Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
THREE PHASE TRANSFORMER PEDESTAL TYPE 500 KVA, 10.5/0.23 KV
FOR WORKING IN ALTITUDE OF 3500 M.O.S.L.
Ítem |
Descriptión |
Unit |
Required |
Guaranteed |
1 |
GENERAL DATA |
|
|
|
1.1 |
Manufacturer |
|
To indicate |
HEMG |
1.2 |
Country |
|
To indicate |
P.R.China |
1.3 |
Brand |
|
To indicate |
HEMG |
1.4 |
Power |
KVA |
500 |
500 |
1.5 |
Number of coils |
|
2 |
2 |
1.6 |
Number of phases |
|
3 |
3 |
1.7 |
Altitude of operation |
|
3500 |
3500 |
1.8 |
Mounting |
|
Outdoor |
Outdoor |
2 |
NOMINAL DATA AND CHARACTERISTICS |
|
|
|
2.1 |
NominalFrequency |
Hz |
60 |
60 |
2.2 |
Nominal Voltage High voltaje side without load |
KV |
10.5+/-2x2.5% |
10.5+/-2x2.5% |
2.3 |
Nominal Voltage low voltage side without load |
kV |
0.230 |
0.230 |
2.4 |
Insulation level high voltage |
|
|
|
|
Insulation Class |
KV |
12 |
12 |
|
Impulse Withstand Voltage 1.2/50 of external insulation |
kVp |
125 |
125 |
|
Impulse Withstand Voltage 1.2/50 of internal insulation |
kVp |
75 |
75 |
|
Withstand voltage industrial frequency |
KV |
28 |
28 |
|
Number of terminals in the primary side |
|
6 |
6 |
|
Material of the coils |
|
Copper |
Copper |
|
Bridge capacity for work in mesh or ring. |
Amps |
200 |
200 |
2.5 |
Insulation level low voltage side |
|
|
|
|
Insulation Class |
KV |
1.1 |
1.1 |
|
Withstand voltage industrial frequency |
KV |
3.0 |
3.0 |
|
Material of the coils |
|
Copper |
Copper |
|
Number of terminals in the secondary side |
u |
3 |
3 |
2.6 |
ConnectionGroup |
|
Dyn5 |
Dyn5 |
2.7 |
Type of working |
|
Meshor ring |
Meshor ring |
2.8 |
Shortcircuit voltage at 75 C |
% |
4 |
4 |
2.9 |
Losses |
VA |
30 |
30 |
|
Losses in the iron (% Nominal Power ) |
|
1179 w |
1179 w |
|
Losses in the copper with full load (% Nominal Power ) |
|
6540 w |
6540 w |
2.10 |
On temperature rise ( Limit Max Power ONAN ) |
|
|
|
|
On temperature rise in the hot point of the coils |
C |
65 |
65 |
|
On temperature rise of the oil in the top side of the tank |
C |
60 |
60 |
2.11 |
Type of Oil
|
|
Mineral, free of PCBs |
Mineral, free of PCBs |
2.12 |
Standard for design, manufacture and test reports |
|
Indicate |
IEC60076 |
2.13 |
Standard for capacity of overload |
|
Indicate |
IEC60076 |
2.14 |
Standard for insulation oils |
|
Indicate |
|
2.15 |
Standard for the bushing plug type |
|
Indicate |
IEC60076 |
2.16 |
Standards for guaranteed losses |
|
Indicate |
IEC60076 |
3.0 |
Equipments |
|
|
|
3.1 |
Cabin of Medium Voltage |
|
Yes |
Yes |
|
Load Break switch submergible in oil, arranged such as to allow the primary network continue without interruption even when the transformer is out of service. |
|
Yes |
Yes |
|
Hold fuse Bay -O-Net type
|
|
Yes |
Yes |
|
Fuses system Bay -O-Net current sensing |
|
Yes |
Yes |
|
Current limiting fuses |
|
Yes |
Yes |
|
Resyn insulators for system of connector plug-in |
|
Yes |
Yes |
|
Lock of the door |
|
Yes |
Yes |
|
Support of parking |
|
Yes |
Yes |
|
Plugs connector for Medium Voltage cubit type |
|
Yes |
Yes |
|
Kit of grounding of plugs connectors |
|
Yes |
Yes |
3.2 |
Cabin of low voltage |
|
Yes |
Yes |
|
Porcelain Insulators |
|
Yes |
Yes |
|
General Circuit Breaker for low voltage |
|
Yes |
Yes |
|
Auxiliar Circuit Breaker for low voltage |
|
Yes |
Yes |
|
interlocking for the door |
|
Yes |
Yes |
|
Lock of the door |
|
|
|
3.3 |
Transformation Module |
|
Yes
|
Yes
|
|
Indicator of oil level |
|
Yes Yes |
Yes Yes |
|
Drain tap |
|
Yes |
Yes |
|
Lifting ears |
|
Yes |
Yes |
|
Nameplate |
|
Yes |
Yes |
|
Vacuum tap changer |
|
Yes |
Yes |
|
Terminal for grounding |
|
Yes |
Yes |
|
Viwefinder of oil level |
|
Yes |
Yes |
|
Well for measure temperatures |
|
Yes |
Yes |
3.4 |
Telescopic pole operation of 6 bodies, 33 KV |
|
yes |
yes |