ITEM | PARAMETER | UNITY | SPECIFICATIONS | ||||
REQUIRED | PROPOSAL | ||||||
1 | Name Manufacturer | Specify | XD/HEMG | ||||
2 | Country Factory | Specify | CHINA | ||||
4 | E-mail contact representative: | Specify | tailichen | ||||
5 | Model | Specify | Lw24 | ||||
6 | Warranty period | months | 24 | 24 | |||
7 | Standards | IEC-62271-100 | IEC62271-100 | ||||
dead tank | DEAD TANK | ||||||
8 | Type | ||||||
9 | Number of poles | 3 | 3 | ||||
10 | Installation Site | Outdoor | OUTDOOR | ||||
eleven | Installation height | m | 2800m | 2800 | |||
12 | nominal frequency of the system | Hz | 60 | 60 | |||
13 | Nominal system voltage | kv | 69 | 69 | |||
14 | Maximum operating voltage | kv | 72.5 | 72.5 | |||
15 | Test Voltage 60 Hz., Applied for 1 minute | kv | 185 or more | 185 | |||
16 |
Test voltage wave impulse with 1.2 / 50 µs. (BIL or LIWL) | ||||||
kv | 450 or higher | 450 | |||||
17 | Downtime | cycles | 3 | 3 | |||
18 | Symmetrical interrupting capability | KA | 25 | 25 | |||
19 | Steady stream | TO | 1200 | 1250 | |||
20 | Means of extinction | SF6 | SF6 | ||||
21 | Voltage control and drive operation | vdc | 125 | 125VDC | |||
22 | Operating voltage charging motor spring | vdc | 125 | 125VDC | |||
2. 3 | Closing coil | 1 | 1 | ||||
24 | Trip coil | 2 | 2 | ||||
25 | Voltage heaters | Vac | 240/220/208 | 220V | |||
26 | Power resistance heaters | W | Specify | 2X100W | |||
27 | Type operating mechanism | Motor-Spring | MOTRO-SPRINGO | ||||
28 |
O - 0.3 s - CO - 3 min. - CO | O-0.3S-CO-3MIN-CO | |||||
Sequence of Operation | |||||||
29 | External manual release mechanism | Yes | YES | ||||
30 | Full weight breaker structureless | kg | Specify | 1550 | |||
31 | Weight structure | kg | Specify | 150 | |||
32 | Pressure limit for operation | PSI | Specify | 0.4MPA | |||
33 | Gas volume per pole | m3 | Specify | 5KG | |||
3. 4 | Maximum loss of gas per year | m3 | Specify | <=1% | |||
35 |
terminal connectors | Al cable range 4/0 to 477 MCM. | |||||
YES | |||||||
36 | Maximum delivery | days | 180 | 180DAY | |||
37 | The offeror must include catalogs | YES | YES | ||||
38 | Closing coil replacement | unity | 3 | YES | |||
39 | Opening coil replacement | unity | 3 | YES | |||
40 | Motor replacement spring load | unity | 3 | YES | |||
Equipment, accessories minimal SF6 gas filling | |||||||
41 | Coupling for gas tank Coupler circuit breaker Input and output manometers Stopcock, input and output Hoses and other necessary for filling SF6 Gas bottle for filling |
YES |
characteristics |
Solicited specification |
Offered specification |
Rules(*): |
Fromthe International Electrotechnical Commission (IEC), particularly IEC 62271-100 and ANSI /IEEEC57.13 |
yes |
ANSI (American National Standards Institute)C 3704 - 1979 Rating structure; C 3706 - 1979 Preferred ratings; C 3709 - 1979 Test procedure; C 37010 - 1979 Aplication guide; C 37011 - 1979 Application guide for recorry transient voltage; C 37012 - 1979 Capacitance current switching. |
yes | |
Circuit breakers: |
Suitable for automatic reclosing tripolar Of high speed | yes |
CapacitySF6 gas replenishment during operation, enough gas for initial filling and additional reserve of 10%. | yes | |
suitable devicesPressure measurement with alarm contacts and lock cases of pressure loss, in addition to the safety valve. | yes | |
Right to workweather | yes | |
insulators |
Insulators / bushings (bushings) should beporcelain or polymer | porcelain |
MechanismOperation |
For local electrical operationor remotely. Selection should be through a local device provided with a removable key. | yes |
They must be drivenengine, opening and closing by spring. The mechanism should be contained in a cabinet weatherproof, dust and corrosion, IP55 according to IEC-60529 | yes | |
Must beFree shot, according to IEC-62271-100, with anti-pumping device. | yes | |
Hecommand must be the tripolar type. The breaker poles shall be suitably interconnected to ensure a simultaneous and tripolar positively secure operation. | yes | |
must be provideda locking device that locks the circuit breaker closing when no sufficient accumulated or if the density of SF6 is under the permissible level energy, the circuit breaker must bloquearse- | yes | |
Once an opening or closing operation, it must always be completed without interruption and independent of external media. | yes | |
The engines load springs must be fed continuously and / or alternating current. | yes | |
It must exista visual indicator of the position of the breaker contacts, which will be installed externally. the word "OPEN" on a background of green and use the word "CLOSED"ona background of red. | yes | |
Cabinet Command and Control |
Beweatherproof, dust and corrosion and must be protected against accidental contact and be tight dropwise with degree of protection IP55 according to IEC- 60529 | yes |
For the tripolar electric driveLocal must be provided at least buttons for "opening" and "closing" and the selector "local-remote", located so that allow the operator to maneuver from the ground level. The LOCAL-REMOTE selectors must have two additional type auxiliary contacts "a" and "b" available for remote signaling | yes | |
It must be provideda counter of the number of operations of the circuit breaker. Removable plates must be provided in the bottom of the cabinets for inlet ducts, with enough space for the connection of external wiring | yes | |
Everybodycomponents cabinets must be connected to terminal blocks designed for conductor cross-section up to 10 mm2. They are left, at least 10 free terminals for customer use. | YES | |
Internal wiringcabinets will be made with a minimum wire section 3.31 mm2(12 AWG) insulated 600 V, and feature fire resistance, moisture and mildew. | YES | |
Cabinets shall be providedan anti-condensate resistance with thermostat, hygrometer and circuit breaker, a lamp for indoor lighting circuit breaker and an electrical outlet. All these devices are suitable to operate at 120 VAC. | yes | |
terminals |
terminals circuit breakers must be copper-coated silver (alternatively be tinned), with perforations according to NEMA standards. | yes |
Foreach terminal a suitable connector tube driver or characteristics that determine the ED's be supplied promptly | yes | |
Circuit breakerswill be supplied with terminal connectors grounding suitable for copper conductor wiring 2 AWG to 4/0 AWG, located at opposite ends diagonally | yes | |
accessories |
supportsgalvanized steel mounting concrete foundations, if required, with bolts | yes |
platesidentification weatherproof and corrosion, in Castilian language, containing at least the information specified in IEC-62271-100 | yes | |
Blockauxiliary contacts 10-pole with contact convertibles normally open to normally closed. The ability of the contacts 10 will be minimal 48/125 A to V DC / AC C. Local media opening and closing the circuit breaker without control voltage | yes | |
Protectionmotor overload operation, where the case. | yes | |
Mediato lock by lock operation. | yes | |
Device gas filling and bottle SF6 | yes | |
Dispositivesgas control: - Pressure gauge with contactsalarm and lock - Valveoverpressure |
yes | |
In casebeing standardized design manufacturer, it is desirable to have means to enable connection of a recorder run of contacts. | yes | |
Prototype testing |
a) Seismic tests: Seismic tests for Circuit Breakers Dead Tank SF6 gas insulated required. The test consistsin applying vibrations forced through a horizontal movement exerted parallel to the main horizontal axes of the equipment. an acceleration of 0.33 g soil spectrum frequency response between 1 and 10 Hz, with a maximum duration of the earthquake will take 3 minutes. b) Mechanical tests (IEC 62271-100, clause 10.2.102.2). c) Tests temperature rise (IEC 62271-100, Clause 6.5). d) Dielectric tests (IEC-62271-100, clause6.2). e) Tests short circuit switch terminals (IEC 62271-100, clauses 6102-6106). f) Tests short line failure (IEC 62271-100, clause 6.109). g) Tests discordance switching phases (IEC 62271-100, clause 6110, IEC-267). h) Tests supportable short current (IEC 62271-100, Clause 6.6). i) Tests Interrupt line current load (IEC 62271-100, Clause 6.111.5.1). j) Tests interruption of small inductive currents (IEC 62271-100, Clause 4108). |
yes |
informationto be included in the offer |
certified copiesof Prototype test reports (of listings) made similar to those offered Circuit Breakers | yes |
schemesshowing the main dimensions of the circuit breaker and the general location of its components | yes | |
descriptive bulletinsand catalogs breakers, operation mechanisms, control cabinets and other important elements | yes | |
Sectional viewsshowing the design details of the equipment and its components. | yes | |
detailsof any particular element provided with the circuit breakers. | yes | |
CertificateAuthorized Distributor, issued by the manufacturer | yes | |
short instructionsinstallation, operation and maintenance of circuit breakers, operating mechanisms and their elements. | yes |