LW high voltage sulphur hexafluoride circuit breakers belongs to three-phase alternating current 50 Hz high voltage switchgear, which is mainly used for the control and protection of transmission line as well as used as the contact circuit breaker.
The product adopts mixed type self-arc extinguish chamber. The triple pole is equipped with one spring operating mechanism to conduct the tree-pole mechanical operating, so as to realize remote or local operation.
No. | Name | Unit | Value | |
LW-145 | ||||
1 |
Rated voltage |
kV |
145 |
|
2 |
Rated current |
A |
1600,2000,3150 |
|
3 |
Rated frequency |
Hz |
50/60 |
|
4 |
Rated short time withstand current (4S) |
kA |
40 |
|
5 |
Rated short-circuit period |
S |
4 |
|
6 | Rated short circuit Dropout current |
Short-circuit current | kA | 40 |
Percent for zero frequency component | - | 45% | ||
7 |
Rated short circuit close current (peak value) |
kA |
100 |
|
8 |
Rated peak withstand current |
kA |
100 |
|
9 |
Close-in fault drop-out current |
kA |
Ie×90% le×75% |
|
10 |
Rated step-out dropout current |
kA |
Ie×25% |
|
11 |
Rated line charging dropout current |
A |
31.5 |
|
12 |
Initial pole factor |
- | 1.5 |
|
13 |
Rated operating sequence |
- | O-0.3S-CO-180S-CO |
No. | Name | Unit | Value | |||
LW-145 |
||||||
14 | Rated insulation level | 1-min power frequency stand voltage (valid value for dry and wet) | Open contact |
kV | 275 |
|
Space in between |
275 |
|||||
Over the ground | 275 |
|||||
Lightning surge Stand voltage (peak value) |
Open contact | 750 |
||||
Space in between | 650 |
|||||
Over the ground |
650 |
|||||
5minZero gage pressure withstand test (valid value) | Open contact | 105 |
||||
Over the ground | 105 | |||||
15 |
Open circuit time |
ms | ≤60 |
|||
16 | SF6 gas rated pressure (20ºC) |
MPa | 0.55 |
|||
Alarm pressure |
0.50 |
|||||
Interlock pressure |
0.45 |
|||||
17 | Terminal ST | Vertical orientation |
N | 1250 |
||
Horizontal orientation |
750 |
|||||
Vertical direction |
1000 |
|||||
l 8 | Inherent opening time | Rated voltage |
ms | 26~35 |
||
Low-voltage |
26~35 |
|||||
19 |
Closing time |
ms | ≤120 |
|||
20 |
Opening synchronism |
ms | ≤2 |
|||
21 |
Closing synchronism |
ms | ≤4 |
|||
22 | Re-closing property Opening-0.3S-closi-ng and opening |
First opening time |
ms | 26~35 |
||
Opening and closing time |
ms | 280~300 |
||||
Closing time |
ms | 80~120 |
||||
Closing and opening time |
ms | <50 |
||||
Second opening time |
ms | 26~35 |
||||
23 |
Major loop circuit resistance for each pole |
μOM |
≤40 |
|||
24 |
Control circuit voltage |
V |
DC110/DC220 |
|||
25 |
Opening & closing coil voltage |
V |
DC110/DC220 |
|||
26 | Opening & closing coil current | A | 3.67/2 | |||
27 |
Motor voltage |
V |
AC220/DC220 |
|||
28 |
Motor | W | 600 | |||
29 | Heater voltage | V | AC220 | |||
30 |
Mechanical life |
times |
6000(2000×3) |
|||
31 |
Radio interference voltage |
U V |
≤500(2500)*2 |
|||
32 |
Leakage rate examination for SF6 gas |
- | ≤1% |
|||
33 |
Shell protection level |
- | IP4× |
|||
34 |
SF6 gas is charged for each unit |
kg |
7 |
|||
35 | Gross weight for each unit | kg | 2700 | |||
No. |
Item |
Unit |
Data |
Remark |
1 |
Stroke |
mm | 150+2-4 |
See figure 13 for stroke measuring of the circuit breaker |
2 |
Contact stroke | mm | 27±2 | |
3 |
Spring mechanism's piston rod stroke |
mm | 1000-3 |
|
4 | Gap between the shear lever roller and the cam | mm | 1.4±0.3 | As the Circuit breaker is in opening state, the closing spring has been stored with energy. |
5 | Set nut for the closing spring Distance to the locating lever |
mm | ≤55 | |
6 | Closing electromagnetic iron stroke C |
mm | 5.0~5.5 |
The circuit breaker is in the opening status, see figure 14 |
Gap between the Flip-flop and the release device D | 2.0~2.5 | |||
C -D |
2.5~3.5 |
|||
Gap between the flip-flop and the de-bouncing bar E | 1.0~2.0 | |||
7 | Closing electromagnetic iron stroke F |
mm | 2.8~3.2 |
See table 15 for the on-position of the circuit breaker |
Gap between the Flip-flop and the release device G | 0.8~1.2 | |||
F - G |
1.6~2.4 |
No. |
Item |
Unit |
Data |
Remark |
|
1 | Opening & closing coil control voltage | V | DC110/220 | ||
2 |
Opening coil current | A | 3.67/2 | ||
3 |
Closing coil current |
A |
3.67/2 |
||
4 | Motor voltage | V | DC 220/ AC 220 |
As per purchase contract | |
5 |
Power of motor |
W |
600 |
||
6 |
Motor speed |
r.p.m |
530 |
||
7 |
Motor current |
A |
5.5/2.7 |
||
8 | Heater | Voltage | V | AC 220 | As per purchase contract |
Power |
W |
100(250) |
No. |
Item |
Unit |
Data |
1 | Rated inflation pressure | Mpa | 0.55 |
2 |
Alarm pressure for air-in |
Mpa |
0.50±0.02 |
3 | Bottoming pressure of the circuit breaker | Mpa | 0.45±0.02 |