A.- THREE PH ASE RECLOSER 33 KV |
|
|
|
|
ITEM |
DESCRIPTION |
UNIT |
REQUIRED |
GUARANTEED |
1 |
RECLOSER |
|
|
|
1.01 |
COUNTRY |
|
TO INDICATE |
CHINA |
1.02 |
MANUFACTURER |
|
TO INDICATE |
HEMG |
1.03 |
MODEL |
|
TO INDICATE |
CHZ4 |
1.04 |
STANDARD |
|
ANSI C-37.60 |
YES |
1.05 |
TYPE |
|
OUTDOOR |
YES |
1.06 |
SYSTEM |
|
THREE PHASE |
YES |
1.07 |
OPERATION TYPE |
|
AUTOMATIC AND MANUAL |
YES |
1.08 |
ALTITUDE OF OPERATION |
MO.S.L |
2500 OR MORE |
YES |
|
ELECTRIC CHARACTERISTICS |
|
|
YES |
1.09 |
OPERATION VOLTAGE |
KV |
33 |
YES |
1.10 |
MAX, VOLTAGE OF THE EQUIPMENT |
KV |
38 |
YES |
1.11 |
NOMINAL FREQUENCY |
HZ |
60 |
YES |
1.12 |
NOMINAL CURRENT |
A |
630 |
YES |
1.13 |
NOMINAL SYMETRIC INTERRPTION CURRENT |
KA |
12.5 |
YES |
1.14 |
SPECIFIC LEAKAGE DISTANCE |
mm/KV |
31 |
YES |
1.15 |
BIL |
KV |
170 |
YES |
1.16 |
DISCHARGE VOLTAGE, DRY, 60 HZ, 1 MINUTE |
KV |
70 |
YES |
1.17 |
DISCHARGE VOLTAGE, WET, 60 HZ, 10 SECONDS |
KV |
60 |
YES |
1.18 |
CYCLE OF WORK ACCORD ANSI C-37.60 |
|
YES |
YES |
1.19 |
INTERRUPTIION WAY |
|
VACUUM |
YES |
1.20 |
INSULATION WAY |
|
SOLID DIELECTRIC OR GAS SF6 |
YES |
1.21 |
NUMBER OF ELECTRIC OPERATIONS |
|
10000 |
YES |
1.22 |
CURRENT MEASURE |
|
WITH CURRENT SENSORS |
YES |
|
INSTALLATION |
|
INDOOR |
YES |
|
SYSTEM |
|
SINGLE PHASE |
YES |
1.23 |
RELATION OF TRANSFORMATION |
A |
400/1. |
YES |
1.24 |
PRECISION |
% |
1% |
YES |
1.25 |
VOLTAGE MEASURE |
|
VOLTAGE SENSORS INTERNAL |
YES |
1.26 |
TYPE |
|
CAPACITIVE |
YES |
1.27 |
INSTALLATION |
|
IN BUSHING |
YES |
1.28 |
PRECISION |
% |
2.5 |
YES |
1.29 |
QUANTITY |
|
6 |
YES |
1.3 |
SENSITIVE GROUND FAULT CURRENT DETECTION. |
|
CURENT TRANSFORMER |
YES |
|
INSTALLATION. |
|
IN THE TANK (INSIDE THE TANK ) |
IN CONTROL TANK |
|
QUANTITY. |
|
1 |
YES |
|
TRANSFORMATION RELATION. |
Ma |
200/1.5 |
YES |
|
MECHANIC CHARACTERISTICS |
|
|
|
1.3 |
METALLIC HARDWARE |
|
|
|
|
MATERIAL |
|
STAINLESS |
YES |
|
STANDARD OF THE MATERIAL |
|
ASTM A575 |
YES |
|
STANDARD OF HOT GALVANIZED |
|
ASTM A 153 |
YES |
|
THICKNEES OF GALAVANIZATION MIN |
gr/CM2 |
800 |
YES |
1.31 |
MOUNTING |
|
ON CIRCULAR POLE |
YES |
1.32 |
MECHANISM OF OPERATION |
|
MAGNETIC ACTUATOR |
YES |
1.33 |
POSITION INDICATOR |
|
VISIBLE FROM THE SOIL |
YES |
1.34 |
OPERATION BETWEEN POLE WITH HOOK |
|
YES |
YES |
1.35 |
MANUAL LOCKING EMERGENCY (ATTACHED DRAWING) |
|
YES |
YES |
1.36 |
TOOL PROVIDED WITH MANUAL CONTROL |
|
YES |
YES |
1.37 |
WITH LIFTING HOOKS |
|
YES |
YES |
1.38 |
INDICATES THE LIFE OF CONTACTS |
|
YES |
YES |
1.39 |
NUMBER OF MECHANICS OPERATION |
|
10000 OR MORE |
YES |
1.40 |
FULLY ASSEMBLED |
|
YES |
YES |
1.41 |
WEIGHT |
|
|
YES |
|
PRINCIPAL TANK |
KG |
TO INDICATE |
75KG |
|
CONTROL BOX |
KG |
TO INDICATE |
35KG |
2 |
TANK |
|
|
|
2.01 |
MATERIAL |
|
STAINLESS STEEL |
YES |
|
CONSTRUCTION REQUIREMENTS |
|
INDICATE THE STANDARD |
YES |
2.02 |
COATING OF TIN IN TERMINALS AND CONDUCTIVE PARTS. |
|
8 um |
YES |
2.03 |
PROTECTION DEGREE |
|
Able to withstand pressure fresh water cleaning insulators. |
YES |
3 |
BUSHINGS |
|
|
|
3.01 |
COUNTRY |
|
TO INDICATE |
ZSW |
3.02 |
MANUFACTURER |
|
TO INDICATE |
HM |
3.03 |
STANDARD |
|
ASTM D624, DIN 63504,IEC 60587,ASTM G154, AST G 155. |
YES |
3.04 |
CHARACTERISTICS OF MANUFACTURE |
|
|
|
|
MATERIAL OF CORE |
|
FIBER GLASS OR RESYN |
YES |
|
INSULATION MATERIAL OF COVER HOUSING AND SHEDS |
|
Cycloaliphatic EPOXY RESIN |
YES |
|
ELONGATION AT BREAK |
% |
450 ( ACCORD STANDARD DIN 53504 ) |
YES |
3.05 |
TEAR RESISTANCE. |
N/M |
MAJOR OF 20 ( Standard ASTM D624) |
YES |
3.06 |
TRACKING AND EROSION RESISTANCE. |
|
CLASS 2A,4.5 ( IEC 60587 ) |
YES |
3.07 |
TESTING OF RESISTANCE TO UV RAYS. |
|
ACCORDING ASTM G154 AND ASTM G155 |
YES |
3.08 |
RANGE OF SECTION OF DRIVERS. |
|
16 TO 120 MM2 |
YES |
3.09 |
CONDUCTOR MATERIAL OF ELIGIBLE. |
|
CU/AL , CU/CU , AL/AL |
YES |
4 |
SYSTEM OF CONTROL AND PROTECTION |
|
|
|
4.01 |
COUNTRY |
|
SAME COUNTRY INDICATE POINT 1.1 |
YES |
4.02 |
STANDARD OF MANUFACTURE |
|
ANSI / IEEE 37.90 |
YES |
4.03 |
INSTALLATION |
|
OUTDOOR |
YES |
4.04 |
MANUFACTURER |
|
SAME MANUFACTURER INDICATE POINT 1.2 |
YES |
4.05 |
CATALOGUE |
|
TO INDICATE |
YES |
4.06 |
MODEL OF ELECTRONIC SYSTEM |
|
TO INDICATE |
CHK4 |
|
CONTROL BOX |
|
|
|
4.07 |
MATERIAL |
|
STAINLESS STEEL |
YES |
4.08 |
THICKNESS |
|
2 MM |
YES |
4.09 |
SURFACE |
|
BRIGHT PASSIVATING |
YES |
4.10 |
COLOUR |
|
TO INDICATE |
GREY |
4.11 |
PROTECTION DEGRE OF THE BOX |
|
|
|
|
CLOSE OPEN |
|
IP65 |
CLOSE IP65 |
|
INSULATION VOLTAGE TO 1 MINUTE |
|
2 KV |
YES |
|
INSULATION VOLTAGE TO IMPULSE |
|
6 KVp |
YES |
|
SUPPORT TO INTERFERENCE TESTING ACCORDING TO STANDARDS: |
|
SWC ANSI C37.90.1, IEC 61000-4-4- |
YES |
|
IMMUNITY TO INTERFERENCE RADIO WAVES. |
|
IEC 255-22-3 CLASS, ANSI C37.90.2 |
YES |
4.12 |
WITH NAMEPLATE |
|
YES |
YES |
|
CHARACTERISTICS |
|
|
|
4.13 |
FUNCTION |
|
WITH MICROPROCESSOR |
YES |
4.14 |
PRINCIPAL PROTECTIONS |
|
50/51,50N/51N,SEF,25,27,59,59N, 67 |
YES |
4.15 |
SECONDARY PROTECTIONS |
|
46.81 |
YES |
4.16 |
ADJUSTEMENT GROUPS |
|
2 MIN |
YES |
4.17 |
MIN CURRENT OF SHOOT |
|
|
YES |
|
FAILURE BETWEEN PHASES |
A |
20 or minor |
YES |
|
FAILURE TO GROUND |
A |
10 or minor |
YES |
|
SENSITIVY FAILURE |
A |
1 or minor |
YES |
4.18 |
SETTING ALLOWS PARAMETERS PROTECTION |
|
YES |
YES |
|
IEC STANDARD CURVES |
|
YES |
YES |
|
CUSTOM CURVES |
|
YES |
YES |
4.19 |
FAILURE TO GROUND |
|
YES |
YES |
4.20 |
MINIMUN VOLTAGES |
|
YES |
YES |
4.21 |
OVER VOLTAGE |
|
YES |
YES |
4.22 |
STATUS INDICATOR OF RECLOSERS |
|
|
YES |
|
PARAMETERS |
|
YES |
YES |
|
POSITION OF THE EQUIPMENTS |
|
YES |
YES |
4.23 |
ALLOWS STORAGE OPERATING EVENTS |
|
|
YES |
|
OPEN OR CLOSE |
|
YES |
YES |
|
LOSS VOLTAGE |
|
YES |
YES |
|
OPERATION CURRENT |
|
YES |
YES |
4.24 |
REPORT FUNCTIONS |
|
|
YES |
|
EVENT REGISTRATION NUMBER SYSTEM |
|
2048 |
YES |
|
EVENT REGISTRATION NUMBER OF DIAGNOSIS |
|
512 |
YES |
|
EVENT OF PERFIL LOAD REGISTRATION |
|
512 |
YES |
|
REGSITER OF NUMBER OF SHOOTS |
|
YES |
YES |
|
REGISTER OF COUNTER OF FAILURES |
|
YES |
YES |
|
NUMER OF REGISTER WAVE FORM |
|
32 |
YES |
|
REGISTRATION FORM |
|
COMTRADE or software application |
YES |
|
|
|
|
|
4.25 |
REPORT FUNCTIONS |
|
|
|
|
ERROR IN THE MEASUREMENT |
|
|
|
|
BEFORE FAILURE |
|
1% OR MINOR |
YES |
|
AFTER FAILURE |
|
3% OR MINOR |
YES |
|
MEASSUREMENTS OF INSTANTANEOUS VALUES |
|
V,I,F,P,Q |
YES |
|
ACTIVE AND REACTIVE POWER |
|
YES |
YES |
4.26 |
THE CONTROL MUST HAVE TO DISPLAY DATA AND ADJUSTMENT |
|
YES |
YES |
4.27 |
COMMUNICATIONS PROTOCOL (READY FOR INTEGRATION WITH SYSTEMS SCADA) |
|
DNP 3.0 |
YES |
4.28 |
COMMUNICATION PORTS |
|
|
YES |
|
ETHERNET |
|
YES |
YES |
|
COMMUNICATION WITH PERSONAL COMPUTER |
|
RS232, ETHERNET |
YES |
|
COMMUNICATION READ DATA |
|
RS232, ETHERNET, RS485 |
YES |
4.29 |
OPTION be commanded remotely WITH RADIO MODEM OR GSM MODEM. |
|
YES |
YES |
|
EFFORTS TO SAFE OPERATION. |
|
YES |
YES |
|
INPUT AND OUTPUT NEEDED FOR THIS EFFECT. |
|
YES |
YES |
4.3 |
CONFIURATION SOFTWARE |
|
|
|
|
ENVIROMENT |
|
WINDOWS |
YES |
|
SECURITY SYSTEM |
|
WITH PASSWORD |
YES |
|
INFORMATION DISCHARGE |
|
YES |
YES |
|
PROGRAMMING IN REMOTELY |
|
YES |
YES |
5 |
AUXILIAR ENERGY FEEDER SYSTEM |
|
|
YES |
|
SYSTEM |
|
SINGLE PHASE |
YES |
|
INCLUDE AUXILIAR TRANSFORMER FOR CONTROL BOX |
|
YES |
YES |
5.01 |
BATTERY |
|
|
|
|
COUNTRY |
|
TO INDICATE |
CHINA |
|
MANUFACTURER |
|
TO INDICATE |
LEOCH |
|
TYPE |
|
TO INDICATE |
LEAD ACID |
|
NOMINAL VOLTAGE |
|
TO INDICATE |
12VX2 |
|
NUMBER OF UNIT OPERATING VOLTAGE TO FAILURES. |
|
10 OR MORE |
24 |
|
MEASURING THE CONDITION OF THE BATTERY. |
|
YES |
YES |
|
BATTERY LIFE IN FAILURE OF LACK OF VOLTAGE. |
|
48 HOURS |
48 |
|
INCLUDED IN THE CABINET OF CONTROL |
|
YES |
YES |
5.02 |
SYSTEM OF CHARGE OF THE BATTERIES |
|
|
|
|
COUNTRY |
|
TO INDICATE |
CHINA |
|
MANUFACTURER |
|
TO INDICATE |
BEJINAG |
|
AUXILIAR VOLTAGE |
|
220 VAC |
YES |
|
SYSTEM |
|
SINGLE PHASE |
YES |
|
COMPATIBLE WITH SPECIFIED BATTERIES |
|
YES |
YES |
|
INCLUDED IN THE CABINET OF CONTROL |
|
YES |
YES |
|
|
|
|
|
|
|
|
|
|