24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel
  • 24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel
  • 24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel
  • 24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel
  • 24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel
Find Similar Products

Basic Info.

Model NO.
VS1
Speed
High-Speed Circuit Breaker
Arc-extinguishing Medium
Vacuum
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification
ISO9001-2000
Transport Package
Wooden Case
Specification
24kv
Trademark
HEMG
Origin
China
Production Capacity
50000

Product Description



24kv 50Hz/60Hz Indoor Vacuum Circuit Breaker for Distribution Panel
 
item Description Unit PEDEEE
Requirements
Bidder
Specification
1 Manufacturer reputation/skills/quality check     HEMG
2 ISO9001 Certificate     ISO
3 Type of circuit breaker     VACUUM
4 Type designation     INDOOR
5 Rated frequency Hz 60 60
6 Rated voltage
  1. highest system voltage
  2. Minimum service voltage

kV
kV

17              20

24              20
7 Rated normal current at 50ºC ambient temperature
  1. for outgoing bay
b)  for incoming bay


A      A


630
1250


630
1250
8 Rated breaking current capacity
  1. Symmetrical kA (rms)
  2. DC Component %
 
20

25
9 Rated peak making current, kA (peak)   62.5 62.5
10 Rated peak short-circuit current, kA (peak)     50
11 Rated short time current
  1. 1 sec, kA (rms)
  2. 3 sex kA (rms)

 

25

25
12 Rated line charging breaking current  A    
13 Rated cable charging breaking current A   25
14 Rated small inductive breaking current A    
15 Rated breaking current under out of phase conditions kA   17.4
16 Restricting voltage
  1. rated of rise (RRRV), kV/Microsecond
  2. Peak, kV(peak)
     
17 Fist pole to clear factor     1.5
18 One minute power frequency withstand voltage
phase to earth, kV(rms)
  1. across open contacts, kV (rms)

 


50
50


65
65
 
19 Lighting impulse withstand voltage 1.2/50 microsecond   125 125
20 Rated operating sequence     O-0.3s-CO-180s-CO
21 Capacity to make     75
High speed three phase auto recluse      
22 Minimum time between each successive break/make operation Sec   2
23 Opening time (until separation of the arcing contacts
  1. without current
with 100% rated breaking current


ms
ms
 

50
50
24 Maximum total break time
(until total are extinction)
ms   50
25 Maximum time interval between opening of the fist and last phase ms   2
26 Maximum time interval between opening of the interrupters of one phase (if any) ms    
27 Make tine
  1. without current
  2. with 100% rated making current

ms
ms
   
28 Maximum total make time (closing initiation to latching of circuit breaker in fully closed position) ms   75
29 Maximum time between closing of  fist and last phase ms   2
30 Maximum time interval between closing of interrupters of one phase ms    
31 Dead time ms 300 300
32 Maximum peak value of switching over voltage when interrupting rated line charging current, kV(peak)      
33 Radio influence voltage (RIV) measured at rated voltage to earth, micro V      
34 Devices used to limit transient recovery voltages      
35 Creepage distance
  1. to earth
  2. across terminals
     
36 Operating mechanism
type
  1. operating voltage
Rated,/rage


VDC
%


220,110
-20
+10


220,110
-20
+10
37 Closing release coil
  1. rated operating voltage
  2. minimum operating voltage
  3. maximum operating voltage
  4. rated power

VDC
%
%
W

220,110
-20%
+10
 

220,110
-20%
+10
 
38 Trip  release coil
rated operating voltage
  1. minimum operating voltage
  2. maximum operating voltage
  3. Rated Power

VDC
%
%
W

220,110
-30%
+10%
 

220,110
-30%
+10%
 
39 Distance: 
  1. Between phases (between the centers of the two phases "e8" in the attached drawing
  2. Between alive part and earth 
   
275mm


 
40 Weight of circuit breaker 
  1. total 
Heaviest part to be lifted during maintenance or repair producer
   
138kg
41 Type certificate details:
  1. testing station/authority
  2. certificate number
  3. applied standards
the technical specification doesn't mention on the supply of C.B cradle
    YES
42 The interrupter vacuum cubicle/country of origin      CHINA

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier