average warming of windings °C 65 65
Warmest spot heating °C 78 78
 
35
 
 
 
4 Insulation level inside      
  Higher material Voltage kV 24 24
Primary impulse voltage kVpico 50 50
Applied voltage kV 125 125
5 External Insulation Level      
  Higher material Voltage kV 36 36
Primary impulse voltage kVpico 170 170
Applied voltage kV 70 70
6 Guaranteed Parameters      
  Lost in vacuum W 500 500
Excitation current % 0.3 0.3
Homopolar impedance /fase 40 40
7 Weights and dimensions      
  Dielectric liquid weight kg Specify       500
Total weight kg            Specify        1600
Length x Width x Height ** mm According to design 1600x900x1300
8 Classification of atmosphere and coating      
  Class(NBR 11388)   Class II Class II
System   Epoxi Epoxi
Surface Preparation   Sa 2 1/2 Sa 2 1/2
9 Accessories s      
  Oil level indicator without contacts 1 Pz
 
 
 
Yes Yes
Contactless overpressure valve 1 Pz Yes Yes
Drain valve 1 Pz Yes Yes
Contactless bimetallic thermometer 1 Pz Yes Yes
Earthing bar 1 Pz Yes Yes
Sudden pressure relay with a contact 1 Pz Yes Yes
Grounding Terminals 1 Pz Yes Yes
10 TESTING   IEC IEC
11 Neutral Resistance      
  Insulation   Air Air
  Service   Exterior Exterior
  Nominal Voltage kV 20/  √ 3 20/  √ 3
  Intensity of continuous service A 10 10
  Short-term current A 300-10 s 300-10 s
  Resistance ohm 12 12
   
Metal enclosure
  Stainless steel AISI- 304 Painted inside and out 304 Stainless steel AISI- 304 Painted inside and out
  Degree of protection IP IP23 IP23
   
Resistive material
  Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%;
Fe resto304
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%;
Fe resto
  Normative   IEEE Std- 32 IEEE Std- 32
   
 
 
Construction
  Stainless steel stamped grills AISI304 (FeCr18
Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screwsAISI304(FeCr18 Ni10),,.
Stainless steel stamped grills AISI304 (FeCr18
Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws
6


 
  Application   Neutral Resistance Zig Zag Z Neutral Resistance Zig Zag Z
   
Equipped with current transformer
  Toroidal current transformer 300/1A,  1.5 VA Toroidal current transformer 300/1A,  1.5 VA
12 Protection System      
  Removable switch kV 24 kV 24 kV
  Monitoring relay and fault detection with 50/51 and 50N / 51N function GLB Specify satisfy
  Neutral resistance monitoring relay and resistance sensor. kV Specify satisfy
 

Note:

 

1.- They must include all the complete equipment (including a Cell) to implement the artificial Neutral in 20 kV and 22.9 kV Bars of the Rioja and Nueva Cajamarca substations, respectively, to guarantee the operation of ground fault protection in networks.
 
2. - Includes the minimum necessary accessories for the commissioning and operation of the Transformer and equipment associated with the artificial Neutral.
 
 