• 23kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer
  • 23kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer

23kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer

Application: Instrument
Type: Combined Transformer
Phase: Three
Operation Condition: Outdoor
Usage: Protection, Measurement
Winding Form: Multilayer Honeycomb Type
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
CCPT3
Insulating Medium
Epoxy Resin
Installation
Extension Type
Transport Package
Wooden
Specification
13.8KV
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description

23kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer23kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer

 
SPECIFICAITON OF 23KV COMBINED CT PT TRANSFORMER
  1. Model: CCPT -23
 
  1. Standard:IEC 61869-1&2&3&4Instrument transformers.CFE VE100-29

3. Working Condition
3.1 The highest voltage for equipment / frequency:25.8kV
3.2 Frequency: 60Hz
3.3 Working Temperature:-40ºC~+40ºC
3.4 Three phase,Outdoor
3.5 Creepage distances: 28mm/Kv
3.6 Wind Speed :120km/h
3.7 Sea Level :≥2500m

4. Application  
Applicable to the frequency of 60Hz, the highest voltage of 24kV, which is used for measurement and protection., suitable for pole mounted ,outdoor
5. Main technical requirements
5.1 Wiring connecting diagram

5.2 Parameter sheet
5.2.1 data  of voltage transformer
Rated primary voltage (V) Rated primary voltage(V) Accuracy Rated Burden(VA) Voltage factor VAth(VA) Rated insulation level(kV)
14400 120 0.2

50

1.2Un/continue
1.9Un/8h
500 24/50/125 kV
Ext.BIL:150kV
5.2.2 data  of current transformer
Rated
ratio
Rated load
(VA)
Accuracy Icth Ith(kA/1s) Idyn(kA) Rated insulation level(kV)
10/5A,50/5A
200/5A
10 0.2S 200%

80×Ipr

2.5×Ith

24/50/125 kV
Ext.BIL:150kV
5.3 Withstand requirement: (installation site should be not more than 1000m under standard pressure )
5.3.1 Inductive withstand voltage: Pri.-Sec. &Ground 50kV/40s@180Hz,
5.3.2 Power frequency withstand voltage: Sec.-Sec. &Ground 3kV/1min, N earth terminal - Sec. &Ground: 3kV/1min
5.4 Insulation resistance test
Pri.-Sec. &Ground:  ≥1000MΩ/DC2500V, Sec.-Sec. &Ground: ≥500MΩ/DC2500V
5.5 Partial discharge: meet standard IEC61869-1:2007
6.Dimension  

Fig.1  Outline dimension

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now