1.Introduction
ZW32-15KV/27KV/38KV Outdoor Dead Tank Vacuum Circuit Breaker is designed to meet all applicable ANSI, NEMA and IEEE standards.
ANSI/IEEE C37.04-1999 rating structure for ac high-voltage circuit breakers
ANSI/IEEE C37.06-2009 preferred ratings ac high-voltage circuit breakers
ANSI/IEEE C37.09-1999 test procedure for ac high-voltage circuit breakers
NEMA SG4-2009 ac high-voltage circuit breakers.
2.Magnetic-actuator operator features:
Design adapted from type TD stored-energy operator configuration, High-voltage compartment configuration identical to stored energy version
Design tested to ANSI/IEEE C37.09, Built-in fast discharge circuit for electronic controller power capacitors
Manual opening handle requires very modest force for operation, Electronic controller life estimated at 30 years.
4.SPECIFICAITON
ITEM |
UNIT |
15KV |
27KV |
38KV |
Lightning Impulse Withstand Voltage 1.2/50us |
KV |
110 |
150 |
200 |
Power Frequency Withstand Voltage |
KV |
50 |
60 |
80 |
Rated Short Circuit Breaker |
KA |
20/25/31.5 |
20/25/31.5 |
20/25/31.5 |
DC Component |
% |
48% |
48% |
48% |
Rated Making Closing Current |
KA |
52/65/82 |
52/65/82 |
52/65/82 |
Rated duty cycle |
|
o-3s-180s-co |
o-3s-180s-co |
o-3s-180s-co |
Rated Current |
A |
630/1250/2000 |
630/1250/2000 |
630/1250/2000 |
Rated Transient Recovery Voltage |
Uc TRV Peak Value |
29.2 |
52 |
71.7 |
|
Time to voltage Uc |
32 |
45 |
59 |
Heater |
w |
3x100w |
3x100w |
3x100w |
Auxiliary voltage |
DC/AC |
125/220 |
125/220 |
125/220 |
Radio Influence Voltage |
RIV 1000KMZ |
LESS 600 |
LESS600 |
LESS600 |
CT Input side |
|
0.2/5P/5VA |
0.2/5P/5VA |
0.2/5P/5VA |
CT Output side |
|
0.2/5P/5VA |
0.2/5P/5VA |
0.2/5P/5VA |
With Control |
|
CHK |
CHK |
CHK |