33kv Outdoor Vertical Installation Double Side Break Disconnect Switch

Type: High-voltage
Structure: Three-column Disconnector
Installation: Outdoor High-voltage
Operation: Electric
Grounding Mode: Grounding
Movement Mode: Horizontal Rotary Type
Customization:

Contact Supplier

Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
GW7B
Number of Poles
Three Pole
Grounding
Single Ground
Series
Two
Run
Vertical Rotation
Switching Mode
Single Throw-in
Common Model
YR
Structure of Operating
Electric
Certification
ISO
Brand
Hemg
Transport Package
Carton with Wooden
Specification
33KV/72.5KV/145KV
Trademark
HEMG
Origin
China
Production Capacity
50000PCS

Product Description

 
Double Break Three Columns High-voltage Dis-Connector
 
Model No : GW7-145
33kv Outdoor Vertical Installation Double Side Break Disconnect Switch

 
 
1. Overview
 
1.1 GW7-145D (W) High-voltage Dis-connector (Hereinafter referred to as the disconncetor),it switch under the 145kV, 60Hz high voltage lines in the no-load current, and maintenance of high-voltage lines are and other electrical equipment with live electrical lines for three-pole high-voltage electrical isolation. Which part is called earth switch, and the rest said the main switch.
The disconnector moving contacts for complex rotary motion, the existing GW7 series disconnector, principles and structure of the work had significant improved. 
  1.2 The disconnector operate with CJ ─3 for the three-phase linkage.For single grounding type disconnector, main link and ground link interlocked through interlocking board. For the doubled grounding type disconnector, it should be work in with CS9 manual mechanism.
  1.3 Ground link and main link have mechanical interlock device, manual mechanism also can increase electromagnetic lock to prevent misuse.
  1.4 the disconnector satisfy the following standard:
1.4.1 IEC  62271-102 / IEC 60265 / ANSI C37.32
1.4.2  GB1985/GB311.1/GB311.2 ~6 /GB/T11022/GB/T13384/GB3309                                 
 
 
2. Technical data and operating conditions table 1
  Items Parameter Unit Remarks
1 Rated voltage 138 KV  
2 Rated frequency 60 Hz  
3 Rated Current 1250 2500 3150 A  
4 Rated peak withstand current 100 125 kA  
5 Rated short time withstand current 40 50 kA  
6 Rated short-time withstand current duration 4 S earth switch 3S
7 Frequency withstand voltage (RMS) Earth, Alternate 275 kV  
Fracture 325
8 Lightning impulse withstand voltage (peak 1.2 / 50μs) Earth, Alternate 650 kV  
Fracture 750
9 Mechanical life 10000 Frequency earth switch 1000TIMES
10 Environment and conditions Altitude 1000(2000)(3000) m  
wind pressure 700 Pa  
seismic intensity 8 degree  
Ice thickness 10 mm  
environment temperature -40 to 40 ºC  
11 Rated static terminal Rally endwise 1500 N  
cross 1000  
vertical 1250  
12 creepage distance Antifouling  3 level 3450 mm  
Antifouling  4level 4350 mm  
13 Motor Drive Parameters Opening time 7/12±1 S  
Closing time 7/12±1 S  
Motor power 550 W  
Control Power AC125/220 V  
DC125/220  
Motor Power AC125 V  
Auxiliary contacts According to the contract    
Output angle 180 degree  
14 Manual mechanism Parameters Auxiliary contacts According to the contract    
Output angle 90 degree  
15 Disconnector main circuit resistance 130 μΩ Both ends of the connection plates
16 Earth switch loop resistance 250 μΩ    Soft coupled to ground static contact
17 Insulation distance after disconnector open 2 m  
18 Insulation distance after earth switch open 1.8 m  
19 Disconnector three-pole closing period 20 mm  
20 Earth switch three-pole closing period 15 mm  
21 Final pressure of disconnector' contact 120 N  
                 
 
3. Structure and working principle
 
3.1  GW7 dis-connector is three-column double fracture ,The level of division and three-pole linkage type,also can use uni-polar,it consist of main switch .earth  switch and actuator. Main switch consist of brace, porcelain insulators and conductive portions.
 
3.2  motor process of dis-connector is a compound composed of two parts made of rotational motion ,That horizontal rotation and vertical rotary motion. Dis-connector contact system is complex rotary (See Figure A). At both ends of the base frame 1 is provided with the support porcelain insulators 3 ,At its upper end with the stationary contact base 12,in the middle of the base has a driven shaft,The shaft is fixedly connected with the rotary flange 2, An operating porcelain insulators 4 on a rotating flange. Motor drive rotate flange and operating porcelain insulators ,by positioning the trip mechanism and fork mechanism drives the movable contact rod holder 7 and moving contacts 6,synchronously rotating it from the OFF position to the closed position.In the closing position, driven by a horizontal rod 8 9 realize swing block commutation trip, movable contact rod holder 7 does not make the rotation, driven fork lever 15 about its own axis conductive rod 6 flipped so that the conductive bars on the movable contact 6 head and static contact completely closing.
3.3  A mechanical interlock between the main switch and earth switch. For interlock between the front and rear breaker, electromagnetic locks can be installed outdoors. For no grounding and grounding with CJ -3 single type operating mechanism for double ground was equipped CS9-G manual mechanism.
 
3.4  Structure and working principle of earth switch
Earth switch(see the right picture) ,the movement is by CJ -3 institutions operating lever to earth switch through a link after the conversion, driving a four-link active grounding arm rotation, due to the active arm and door type bracket and earthing pipe is composed according to the design requirements special four-link system, thus ensuring the earth switch in the closing process, the first rotary motion, near the closing position, linear motion upward, insert static inner contact, opening and vice versa.

4 Installation and Test
 
Before installation, according to the packing list before unpacking inventory of spare parts, under the premise of complete components before installation, if found oxide layer in the surface need to use sandpaper or steel brush to remove, wipe with a cloth coated with oil and then quickly installation can be carried out after the temperature grease.
 
4.1 Installation and commissioning of each phase dis-connector
4.1.1  It is shown in Figure, the base 1 is mounted with bolts on the basis of the installation should pay attention to put the pads. And the base plate should be placed with a relative. Then check with the spirit level on the base plane is level, if not the level of the need to add shimming between the base and foundation.
 4.1.2   The three porcelain insulators are lifting in the end under the seat, secured with bolts. On the ground, and the two stationary contacts, respectively, with the upper porcelain insulator bolt preloaded together. And integral lifts on both ends of the base, note the direction of the two seats facing opposite stationary contact.
  4.1.3  The movable contact lever member 6 and a porcelain insulator pre-install together with bolts, the integral lifting to the middle of the rotation on the base flange. Fork lever 15 is biased in the operating side of 4 porcelain, from the outside you can see a bolt head. Both ends of the stationary contact each seat fitted with a nylon hook plate, a static contact Ann seat thereon, and the other is mounted below it.
4.1.4 The requirements of grounding products, according to the position shown static contact with the ground bolt, fixed to the main switch static contact base, then place the knife moving contacts loaded clamping inner coupling, adjust the depth of insertion tubes, and the earth switch smooth closing.
  4.1.5  The main switch move to the position where just close, check that:
a: the ends of movable contact rod should be simultaneously exposed to static finger;
b: moving contacts of the upper and lower stationary contact centers should refer to the same height in the center row;
c: nylon hook board should not prevent the movable contact rod smoothly fit into the seat within the stationary contact
4.1.6  The main switch moves to the closing position, check that:
a: movable contact rod ends of the edge of the gap and static contact base should be the same (as shown enlarged in a four-I at the size);
b: nylon hook board should be effective hooked silver-plated movable contact plate;
c: Application feeler on the finger of each exposure. 
  4.2   When the three-phase disconncetor coupling and debug connection, all rotating parts are coated 2 # low temperature grease.
4.2.1   Installation and commissioning operating drive
4.2.1.1  After the installation phase main switch and put the main switch in the closing position, then CJ -3 operating mechanism, according to the position shown in Figure installed base in the three-pole on. Note that when you install, try to keep the institution main knife switch is coupled with the output shaft axis of the straight part of a grounding switch, the agency should maintain its operating shaft is coupled to the axis of the knife on the straight. To the horizontal in a vertical position.
4.2.1.2 connect switch and drive by coupling (Figure 2 Item 4), contact  (Figure 2 Item 3)and welded steel pipe.
 4.2.1.3 Adjusting the start of closing position:
Through that adjust the rotation angle of the coupling to solve. First CJ -3 agency shake to the closing position with the handle clockwise, then reverse direction after tightening the coupling nut roll on 6-8 laps, and then use the handle shake CJ -3 agency to carry out a closing operate and observe the action switch position adjustment in the event of the case as follows: Main switch opening is not in place, or opening and closing the interference is not in place, indicating that the initial angle of the initial angle of the main body does not match the switch should loosen the coupling nut on the adjustment in place after tightening.
4.2.2. Put each pole main switch into the closing position, and then install a three-phase link I provided, if the initial angular misalignment, can be adjusted three-pole linkage drawbar length by rotating the screw .
4.2.3  The main switch in the middle position, whether it touches a button or closing button opening main switch to observe the  direction of motion as expected, if not, immediately turn off the power, and swap any two of the three-phase power supply phase.
4.2.4  Three-phase earth switch connection and commissioning .
4.2.4.1  According to the method of couple main switch and switch , will be operating on a joint mechanism to link up with the switch.
4.2.4.2  The three-phase installation link that we provided, if the initial angular misalignment, can be adjust by turning the screw tripolar linkage drawbar length.
 
5 Operation, maintenance and repair
 
5.1  Inspection when used
5.1.1  Visual inspection of the main switch closing position should be set in a straight line .
5.1.2  Main switch fracture distance is not less than 2600 MM , earth switch fracture distance is not less than 2100MM.
5.1.3 Check the main switch three-pole on the same period of not more than 20 mm, the measurement method: When either one pole piece both sides of the movable contact means contact with the stationary contact when measured in addition poles moving away from static contact between L1, L2 . And 1/2 (L1 + L2) ≤20MM.
5.1.4  Check the three-pole of earth switch on the same period of not more than 15 mm, inspection methods, when either extremely dynamic and static contact fourth year when measured in addition poles move from static contact is not more than 15 mm.
5.1.5    After earth switch closes, head should be in place to insert static contact depth.
5.1.6  Connect the power supply, the electric mechanism is applied respectively, 85%, 100%, 110% of rated voltage, and three points respectively, closing operation, points, closing the position should be correct.
5.1.7  when Operate earth switch by motor drive, the force acting on the handle is not more than 200N.
5.1.8  The total loop resistance electric drop test disconnector and earth switches meets the technical parameters specified items, since this type disconnector is a double fracture, should measure the contact resistance with two poles, and its value should be less than 20%.
5.1.9  Check that the disconnector and earth switche can achieve reliable mechanical linkage, and electromagnetic lock action is reliable.
5.1.10 Check all parts of the axle pin and there is relative motion is coated with grease, if the bolts tightened.
 5.1.11 Check the disconnector'surface plate (coating)which damage or loss.
5.2  Maintenance and repair
Main switch , due to the moving parts are mounted in the middle of the conductive pipe inside the casing, seal better, it is generally two to three years before they need maintenance, but one should be under heavy filthy environments timely maintenance. Connecting rod shaft pin is directly exposed to the air, therefore, should pay attention to regular temperature grease coated # 2.
Maintenance should note the following :
Remove the parts in the process, pay attention to the mutual position of the recording between the various components, standard specifications in order to avoid errors when re-loading complex.
After repaired and refitted, the bottom shelf of all moving parts should be coated with a relatively low temperature grease # 2, all aluminum conductive surface in contact with aluminum, due to oxidation fast, it should be coated with a layer of Vaseline, use sandpaper or steel brush Press grid mode rubs (removing the oxide layer) with a cloth to wipe off the oil, immediately re-coated with a thin layer 2 # low temperature grease, before assembly.
Maintenance projects include: insulators decontamination; mechanical rotating joint inspection; contact contacting health checks, etc.
 
6 Technical parameters and the use of electromagnetic locks
 
CS9-G (F) Manual operating mechanism operating angle of the disconnector is 90 degrees, and it can be attached DSW Outdoor electromagnetic locks, to achieve main switch, earth switch and circuit breakers between the three connection, thereby preventing the occurrence of an electrical malfunction of the accident.
 
6.1 Technology parameters of Electromagnetic lock in Table 2:
                                       
Electromagnetic lock AC DC
Rated voltage(V) 220/125 200 125
Rated current(A) 0.3/0.5 0.25~0.35
 
 
6.2   The use of electromagnetic locks
When the main control circuit the signal is given, the operator depresses the electromagnetic lock with the index finger of the operating lever, the auxiliary contact in the lock is turned on, while the upper end of the operating lever is pulled back to the thumb plate, that can pull the lock bolt, to unlock, then the operator to rotate with the other hand grounding switch manually agency handles, electromagnetic lock bolt is inserted into the card automatically block to block within the lock plate notch on the spindle, so that agencies cannot continue or the handle back and forth action, so that it controls points or co-location of the grounding switch, to avoid the purpose of the interlock to prevent misuse.
In order to deal with emergency situations, in front of electromagnetic locks, there is an emergency unlocking hole, when in the event of loss of power still open electromagnetic lock bolt, simply by inserting a special key with 30 ° rotation within the keyhole, you can unlock by operating lever.
Specifications of a three phase disconnector 22kV 
Features Order
Quantity 2
Model/type GW
Manufacter HEMG
Origin CHINA
Installation outdoor, 1000 meters over sea level
Service condition temperature: 0-40 °C
relative humidity: 93%
Standards of manufacturing and testing IEC 62271-1/ANSI C.37
Number of phases 3
Frequency 60 Hz
Nominal voltage (phase-phase) 22 kV
Max. Voltage 24 kV
BIL 50 kVrms (60Hz, 0 masl)
125 kVp (1,2x50 µs)
Nominal current 1200 A
Isc (3 seconds) 20 kA
Isc (3 seconds) for ground blade 20 kA
Minimum Creepage distance 600 mm
Pole distance  1200MM
Operated mechanism motor/manual
Auxiliary service Vac=127-220 Vac (3 phases)
Vdc=125 Vdc
Maximum Vdc (auxiliary service) 140Vdc
Minimum Vdc (auxiliary service) 70 Vdc
Open time (s) 4
Close time (s) 4
Driving force {Kg} 500NM
Control motor box IP 44
interlock coil
auxiliary switch (8 open/8close) - main blade
auxiliary switch (3 open/3 close) - ground blade 
Electromechanical interlock  yes
Installation position vertical 
Ground blade  yes
Maximum contacts temperature 65 °C
Porcelaing color grey/dark brown 
Control wiring  600 V Cu
Temperature: 90°C
Color code (winding)  
DC circuits BROWN/BLUE
AC circuits RED/YELLOW/GREEN
Maximun wind speed 90 Km/h
Isc for relays and switch (protection) 2A
Dielectric strenght AC and DC circuits 2 kV (1 minute)
Spares a single phase disconnector
motor 125 Vdc
Accessories kit for open/close mechanism 

Send your message to this supplier

*From:
*To:
avatar Mr. Tailichen
*Message:

Enter between 20 to 4,000 characters.