Technical data |
Unity |
Specification |
offered |
Observations |
1) Technical data |
1.1 |
Brand |
|
(*) |
HEMG |
|
1.2 |
Model |
|
(*) |
CJ |
|
1.3 |
rated torque: 500 |
NM |
Required |
500 |
|
1.4 |
Operating frequency: 60 |
Hz |
Required |
60 |
|
1.5 |
Operating Voltage: 125 ± 10% |
vdc |
Required |
125VDC+/-10% |
|
1.6 |
Type of operation |
|
|
|
|
1.6.1 Electric |
|
Required |
ELECTRIC |
|
1.6.2 Manual crank |
|
Required |
MANUAL CRANK |
|
1.7 |
keypads |
|
|
|
|
1.7.1 Opening: Green Color |
|
Required |
GREEN COLOR |
|
1.7.2 Close: Color Red |
|
Required |
RED COLOR |
|
1.8 |
Wiring contact closing and opening available in borneras |
|
Required |
YES |
|
1.9 |
Position selector |
|
|
|
|
1.9.1 Local |
|
Required |
LOCAL |
|
1.9.2 Remote |
|
Required |
REMOTE |
|
1.9.3 Maintenance |
|
Required |
MAINTENANCE |
|
1.10 |
Motor Voltage: 125 |
Vdc / Vac |
Required |
125VDC |
|
1.10.1 Operating voltage range: |
vdc |
80 to 150 |
80-150 |
|
1.11 |
Control coils 125 |
vdc |
Required |
125VDC |
|
1.11.1 Operating voltage range: |
vdc |
80 to 150 |
80-150 |
|
1.12 |
Limit (Limit Swich) Adjustable: |
Degrees |
90 and 180 |
90/180 |
|
1.13 |
Direction of rotation for opening: Schedule |
|
Required |
ANTICLOCKWISE |
|
1.14 |
Breaker protection shot Auxiliary Contact |
|
Required |
YES |
|
1.15 |
Heating |
|
Required |
|
|
1.16.1 Heating Voltage: 120 |
Vac |
Required |
120VAC |
|
1.16.2 Adjustable Temperature: |
° C |
≥30;≤55 |
≥30;≤55 |
|
1.17 |
contacts |
|
|
|
|
1.17.1 normally open contact 10 |
c / u |
Required |
10 |
|
1.17.2 Contact normally closed 10 |
c / u |
Required |
10 |
|
1.18 |
Block wiring contacts available on terminal blocks |
|
Required |
YEW |
|
1.19 |
Lamp for indoor lighting |
|
|
|
|
1.19.1 Lamp type: LED |
|
Required |
YES |
|
1.19.2 Lamp power |
W |
(*) |
10W |
|
1.20 |
The lower cap must be removable and smooth. |
|
Required |
YES |
|
1.21 |
Set in block control terminals, power and signaling |
|
Required |
YES |
|
1.22 |
Landing site |
|
Required |
|
|
1.22.1 Landing Holes: 2 |
c / u |
Required |
2 |
|
1.23 |
DC Contactor: 2 |
c / u |
Required |
2 |
|
1.23.1 force contacts NA: 4 |
c / u |
Required |
4 |
|
1.23.2 auxiliary contacts NC: 2 |
c / u |
Required |
2 |
|
1.23.3 auxiliary contacts: 2 |
c / u |
Required |
2 |
|
1.24 |
Lock system |
|
|
|
|
1.24.1 Lockout |
|
Required |
YES |
|
1.24.2 Mechanical lock |
|
Required |
YES |
|
1.25 |
Degree of protection: IP55 |
|
Required |
IP55 |
|
1.26 |
Manufacturing material: aluminum or stainless steel |
|
Required |
|
|
1.27 |
Fixing brackets 4 5/8 holes in galvanized steel bar |
|
Required |
STAINLESS STEEL |
|
1.28 |
Disconnector opening time: |
Sec. |
≤9 |
<=9 |
|
1.29 |
Construction standards: IEC 62271-102, 62271-1 |
|
Required |
IEC62271-102,IEC62271-1 |
|
1.30 |
Or latchkey lock: Handle with possibility to type padlocked |
|
Required |
YES |
|
1.31 |
Control planes: |
|
Required |
YES |
|
2) testing and factory testing |
2.1 |
IEC 62271-1, 60255-5 and 62271-102 a) Insulation Resistance Motor b) opening and closing speed c) Rotation d) electrical and mechanical lock e) Test torque |
|
Required |
YES |
|
|
|
|
|
|