Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ÍTEM | CHARACTERISTICS | UNITY | REQUIRED VALUE | OFFERED VALUE |
1 | General | |||
Country | Specify | China | ||
Manufacturer | Specify | HEMG | ||
Manufacturing standards | IEC 60076-6 Acapite 10 IEC 60296 |
IEC 60076-6 Acapite 10 IEC 60296 |
||
Type |
Submerged in oil or other superior insulation. | Submerged in oil | ||
Main Nominal Voltage | kV | 22.9 | 22.9 | |
Short-term neutral current | A | 300 | 300 | |
Duration of neutral current of short duration | S | 10 | 10 | |
Frequency | Hz | 60 | 60 | |
Permanent neutral current | A | 10 | 10 | |
Short time current to ground for 60 sec | KA | 25 | 25 | |
Conservation system | Airtight with gas mattress | Airtight with gas mattress | ||
Connection | Zigzag | Zigzag | ||
Type of liquid | Natural Ester | mineral oil | ||
Insulation system |
120° C (TUP Thermally enhanced paper)TUP | 120° C (TUP Thermally enhanced paper)TUP | ||
Cooling Mode | ONAN | ONAN | ||
2 | Conditions of service | |||
Altitude | msnm | <1000 | <1000 | |
Air temperature |
°C |
28°C anytime | 28°C anytime | |
25°C Monthly average of the warmest month | 25°C Monthly average of the warmest month | |||
20°C Annual average | 20°C Annual average | |||
5°C minimum | 5°C minimum | |||
Degree of pollution | mm/kV | 25 | 25 | |
Seismic disturbance | g | Specify | 0.2 | |
3 | Temperature limits | |||
Thermal class | °C | 105 | 105 | |
Heating of the upper liquid | °C | 60 | 60 | |
Average warming of windings | °C | 65 | 65 | |
Warmest spot heating | °C | 78 | 78 | |
4 | Insulation level inside | |||
Higher Material Voltage | kV | 24 | 24 | |
Primary impulse voltage | kVpico | 50 | 50 |
Applied voltage | kV | 125 | 125 | |
5 | External Insulation Level | |||
Higher Material Voltage | kV | 36 | 36 | |
Primary impulse voltage | kVpico | 170 | 170 | |
Applied voltage | kV | 70 | 70 | |
6 | Guaranteed Parameters | |||
Lost in vacuum | W | 500 | 500 | |
Excitation current | % | 0.3 | 0.3 | |
Homopolar impedance | /fase | 45 | 45 | |
7 | Weights and dimensions | |||
Dielectric liquid weight | kg | Specify | 550 | |
Total weight | kg | Specify | 1700 | |
Length x Width x Height | mm | According to design | 1600x950x1300 | |
8 | Classification of atmosphere and coating | |||
Class (NBR 11388) | Class II | Class II | ||
system | Epoxi | Epoxi | ||
9 | Accessories | |||
Oil level indicator without contacts | 1 Pz | Yes | Yes | |
Contactless overpressure valve | 1 Pz | Yes | Yes | |
Drain valve | 1 Pz | Yes | Yes | |
Contactless bimetallic thermometer | 1 Pz | Yes | Yes | |
Earthing bar (5x30mm) | 1 Pz | Yes | Yes | |
Sudden pressure relay with a contact | 1 Pz | Yes | Yes | |
Grounding Terminals | 1 Pz | Yes | Yes | |
10 | Testing | IEC | IEC | |
11 | Neutral Resistance | |||
Insulation | Air | Air | ||
Service | Exterior | Exterior | ||
Nominal Voltage | kV | 22.9/√3 | 22.9/√3 | |
Intensity of continuous service | A | 10 | 10 | |
Short-term Intensity | A | 300-10 s | 300-10 s | |
Resistance | ohm | 12 | 12 | |
Metal enclosure |
AISI-304 stainless steel painted interior and exterior | AISI-304 stainless steel painted interior and exterior | ||
Degree of protection | IP | IP23 | IP23 | |
Resistive material |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto304 |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto |
||
Normative | IEEE Std- 32 | IEEE Std- 32 | ||
Construction |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws304,,. |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws |
||
Application | Neutral Residence Zig Zag Z | Neutral Residence Zig Zag |
Equipped with current transformer |
Toroidal current transformer 300/1A, 1.5 VA | Toroidal current transformer 300/1A, 1.5 VA | ||
12 | Protection System | |||
Removable switch | kV | 24 kV | 24 kV | |
Monitoring relay and fault detection with 50/51 and 50N / 51N function | GLB | Specify | satisfy | |
Monitoring relay neutral resistance and resistance sensor.. | kV | Specify | satisfy |
ÍTEM | CHARACTERISTICS | UNITY | REQUIRED VALUE | OFFERED VALUE |
1 | General | |||
Country | Specify | China | ||
Manufacturer | Specify | HEMG | ||
Manufacturing standards | IEC 60076-6 Acápite 10 IEC 60296 |
IEC 60076-6 Acápite 10 IEC 60296 |
||
Type |
Submerged in oil or other superior insulation. | Submerged in oil | ||
Primary Nominal Voltage | kV | 20 | 20 | |
Short-term neutral current | A | 300 | 300 | |
Duration of the neutral current of short duration | S | 10 | 10 | |
Frequency | Hz | 60 | 60 | |
Permanent neutral current | A | 10 | 10 | |
Short time current ground for 60 sec 60 | KA | 25 | 25 | |
Conservation system | Airtight with gas mattress | Airtight with gas mattress | ||
Connection | Zigzag | Zigzag | ||
Type of liquid | Natural Ester | mineral oil | ||
Insulation system |
120° C (TUP Thermally enhanced paper) | 120° C (TUP Thermally enhanced paper) | ||
Cooling Mode | ONAN | ONAN | ||
2 | Conditions of service | |||
Altitude | msnm | < 1000 | < 1000 | |
Air temperature |
°C |
28°C anytime | 28°C anytime | |
25°C Monthly average of the warmest month | 25°C Monthly average of the warmest month | |||
20°C Annual average | 20°C Annual average | |||
5°C minimum | 5°C minimum | |||
Degree of pollution | mm/kV | 25 | 25 | |
Seismic disturbance | g | Specified | 0.2 | |
3 | Temperature limits | |||
Thermal class | °C | 105 | 105 | |
Heating of the upper liquid | °C | 60 | 60 | |
Average warming of windings | °C | 65 | 65 | |
Warmest spot heating | °C | 78 | 78 |
4 | Insulation level inside | |||
Higher material Voltage | kV | 24 | 24 | |
Primary impulse voltage | kVpico | 50 | 50 | |
Applied voltage | kV | 125 | 125 | |
5 | External Insulation Level | |||
Higher material Voltage | kV | 36 | 36 | |
Primary impulse voltage | kVpico | 170 | 170 | |
Applied voltage | kV | 70 | 70 | |
6 | Guaranteed Parameters | |||
Lost in vacuum | W | 500 | 500 | |
Excitation current | % | 0.3 | 0.3 | |
Homopolar impedance | /fase | 40 | 40 | |
7 | Weights and dimensions | |||
Dielectric liquid weight | kg | Specify | 500 | |
Total weight | kg | Specify | 1600 | |
Length x Width x Height ** | mm | According to design | 1600x900x1300 | |
8 | Classification of atmosphere and coating | |||
Class(NBR 11388) | Class II | Class II | ||
System | Epoxi | Epoxi | ||
Surface Preparation | Sa 2 1/2 | Sa 2 1/2 | ||
9 | Accessories s | |||
Oil level indicator without contacts | 1 Pz |
Yes | Yes | |
Contactless overpressure valve | 1 Pz | Yes | Yes | |
Drain valve | 1 Pz | Yes | Yes | |
Contactless bimetallic thermometer | 1 Pz | Yes | Yes | |
Earthing bar | 1 Pz | Yes | Yes | |
Sudden pressure relay with a contact | 1 Pz | Yes | Yes | |
Grounding Terminals | 1 Pz | Yes | Yes | |
10 | TESTING | IEC | IEC | |
11 | Neutral Resistance | |||
Insulation | Air | Air | ||
Service | Exterior | Exterior | ||
Nominal Voltage | kV | 20/ √ 3 | 20/ √ 3 | |
Intensity of continuous service | A | 10 | 10 | |
Short-term current | A | 300-10 s | 300-10 s | |
Resistance | ohm | 12 | 12 | |
Metal enclosure |
Stainless steel AISI- 304 Painted inside and out 304 | Stainless steel AISI- 304 Painted inside and out | ||
Degree of protection | IP | IP23 | IP23 | |
Resistive material |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto304 |
Chrome-nickel steel AISI-304 Cr18/20%, Ni 18/10%; Fe resto |
||
Normative | IEEE Std- 32 | IEEE Std- 32 | ||
Construction |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screwsAISI‐304(Fe‐Cr18 Ni10),,. |
Stainless steel stamped grills AISI‐304 (Fe‐Cr18‐ Ni10), Joined by welding points and insulated from each other by ceramic separators. Stainless steel screws |
Application | Neutral Resistance Zig Zag Z | Neutral Resistance Zig Zag Z | ||
Equipped with current transformer |
Toroidal current transformer 300/1A, 1.5 VA | Toroidal current transformer 300/1A, 1.5 VA | ||
12 | Protection System | |||
Removable switch | kV | 24 kV | 24 kV | |
Monitoring relay and fault detection with 50/51 and 50N / 51N function | GLB | Specify | satisfy | |
Neutral resistance monitoring relay and resistance sensor. | kV | Specify | satisfy |