400kv Outdoor Sf6 Insulating Porcelain Circuit Breaker with Hydraulic Spring Operating Mechanism

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Still deciding? Get samples of US$ 100000/Piece
Request Sample
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 400kv Outdoor Sf6 Insulating Porcelain Circuit Breaker with Hydraulic Spring Operating Mechanism
  • 400kv Outdoor Sf6 Insulating Porcelain Circuit Breaker with Hydraulic Spring Operating Mechanism
  • 400kv Outdoor Sf6 Insulating Porcelain Circuit Breaker with Hydraulic Spring Operating Mechanism
  • 400kv Outdoor Sf6 Insulating Porcelain Circuit Breaker with Hydraulic Spring Operating Mechanism
Find Similar Products

Basic Info.

Model NO.
LW25
Speed
High-Speed Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification
ISO9001-2000
Transport Package
3pole/Pk
Specification
400KV
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description

400kv Outdoor Sf6 Insulating Porcelain Circuit Breaker with Hydraulic Spring Operating Mechanism
SCHEDULE  F    
No. Description   Particulars OFFER 
       
  400KV CIRCUIT BREAKER         
1 Normal current rating A 2500 2500
2 Fault rating   kA 100 100
2.1 Making current     kAp 40 40
2.2 Breaking current under out of phase conditions  kA 10 10
2.3 Maximun overvoltage factor on any switching duty pu < 2.5 1.05
3 Operating sequence        
3.1 Normal    0-10s-CO-3min-CO O-10S-CO-3MIN-CO
3.2 Auto reclosing single phase     0-0.3s-CO-3min-CO O-0.3S-CO-3MIN-CO
3.3 Delayed three phase auto reclose cycle adjustable dead time range ms  2-30 2-30MS
3.4 High speed single phase auto reclose cycle adjustable dead time range s  0.3-2.0 0.3-2.0
3.5 Number of closing operations under out of synchronous conditions pu 2 2
4 Transient recovery voltage    -  
4.1 First phase to clear factor    pu 1.3 1.3
4.2 Surge impedance for short line fault test ohms 450 450
4.3 Minimum voltage to earth when switching capacitive currents,( 1.2 times rated phase to earth voltage )  kV 291 291
4.4 Voltage across circuit breaker under out of phase                  
  switching conditions pu 2 2
5 Electro mechanical performance        
5.1 Maximum total break time throughout complete rating ,         
  ie trip coil initiation to final arc extinction (applicable) only to 100% rating for oil break circuit breakers )  ms 50 50
5.2 Maximum time interval between closure of first and last phase of three phase circuit breakers  ms 3 3
5.3 Maximum time interval between closure of interrupters of one phase of the circuit breaker ms 2 3
5.4 Maximum time interval between opening of first and last phase of three phase circuit breaker  ms 3 3
5.5 Maximum time interval between opening of interrupters  ms 2 2
6 Insulation level ( IEC 694 )        
6.1* Lightning impulse withstand ( 1.2/50 wave ) positive        
  and negative        
      a. To earth , closed contacts   -kVp 1425 1425
      b. Across , open contacts       -kVp 1665 1665
6.2* Switching impulse withstand ( 250/2500 wave )- positive and negative                                  Dry / wet        
      a. To earth , closed contacts   -kVp 1050 1050
      b. Across , open contacts         -kVp 1245 1245
6.3* Power frequency withstand                         Dry / wet        
      a. To earth , closed contacts - 1 minute  kV 520 520
      b. Across , open contacts - 1 minute  kV 610 610
7 Ancillary equipment        
7.1 Number of trip coils required   2/pole 2/POLE
7.2 Number of closing coils required   1/pole 1/POLE
7.3 Degree of protection   IP 55 IP55
           
·         For SF6 circuit breakers , insulation levels at minimum SF6 gas working pressure , at15  C.         YES
*    Based tests ( Impulse + ACp ) , required on switchgear for 300kV and above .         YES
+    Wet tests are required on outdoor open-terminal switchgear .         YES