item | Description | Unit | PEDEEE Requirements |
Bidder Specification |
1 | Manufacturer reputation/skills/quality check | HEMG | ||
2 | ISO9001 Certificate | ISO | ||
3 | Type of circuit breaker | VACUUM | ||
4 | Type designation | INDOOR | ||
5 | Rated frequency | Hz | 60 | 60 |
6 | Rated voltage
|
kV kV |
17 20 |
24 20 |
7 | Rated normal current at 50ºC ambient temperature
|
A A |
≥630 ≥1250 |
≥630 ≥1250 |
8 | Rated breaking current capacity
|
20 |
25 |
|
9 | Rated peak making current, kA (peak) | ≥62.5 | ≥62.5 | |
10 | Rated peak short-circuit current, kA (peak) | 50 | ||
11 | Rated short time current
|
≥25 |
≥25 |
|
12 | Rated line charging breaking current | A | ||
13 | Rated cable charging breaking current | A | 25 | |
14 | Rated small inductive breaking current | A | ||
15 | Rated breaking current under out of phase conditions | kA | 17.4 | |
16 | Restricting voltage
|
|||
17 | Fist pole to clear factor | 1.5 | ||
18 | One minute power frequency withstand voltage phase to earth, kV(rms)
|
≥50 ≥50 |
65 65 |
|
19 | Lighting impulse withstand voltage 1.2/50 microsecond | ≥125 | 125 | |
20 | Rated operating sequence | O-0.3s-CO-180s-CO | ||
21 | Capacity to make | 75 | ||
High speed three phase auto recluse | ||||
22 | Minimum time between each successive break/make operation | Sec | ≤2 | |
23 | Opening time (until separation of the arcing contacts
|
ms ms |
50 50 |
|
24 | Maximum total break time (until total are extinction) |
ms | ≤50 | |
25 | Maximum time interval between opening of the fist and last phase | ms | ≤2 | |
26 | Maximum time interval between opening of the interrupters of one phase (if any) | ms | ||
27 | Make tine
|
ms ms |
||
28 | Maximum total make time (closing initiation to latching of circuit breaker in fully closed position) | ms | ≤75 | |
29 | Maximum time between closing of fist and last phase | ms | ≤2 | |
30 | Maximum time interval between closing of interrupters of one phase | ms | ||
31 | Dead time | ms | ≤300 | ≤300 |
32 | Maximum peak value of switching over voltage when interrupting rated line charging current, kV(peak) | |||
33 | Radio influence voltage (RIV) measured at rated voltage to earth, micro V | |||
34 | Devices used to limit transient recovery voltages | |||
35 | Creepage distance
|
|||
36 | Operating mechanism type
|
VDC % |
220,110 -20 +10 |
220,110 -20 +10 |
37 | Closing release coil
|
VDC % % W |
220,110 -20% +10 |
220,110 -20% +10 |
38 | Trip release coil rated operating voltage
|
VDC % % W |
220,110 -30% +10% |
220,110 -30% +10% |
39 | Distance:
|
275mm |
||
40 | Weight of circuit breaker
|
138kg |
||
41 | Type certificate details:
|
YES | ||
42 | The interrupter vacuum cubicle/country of origin | CHINA |