Bitmap General Specifications and Guarantee Schedule for outdoor silieone rubber termination for 36/66 kv .Single Core XLPE insulated Power Cable with round stranded Copper Conductor 1x630mm2.CU/XLPE/CU(wires+tapes) screen /HDPE sheath | ||||
No | Description | Unit | PETE requirements | Offered data |
1 | Name & country of Manufacturer | HEMG | ||
2 | Country of Origin | China | ||
3 | Outdoor termination type | Outdoor silicone rubber terminations | Outdoor silicone rubber terminations | |
4 | Outdoor termination designation | Prefabricated | ||
5 | Standards | Cenelee ho 628/629…iec60..332..502..vde..din | IEC60840 | |
6 | Climatic Design | c | (-10)to(55) | (-10)to(55) |
7 | Class and form of Conductor | Class 2 rounded stranded &compacted conductor | Class 2 rounded stranded &compacted | |
8 | Material of Conductor | Copper | Copper | |
9 | Rated voltage | kv | 36/66 | 36/66 |
9.1 | Termination suitable to be used with following cables: | Yes | ||
Conductor: | ||||
- Cross section | mm² | 1x630 | 1x630 | |
- diameter | mm | From 29.5 to 31.5 | From 29.5 to 31.5 | |
Conductor Screen: | ||||
- Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
- Thickness | mm | From0.85 to 1 | From0.85 to 1 | |
Insulation: | ||||
- Material | XLPE | XLPE | ||
- Thickness | mm | 12 | 12 | |
- Diameter over insulation | mm | From55to58 | From55to58 | |
Insulation screen: (S.C Layer): | ||||
- Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
- Thickness | mm | From0.85 to 1 | From0.85 to 1 | |
- Thickness of semi-conductive swelling Tape (lapped) | mm | From(0.3 to .5) | From(0.3 to .5) | |
Metallic screen: | ||||
- Cross section of earthing cu wires | mm² | 120 | 120 | |
- Diameter of cu wire | mm | 1.8 | 1.8 | |
- thickness of Copper Tape | mm | 0.2 | 0.2 | |
- Width of Copper Tape | mm | 20 | 20 | |
- thickness of longitude Swilling Tape | mm | 0.2 | 0.2 | |
Metallic Shield: | ||||
- thickness of Comp layer al (Coated Al ) | mm | 0.2 | 0.2 | |
Outer Protective Sheath (HDPE ST7 ) | ||||
- Material | HDPE ST7 | HDPE ST7 | ||
- Thickness of outer Sheath | mm | 4.5 | 4.5 | |
- Outer diameter of cable | mm | 70 | 70 | |
10 | Max. service voltage | kv | 72.5 | 72.5 |
11 | Rated frequency | Hz | 50 | 50 |
12 | Power frequency with stand voltage (a) | Kv/min | 90kv/30min | 90kv/30min |
13 | Partial discharge level | ≤10 PC at 1.5 U0 (54kv) | ≤10 PC at 1.5 U0 (54kv) | |
14 | Impulse with stand voltage 10 x (+)1.2/50us | kv | ±325 | ±325 |
15 | Power freq. with stand voltage (b) | Kv/min | 90kv/15min | 90kv/15min |
16 | Load cycling test Cycle:8h heating 16h cooling | According to iec 60840 on accessories | According to iec 60840 on accessories | |
Conductor temperature | 95oc-100oc | 95oc-100oc | ||
17 | Thermal short circuit current : | KA/1sec | ≥31 | ≥31 |
- 1sec/symmetrical fault with conductor temperature as for cable specification | ||||
18 | Resistively to mineral oil . Acids. Solvents | Yes | ||
19 | Saturated air | Yes | ||
20.1 20.2 20.3 | Water conductivity | Yes | ||
Spray rate | ||||
Salt tog test | ||||
21 | Humidity and congestion test | Kv/h | 42.5 | |
22 | Flame resistance test | IEC 332 | IEC 332 | |
23 | Submit copies of test reports by independent laboratory | Should be submitted | Yes | |
24 | Components ayers and materials of termination and their properties: | Yes | ||
24.1 | Lug | mm² | Conductor 630 mm²CU | Conductor 630 mm²CU |
24.2 | Electrical stress control system : | |||
- indicate shrink ratio properties : | mm | 5-8mm | ||
Design (shape ) | Cone | |||
- length | mm | 1000 | ||
-stress grading ( plot ) | Supplied with products | |||
24.3 | Insulation: | |||
24.4 | Leakage current insulation system : | Number of sheds(skirts):15 pcs.;Diameter of sheds:210mm;Total extended creepage distance: more than 2250 | ||
Number of sheds(skirts) | ||||
Diameter of sheds | mm | |||
Total extended creepage distance | mm | |||
24.5 | Shield. metal continuity CU screen wires Coated Aluminium tape | mm² | Cross section 120 | Cross section 120 |
24.6 | - outer sheath (outer cover ) | -indicate shrink ratio | 50% | |
24.7 | Submit detailed information and documentation about the components layers and materials of termination and their electrical &non-electrical properties | Provide separately | Yes | |
24.8 | Dimensions of termination after completion: | Diameters:220mm;overall length:1500mm | ||
-Diameters | mm | |||
- overall length | mm | |||
24.9 | Printed on tubes | Mandatory according to condition book | Yes | |
24.1 | The applicable range of termination (cross section of conductor) | mm² | The wide range is preferred | 240-2000 |
25 | Submit kit contents of termination | Complete list of kit contents with description | Yes | |
26 | Submit installation instruction | Provide separately | Yes | |
27 | Submit dimension drawing | Provide separately | Yes | |
28 | Shelf life | year | 15 | |
29 | Submit quality assurance certificates (ISO accreditation) | More certificates are preferable (i.e 9001.14001 etc.) | Yes | |
30 | Submit reference list | Provide separately | Yes | |
31 | Total weight of termination kit | kg | 25 | |
32 | Time of execution of one termination | minute | 480 | |
33 | Include any special tools for execution of the termination (if required) with detailed description of tools (with photo/drawings) | optional | None | |
34 | Total number of required termination | Qty | 50 | 50 |
No | Description | Unit | Requirements | Offered data |
1 | Name & country of Manufacturer | HEMG | ||
2 | Country of Origin | China | ||
3 | Joint type | Silicon rubber cable joint | Silicon rubber cable joint | |
4 | Joint designation | Prefabricated | ||
5 | Standards | Cenelee HO 628/629… IEC 60.332.502.. vde..din | IEC60840 | |
6 | Climatic Design | oc | (-10)to(55) | (-10)to(55) |
7 | Class and form of Conductor | Class 2 rounded stranded &compacted conductor | Class 2 rounded stranded &compacted | |
8 | Material of Conductor | copper | copper | |
9 | Rated voltage | kv | 36/66 | 36/66 |
9.1 | Termination suitable to be used with following cables: | Yes | ||
Conductor: | ||||
- Cross section | mm² | 1x630 | 1x630 | |
- diameter | mm | From29.5to31.5 | From29.5to31.5 | |
Conductor Screen: | ||||
- Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
- Thickness | mm | From 0.85 to1 | From 0.85 to1 | |
Insulation: | ||||
- Material | XLPE | XLPE | ||
- Thickness | mm | 12 | 12 | |
- Diameter over insulation | mm | From55 to58 | From55 to58 | |
Insulation Screen: (S.C Layer): | ||||
- Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
- Thickness | mm | From 0.85 to 1 | From 0.85 to 1 | |
- Thickness of semi-conductive swelling Tape (lapped) | mm | From(0.3 to0.5) | From(0.3 to0.5) | |
Metallic Screen: | ||||
- Cross section of earthing cu wires | mm² | 120 | 120 | |
- Diameter of cu wire | mm | 1.8 | 1.8 | |
- thickness of Copper Tape | mm | 0.2 | 0.2 | |
- Width of Copper Tape | mm | 20 | 20 | |
- thickness of longitude Swilling Tape | mm | 0.2 | 0.2 | |
metallic Shield: | ||||
- thickness of Comp layer al (Coated Al ) | mm | 0.2 | 0.2 | |
Outer Protective Sheath (HDPE ST7 ) | ||||
- Material | HDPE ST7 | HDPE ST7 | ||
- Thickness of outer Sheath | mm | 4.5 | 4.5 | |
- Outer diameter of cable | mm | 70 | 70 | |
10 | Max .service voltage | Kv | 72.5 | 72.5 |
11 | Rated frequency | Hz | 50 | 50 |
12 | Power frequency | Kv/min | 90kv/30min | 90kv/30min |
13 | Partial discharge level | ≤10PC at 1.5U0(54kv) | ≤10PC at 1.5U0(54kv) | |
14 | Impulse withstand voltage 10x(+)1.2/50us | kv | ±325 | ±325 |
15 | Power freq.with stand voltage (b) | Kv/min | 90kv/15min | 90kv/15min |
16 | Load cycling test cycle:5 h heating 3 h cooling | 3 cycles | 3 cycles | |
-conductor temperature | 90ºC+10ºC | 90ºC+10ºC | ||
17 | Thermal short circuit current : | KA/1sec | ≥31 | ≥31 |
- 1sec/symmetrical fault with conductor temperature as for cable specification | ||||
18 | Resistively to mineral oil . acids. solvents | Yes | ||
19 | Humidity and congestion test | Kv/h | 41.8 | |
20 | Flame resistance test | IEC 332 | IEC 332 | |
21 | Submit copies of test reports by independent laboratory | Should be submitted | Yes | |
22 | Components layers and materials of joint and their properties: | |||
22.1 | Conductor connector | Bolted or mechanical ( pressure ) | Pressure | |
22.2 | Electrical stress control system : | Design (shape ): Stress cone;length:610mm. | ||
- indicate shrink ratio properties : | mm | 8-12mm | ||
- Design (shape ) | Cylindrical | |||
- length | mm | 610 | ||
-stress grading ( plot ) | Supplied with products | |||
22.3 | Insulation: | mm | ||
Screening | Thickness:0.5 | |||
22.4 | Shield. Metal continuity CU screen wires coated Aluminium tape | mm² | Cross section 120 - 130 mm² | Cross section 120 - 130 mm² |
22.5 | Outer sheath ( outer cover ) | Heat shrink tube with adhesive (in one picce ) (heat melt adhesive) | 50% | |
Indicate shrink ratio | ||||
22.6 | Submit detailed information and documentation about the components layers and materials of termination and their electrical &non-electrical properties | Provide separately | Yes | |
22.7 | Dimensions of termination after completion: | Diameters:200mm;overall length:1500mm | ||
-Diameters | mm | |||
- overall length | mm | |||
22.8 | - printed on all heat shrink tubes | Mandatory according to condition book | Yes | |
22.9 | The applicable range of joint ( cross section of conductor ) | mm² | The wide range is preferred | 240-2000 |
23 | Submit kit contents of joint | Complete list of kit contents with description | Yes | |
24 | Submit installation instruction | Provide separately | Yes | |
25 | Submit dimensions drawing | Provide separately | Yes | |
26 | Shelf life | Year | 15 | |
27 | Submit test reports of all materials of joint kit | Provide separately | Yes | |
28 | Submit quality assurance certificate ( ISO accreditation ) | More certificates are preferable ( i.e 9001 . 14001 ete ) | Yes | |
29 | Submit reference list | Provide separately | Yes | |
30 | Total weight of joint box | Kg | 85 | |
31 | Time of execution of one joint | Minute | 500 | |
32 | Include any special tools for execution of the joint ( if required) with detailed description of tools ( with photo/drawings) | Optional | None | |
33 | Total joints | Qty | 200 | 200 |