34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer

Product Details
Customization: Available
Application: Instrument
Type: Combined Transformer
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer
  • 34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer
  • 34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer
Find Similar Products

Basic Info.

Model NO.
CCPT4
Phase
Three
Operation Condition
Outdoor
Usage
Protection, Measurement
Winding Form
Multilayer Honeycomb Type
Insulating Medium
Epoxy Resin
Installation
Extension Type
Transport Package
Wooden
Specification
13.8KV
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description

34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer
 
SPECIFICATION OF 34.5KV COMBINED CT PT TRANSFORMER
  1. Model: CCPT-34.5
 
  1. Standard:IEC 61869-1&2&3&4Instrument transformers, CFE VE100-29

3. Working Condition
3.1 The highest voltage for equipment / frequency:38kV/60Hz
3.2 Working Temperature:-40ºC~40ºC
3.3 Three phase,Outdoor
3.4 Creepage distances: 28mm/Kv
3.5 Wind Speed:160KM/H
3.6 Sea Level: ≥2500m

4. Application  
Applicable to the frequency of 60Hz, the highest voltage of 38kV, which is used for measurement and protection. Suitable for pole-mounted, outdoor

5. Main technical requirements
5.1 Wiring Connecting Diagram

5.2 Parameter sheet
5.2.1 Data of voltage transformer
Rated primary voltage (V) Rated primary voltage(V) Accuracy Rated Burden(VA) Voltage factor VAth(VA) Rated insulation level(kV)
20125 115 0.2

50

1.2Un/continue
1.9Un/8h
500 38/70/170 kV
Ext.BIL:200kV
5.2.2 Data of current transformer
Rated
ratio
Rated load
(VA)
Accuracy Icth Ith(kA/1s) Idyn(kA) Rated insulation level(kV)
10/5A,50/5A
200/5A
15 0.2S 200%

80×Ipr

2.5×Ith

38/70/170 kV
Ext.BIL:200kV
5.3 Withstand requirement: (installation site should be not more than 1000m under standard pressure )
5.3.1 Inductive withstand voltage: Pri.-Sec. &Ground 70kV/40s@180Hz,
5.3.2 Power frequency withstand voltage: Sec.-Sec. &Ground 3kV/1min, N earth terminal - Sec. &Ground: 3kV/1min
5.4 Insulation resistance test
Pri.-Sec. &Ground:  ≥1000MΩ/DC2500V, Sec.-Sec. &Ground: ≥500MΩ/DC2500V
5.5 Partial discharge: meet standard IEC61869-1:2007
6.Dimension  

Fig.1  Outline dimension
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier