33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Manual Type
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
  • 33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
  • 33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
  • 33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
  • 33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
  • 33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
Find Similar Products

Basic Info.

Model NO.
LW
Speed
High-Speed Circuit Breaker
Arc-extinguishing Medium
SF6
Installation
Outdoor
Structure
Live Tank
Poles Number
1
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification
ISO9001-2000
Transport Package
Carton with Wooden
Specification
33kv/66kv/132kv
Trademark
HEMG
Origin
China
Production Capacity
5000PCS/Year

Product Description

LW high voltage sulphur hexafluoride circuit breakers belongs to three-phase alternating current 50 Hz high voltage switchgear, which is mainly used for the control and protection of transmission line as well as used as the contact circuit breaker.

The product adopts mixed type self-arc extinguish chamber. The triple pole is equipped with one spring operating mechanism to conduct the tree-pole mechanical operating, so as to realize remote or local operation.
 

1.3. Operating ambient

1.3.1 Height above sea level: 2500 m (special order is available for the high elevation);
1.3.2 Ambient temperature: -30ºC~+40ºC(special orders are available under -30ºC)
1.3.3 Rated wind speed:34m/s;
1.3.4 Shock resistance: level 8;
1.3.5 Dirtiness level: l level III 25mm/kV and level :3.1cm/kV.

1.4.  Technical parameters

1.4.1 See table 1 for main technical parameters of the circuit breaker
Table 1
No. Name Unit     Value
LW-145
1
 
  Rated voltage
 
kV
 
145
 
2
 
  Rated current
 
A
 
1600,2000,3150
 
3
 
  Rated frequency
 
Hz
 
50/60
 
4
 
  Rated short time withstand current (4S)
 
kA
 
40
 
5
 
  Rated short-circuit period
 
S
 
4
 
6   Rated
short circuit
Dropout current
  Short-circuit current kA 40
 Percent for zero frequency component - 45%
7
 
  Rated short circuit close current (peak value)
 
kA
 
100
 
8
 
  Rated peak withstand current 
 
kA
 
100
 
9
 
  Close-in fault drop-out current
 
kA
 
Ie×90% le×75%
 
10
 
  Rated step-out dropout current
 
kA
 
Ie×25%
 
11
 
  Rated line charging dropout current
 
A
 
31.5
 
12
 
  Initial pole factor
 
- 1.5
 
13
 
  Rated operating sequence
 
- O-0.3S-CO-180S-CO
 
 
 
 
Table 1 (continued)
No. Name Unit Value
LW-145
 
14 Rated insulation level 1-min power frequency stand voltage (valid value for dry and wet) Open contact
 
kV 275
 
Space in between
 
275
 
Over the ground 275
 
Lightning surge
Stand voltage
(peak value)
Open contact 750
 
Space in between 650
 
Over the ground
 
650
 
5minZero gage pressure withstand test (valid value) Open contact 105
 
Over the ground 105
15
 
Open circuit time
 
ms ≤60
 
16 SF6 gas rated pressure (20ºC)
 
MPa 0.55
 
Alarm pressure
 
0.50
 
Interlock pressure
 
0.45
 
17 Terminal ST Vertical orientation
 
N 1250
 
Horizontal orientation
 
 
750
 
Vertical direction
 
1000
 
l 8 Inherent opening time Rated voltage
 
ms 26~35
 
Low-voltage
 
26~35
 
19
 
Closing time
 
ms ≤120
 
20
 
Opening synchronism
 
 
ms ≤2
 
21
 
Closing synchronism
 
ms ≤4
 
22 Re-closing property
Opening-0.3S-closi-ng and opening
First opening time
 
ms 26~35
 
Opening and closing time
 
ms 280~300
 
Closing time
 
 
ms 80~120
 
Closing and opening time
 
ms <50
 
Second opening time
 
ms 26~35
 
23
 
Major loop circuit resistance for each pole
 
μOM
 
≤40
 
24
 
Control circuit voltage
 
V
 
DC110/DC220
 
25
 
Opening & closing coil voltage
 
V
 
DC110/DC220
 
26 Opening & closing coil current A 3.67/2
27
 
Motor voltage
 
V
 
AC220/DC220
 
28
 
Motor W 600
29   Heater voltage V AC220
30
 
  Mechanical life
 
times
 
6000(2000×3)
 
31
 
  Radio interference voltage
 
U V
 
≤500(2500)*2
 
32
 
  Leakage rate examination for SF6 gas
 
- ≤1%
 
33
 
  Shell protection level
 
- IP4×
 
34
 
  SF6 gas is charged for each unit
 
kg
 
7
 
35   Gross weight for each unit kg 2700
             
 

1.4.2 Mechanical parameters
See table 2 for mechanical parameters of the circuit breaker and the operating mechanism.
Table 2
No.
 
Item
 
Unit
 
Data
 
Remark
 
1
 
    Stroke
 
mm 150+2-4
 
See figure 13 for stroke measuring
of the circuit breaker
2
 
    Contact stroke mm 27±2
3
 
    Spring mechanism's piston rod stroke
 
mm 1000-3
 
4 Gap between the shear lever roller and the cam mm 1.4±0.3 As the Circuit breaker is in opening state,
the closing spring has been stored with energy.
5     Set nut for the closing spring
    Distance to the locating lever
mm ≤55
6     Closing electromagnetic iron stroke C
 
mm 5.0~5.5
 
The circuit
breaker is in the opening status, see figure 14
    Gap between the Flip-flop and the release device D 2.0~2.5
    C -D
 
2.5~3.5
 
    Gap between the flip-flop and the de-bouncing bar E 1.0~2.0
7     Closing electromagnetic iron stroke F
 
mm 2.8~3.2
 
See table 15 for the on-position of the  circuit breaker
    Gap between the Flip-flop and the release device G 0.8~1.2
    F - G
 
1.6~2.4
 
 
See table 3 for parameters of the control circuit and the secondary group circuit
Table 3
No.
 
Item
 
Unit
 
Data
 
Remark
 
1 Opening & closing coil control voltage V DC110/220  
2
 
Opening coil current A 3.67/2  
3
 
Closing coil current
 
A
 
3.67/2
 
 
4 Motor voltage V DC 220/
AC 220
As per purchase contract
5
 
Power of motor
 
W
 
600
 
 
6
 
Motor speed
 
r.p.m
 
530
 
 
7
 
Motor current
 
A
 
5.5/2.7
 
 
8 Heater Voltage V AC 220 As per purchase contract
Power
 
W
 
100(250)
 
 
1.4.3 See table 4 for gas pressure parameter of SF6 (20ºC) (gage pressure)
Table 4
  No.
 
Item
 
Unit
 
Data
 
1     Rated inflation pressure Mpa 0.55
2
 
    Alarm pressure for air-in
 
Mpa
 
0.50±0.02
 
3     Bottoming pressure of the circuit breaker Mpa 0.45±0.02

33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker

33kv/72.5kv/123kv/145kv Outdoor Live Tank Sf6 Insulating Circuit Breaker
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier