Loop Automation Circuit Recloser with Sel-651r-2 Control

Product Details
Customization: Available
Task: Program
Structure: Closed-Loop
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • Loop Automation Circuit Recloser with Sel-651r-2 Control
  • Loop Automation Circuit Recloser with Sel-651r-2 Control
  • Loop Automation Circuit Recloser with Sel-651r-2 Control
  • Loop Automation Circuit Recloser with Sel-651r-2 Control
  • Loop Automation Circuit Recloser with Sel-651r-2 Control
  • Loop Automation Circuit Recloser with Sel-651r-2 Control
Find Similar Products

Basic Info.

Model NO.
SEL-651R-2
Mathematical Model
Non-Linear
Signal
Continuous
Function
Automatic Control, Protection, Monitoring, Measurement
Certification
ISO: 9001
Condition
New
Customized
Customized
Material
Stainless Steel
Transport Package
Wooden
Specification
27KV
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description



 
No. Parameter Specification requested Specification offered
1 Amount 100 100
2 March Indicate HEMG(SEL)
3 Model Indicate CHZ4(SEL-651R-2)
4 Country of origin Indicate CHINA(USA CONTROL)
5 Year of manufacture NO less than 2018 (Take advantage of the 100% of the equipment life and have updated control and communication systems) 2018
6
 
Type Automatic, three-phase reconnector with electronic control. AUTOMATIC ,THREE PHASE RECONNECTOR WITH ELECTRONIC CONTROL
7 Operating room temperature -10 °c to 50 º C Recloser:-40 °c to 85 º C
8 Operating frequency 60 HZ 60Hz
9 NOMINAL capacity 630 A 30A
10 Service Voltage 23 kV 23KV
11 Maximum design voltage ≥ 27 kV 27KV
12 Was ≥150 kV a 3000 m.s.n.m 150KV@3000MSNM
13 Symmetrical interrupt Current 12.5 kA RMS 12.5KA RMS
14 Use Weather WEATHER
15 Degree of protection IP65 the Superior IP65
16 Arc Extinction Medium Vacuum VACUUM
17 Insulation medium SF6 or vacuum VACUUM
18 Number of operations open/close at full load 10 000 10000
19 Shot Electric and manual ELECTRIC AND MANUAL
20 Auto Reconnect 1 to 4 shots, user configurable. 1 TO 4 SHOTS ,USER CONFIGURABLE
21 Current measurement 3 Transformers for measuring phase currents and residual current. 3 TRANSFORMER FOR MEASUING PHASE CURRENTS AND RESIDUAL CURRENT
22 Voltage measurement 6 voltage sensors, to measure phase-ground voltage and phase-phase on both sides. 6 VOLTAGE SENSORS TO MEASURE PHASE GROUND VOLTAGE AND PHASE-PHASES ON BOTH SIDE
23 Power measurement Measuring capacity:
-Active, reactive and total power, single phase and three phase.
-Power Factor.
MEASURING CAPACITY:
-ACTIVE ,REACTIVE AND TOTAL POWER
SINGLE PHASE AND THREE PHASE ,
-POWER FACTOR
24 Measuring harmonics Ability to measure current and voltage harmonics.  
25  Measure 10 analog input channels harmonic for current and voltage harmonics User-Configurable for integration of 1, 5, 10, 15, 30, 60 or 120 minutes. Interval support 5,10,15,30,60min record
26 Phase sequence On both sides of the Reconnector. On both sides of reconnector
27 External display of contacts of contact position, included in the tank. Complied. 7 inputs for external contact.
28 Life-SPAN counter Total number of operations closing/opening and wear Automatic contacts. Complied ,total number of operations closing /opening and wear automatic contacts
29 Fault counter Number of operations for each of the protections:
-Phase Overcurrent
-Overcurrent of ground
-Negative sequence protection
-Earth-sensitive
-Low/over voltage
-Low/over frequency
Complied ,Number of operations for each of the protections:
-Phase Overcurrent
-Overcurrent of ground
-Negative sequence protection
-Earth-sensitive
-Low/over voltage
-Low/over frequency
30 Manufacturing and design standards ANSI/IEEE C37.60 o IEC 62271-111.
IEC 60529.
IEC 60255.
IEEE 1613
IEC 61850-3
Standards for operation in severe electrical environments.
Attach compliance certifications in English or Spanish.
ANSI/IEEE C37.60 o IEC 62271-111.
IEC 60529.
IEC 60255.
IEEE 1613
IEC 61850-3
Standards for operation in severe electrical environments.
Attach compliance certifications in English
31 CONTROL Electronic for recording events stamped over time, includes software.  
The control Panel must include the following:
-Visual display with dimensions not less than 10cm by 8cm.
-Numerical type relay, with keyboard for manual configuration and opening/closing operation, configurable through software for protection and reconnection options,
-Non-volatile memory
-Power supply with a range of 105-250 VAnd and long life battery as backup. The battery must be easily interchangeable and available on the market.
-Surge suppressor for control panel power protection.
-Control Language: Possibility to select between Spanish and English.
-Includes battery status indicator.

Electronic for recording events stamped over time, includes software.  
The control Panel must include the following:
Relay LCD is 6*1.5cm, it can display 16*2 characters.
-Numerical type relay, with keyboard for manual configuration and opening/closing operation, configurable through software for protection and reconnection options,
-Non-volatile memory
-Power supply with a range of 105-250 VAnd and long life battery as backup. The battery must be easily interchangeable and available on the market.
-Surge suppressor for control panel power protection.
-Control Language: Possibility to select between Spanish and English.
-Includes battery status indicator
32 SOFTWARE Have all the updated library/utility, which requires the computer to manage and manage it locally and remotely. Language of the software with the possibility to select between English and Spanish. Complied.Have all the updated library/utility, which requires the computer to manage and manage it locally and remotely. Language of the software with the possibility to select between English and Spanish.
33 Protection groups 4 Configurable protection groups Complied. Max 8 groups can be used.
34 Protection group Selection -Automatic by change in flow direction.
-User-selectable.
Complied,-Automatic by change in flow direction.
-User-selectable
35 Protection functions -overcurrent protection against phase-phase and phase-to-ground faults. Minimum Dial of 0.01
-Instantaneous overcurrent protection against phase-phase and phase-ground faults, independent of the starting current of the timed protection.
-sensitive protection for ground faults.
-Negative sequence protection.
-Directional element
-Live line overcurrent (configurable)
-Function of Hot Line Tag.
-Loss of supply in all three phases, overvoltage and low voltage loss of one phase supply.
-Low and over frequency
-User programmable cold charge function, multiples of starting current from 1 to 5 in steps of 0.1.
Complied,-overcurrent protection against phase-phase and phase-to-ground faults. Minimum Dial of 0.01
-Instantaneous overcurrent protection against phase-phase and phase-ground faults, independent of the starting current of the timed protection.
-sensitive protection for ground faults.
-Negative sequence protection.
-Directional element
-Live line overcurrent (configurable)
-Function of Hot Line Tag.
-Loss of supply in all three phases, overvoltage and low voltage loss of one phase supply.
-Low and over frequency
-User programmable cold charge function, multiples of starting current from 1 to 5 in steps of 0.1.
36 Functions of Loop Automatisms Voltage reconnection Control and automatic supply restoration allowing:
1. Automatic opening before load-side fault or loss of voltage in all three phases on the source side.                   
2. Automatic selection of the protection group.                   
3. Automatic closing in front of a voltage loss in the three phases of the load side and presence of voltage in the three phases of the source side.
4. AutoRecovery of the system, by means of the communication between Reconnectors (Intelligent Loop Automation), with the aim of carrying out load transfer without feeding a permanent fault.        
Complied. Relay can communicate with others to exchange information.
Voltage reconnection Control and automatic supply restoration allowing:
1. Automatic opening before load-side fault or loss of voltage in all three phases on the source side.                   
2. Automatic selection of the protection group.                   
3. Automatic closing in front of a voltage loss in the three phases of the load side and presence of voltage in the three phases of the source side.
4. AutoRecovery of the system, by means of the communication between Reconnectors (Intelligent Loop Automation), with the aim of carrying out load transfer without feeding a permanent fault.
37 Signals to the SCADA All the reconnector signals that can be carried out from the SCADA, the control, supervision and monitoring.
The software supplied with the equipment must allow to perform automatism functions, control, adjustments and downloading of information by the front port, it must also allow to perform these functions remotely.
All the reconnector signals that can be carried out from the SCADA, the control, supervision and monitoring.
The software supplied with the equipment must allow to perform automatism functions, control, adjustments and downloading of information by the front port, it must also allow to perform these functions remotely.
38
Communication interface

 
- Serial RS-232/RS-485 Interface DB-9 / RJ45
- ETHERNET 100Base-TX IEEE 802.3u 10/100 Mbps TCP/IP, para DNP3, IEC104, IEC 61850.
-RJ45 interface (native, without active or passive or similar converters).
-Direct Configuration USB interface
- Serial RS-232/RS-485 Interface DB-9 / RJ45
- ETHERNET 100Base-TX IEEE 802.3u 10/100 Mbps TCP/IP, para DNP3,, IEC 61850.
-RJ45 interface (native, without active or passive or similar converters).
-Direct Configuration USB interface
39 SCADA protocols DNP3 (TCP/IP) , IEC-60870-5-104, IEC 61850 DNP3 or IEC 61850,WITHOUT IEC104
40 Auxiliary power supplies for additional communications equipment 24vDC and 48vDC, with Back Battery for 48 hours ContiNaked.
Exclusive and clearly identifiable dual-terminal connection (+/-)
24vDC and 48vDC, with Back Battery for 48 hours ContiNaked.
Exclusive and clearly identifiable dual-terminal connection (+/-)
41 Internal space for mounting equipment communications The internal compartment of the control box must allow the modular assembly of communications equipment.
Features: 25cm (long) x15cm (high) x20cm (depth) with detachable plate (modularity) for independent manoeuvring of the communications equipment, with securing to the box by type butterfly nut in 4 points.
The internal compartment of the control box must allow the modular assembly of communications equipment.
Features: 25cm (long) x15cm (high) x20cm (depth) with detachable plate (modularity) for independent manoeuvring of the communications equipment, with securing to the box by type butterfly nut in 4 points.
42 Mounting structure Include all concrete circular pole mounting accessories for each equipment. Include all concrete circular pole mounting accessories for each equipment.
43 Accessories by Equipment -Cable of 12 meters for communication control-laptop computer (1 for every 10 equipment).
-6 Terminals for 4 gauge cables/0AWG-500MCM for each equipment.
-6 bird Guards per team.
-Cable of 12 meters for communication control-laptop computer (1 for every 10 equipment).
-6 Terminals for 4 gauge cables/0AWG-500MCM for each equipment.
-6 bird Guards per team.Loop Automation Circuit Recloser with Sel-651r-2 Control
Loop Automation Circuit Recloser with Sel-651r-2 Control
Loop Automation Circuit Recloser with Sel-651r-2 Control
Loop Automation Circuit Recloser with Sel-651r-2 Control
Loop Automation Circuit Recloser with Sel-651r-2 Control
Loop Automation Circuit Recloser with Sel-651r-2 Control

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier