170kv/220kv/245kv Outdoor Hv 2 Columns Central Break Disconnector

Product Details
Customization: Available
Type: High-voltage
Structure: Double-column Disconnector
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 170kv/220kv/245kv Outdoor Hv 2 Columns Central Break Disconnector
  • 170kv/220kv/245kv Outdoor Hv 2 Columns Central Break Disconnector
  • 170kv/220kv/245kv Outdoor Hv 2 Columns Central Break Disconnector
Find Similar Products

Basic Info.

Model NO.
GW4
Operation
Electric
Grounding Mode
Grounding
Movement Mode
Horizontal Rotary Type
Number of Poles
Three Pole
Grounding
Single Ground
Structure of Operating
Electric
Certification
ISO, IS9001, ISO9001
Transport Package
Wooden
Specification
245KV
Trademark
HEMG
Origin
China
Production Capacity
50000

Product Description


170kv/220kv/245kv Outdoor Hv 2 Columns Central Break Disconnector
 
SPECIFICATION OF 245KV DISCONTECTOR 
3.1.2 DISCONNECTORS(ISOLATORS)  
Item                                                             No Description  Particulars OFFERED
245kV 245KV
1 Manufacturer    
1.1 Name  Pars Switch Co. HEMG
1.2 Country of origin  IRAN CHINA
2 Type/Designation  NSA245/3150D DS,DS+ES GW4-252KV
2.2 State whether end posts,vertical,centre break,etc H.C.B. CENTRA BREAK ,2 COLUMNS
2.3 Three phase or single phase 3Phase 3 PHASES
2.4 Earthing switch incorporated NVA245 JW10-252KV
3 Type of operating mechanism  BCM-F SCRJ2
4 Power at normal voltage required for:    
4.1 Operating coil                                                             W ------ (--)
4.2 Motor (where provided)                                              W 170 370W
5 Operating characteristics:    
5.1 Total time from initiation of opening operation to           s     isolator in fully open position  3 up to 5 10S
5.2 Time from contact separation to extinction of               s     capacitive arc 3 up to 5 10S
5.3 Total time from initiation of opening operation to time    s     when isolator gap can withstand phase voltage 3 up to 5 10S
6 Rated voltage                                                             kV 245 245KV
7 Rated normal voltage: a) for coupler bay                      A 3150 3150A
                                 b) for other bays                        A 3150 3150A
8 Maximum short time current                                   for(1    
                                                                          second/3    
                                                                          second )    
8.1 Disconnector                                                        kA rms 50(1S) 50KA(1S)
8.2 Earth switch                                                         kA rms 50(1S) 50KA(1S)
9 Total mass of three phase isolator complete               Kg 1100(shipping) 2665(SHIPPING)
10 Type pf earthing switch (where provided) NVA JW10-252KV
11 Type of operating mechanism for earthing switch  BCM-F SCRJ3
12 Basic insulation level at site altitude (IEC 694)    
12.1 Lighting impulse withstand level (1.2/50μs wave)                    positive and negtive    
12.1.1 To earth and between phases in the closed position    kVp 1050 1050KV
12.1.2 Between phases in the open position                         kVp 1050 1050KV
       
Item                                                             No Description  Particulars OFFERED
245kV 245KV
12.1.3 Across open gap     
12.1.3.1 Lightning impulse                                                        kVp 1200 1200KV
12.1.3.2 Lighnting impulse/Bias                                                kVp+ 1200 1200KV
                                                                                 kV ACP    
12.2 Switching surge withstand level (250/2500μs wave)    
at site altitude - positive and negtive          dry/wet    
12.2.1 To earth and between phases in closed position            kVp N.A. N.A
12.2.2 Between phases in open position                                 kVp N.A. N.A
12.2.3 Across open gap     
12.2.3.1 Switching surge                                                          kVp N.A. N.A
12.2.3.2 Switching surge/Bias                                                  kVp+ N.A. N.A
                                                                                 kV ACP    
12.3 Power frequency withstand voltage at site altitude    dry/wet    
12.3.1 To earth and between phases in closed position - 1       kV          minute 460 460KV
12.3.2 To earth and between phases in open position - 1         kV           minute 460 460KV
12.3.3 Across open gap -1minute                                             kV 520 520KV
13 In air clearances:    
13.1 Phase to earth aecing distance                                       mm please see DIM. Prints 2100MM
13.2 Phase to phase distance in open position                      mm please see DIM. Prints 2550MM
13.3 Distance between terminals of open isalator                 mm please see DIM. Prints 2200MM
14 Support insulators    
14.1 Manufaturer China CHINA
14.2 Type, designation of unit Brown glazed porcelain  BROWN GLASED PROCELAIN
14.3 Minimum creepage to earth (to IEC 815)                      mm 7500 7500MM
15 Protected creepage distance                                           mm 3204 3205MM
16 Radio influence voltage level measured at 1.1 times      μV             Us/3 at 1MHz 2500 2500MM
17 Maximum capacitive current that can be interrupted      A               by the disconnector   1A
Item                                                             No Description  Particulars OFFERED 
245kV 245KV
18 Operating mechanism for disconnecting switch:    
18.1 Type  BCM-F(MOTOR&HAND) SCRJ2
18.2 Operating voltage - rated/ min for :    
(a) operating coil (if any)                                     V -----  
(b)Motor                                                              V 220 VDC 220VDC
19 Opening time- from the moment when the coil is                               energised until the complete extinction of arc                between opened contacts( under system highest              voltage condition) 3 up to 5 10S
20 Operation time - from the moment when the coil is                           energised until the disconnectoon of operating motor      in limit open disconnected positioning. 3 up to 5 10S
21 Operating mechanism for earthing switch    
(a) type  BCM-F(MOTOR&HAND) SCRJ3
(b) operating voltage- rated/min/max 220 VDC 220VDC
(c)rated power 170 370W
22 Total weight of complete disconnecting switch ( one or                          three poles). 1100(shipping) 2665KG(SHIPPING)
23 Type test certificate details     
(a)testing station CESI - ITALY KEMA
(b)certificate numbers A6020791 TIC3010-03
3.1.3 EARTHING SWITCHES    
Item                                                             No Description  Particulars  
245kV 245KV
1 Manufacturer    
1.1 Name  Pars Switch Co. RGHY
1.2 Country of origin  IRAN CHINA
2 Type / Designation  NVA245(associated with earthing switch )/outdoor JW10-252
3 Type of contacts PIN PIN
4 Materials of contact surface Sliver Plated Copper SILVER PLATED COPPER
5 Rated short time current     
                (a) For 1 sec                               KA(rms) 50 50KA
                (b) For 2 sec                               KA(rms) ----  
6 Rated peak short current                              KA(peak) 125 125KA
7 Gap between poles                                       Mm Please see DIM.Prints 2050MM
8 One minute power frequency withstand           kV           voltage cross open gap       Please see type test reports 460KV
9 Lightning impulse withstand voltage  Please see type test reports 1050KV
10 Operating mechanism     
(a)Type  MOTOR&HAND(BCM-F) SCRJ3
(b)Operating voltage - rated/min                      V 220 VDC 220VDC
(c)Rated power                                             W 170 370W
11 Main dimensions                                         Mm Please see DIM.Prints SEE THE DRAWING 
12 Total weight                                                Kg Please see DIM.Prints SEE THE DRAWING 
13 Type test certificate details     
(a) Testing station/authority CESI-ITALY KEMA
(b)Certificate number  A6020791 TIC3010-03
(c)Applied standards IEC62271-102 IEC62271-102
14 Creepage distance                                        mm 7595 7595MM

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier