Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Double-column Disconnector |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | TYPE Rated parameter |
GW5-40.5 | GW5-72.5 | GW5-126 | ||||||||||||||||||||
1 | Rated voltage kV | 40.5 | 72.5 | 126 | ||||||||||||||||||||
2 | Rated current A | 630 | 1250 | 1600 | 2000 | 630 | 1250 | 1600 | 2000 | 630 | 1250 | 1600 | 2000 | |||||||||||
3 | Disconnect witchg | Peak withstand current (kA) |
50 | 80 | 100 | 100 | 50 | 80 | 100 | 100 | 50 | 80 | 100 | 100 | ||||||||||
Short-time withstand current (effective value) (kA) | 20 | 31.5 | 40 | 40 | 20 | 31.5 | 40 | 40 | 20 | 31.5 | 40 | 40 | ||||||||||||
Short-circuit keeping time (S) | 4 | |||||||||||||||||||||||
4 | type earth knife | Peak withstand current (kA) |
25 | |||||||||||||||||||||
Short-time withstand current (kA) | 10 | |||||||||||||||||||||||
Short-circuit keeping time (s) | 4 | |||||||||||||||||||||||
5 | type earth knife | Peak withstand current (kA) |
100 | |||||||||||||||||||||
Short-time withstand current kA | 40 | |||||||||||||||||||||||
Short-circuit keeping time (s) |
2 | |||||||||||||||||||||||
6 | Short time power frequency withstand voltage (effective value) (kV) | To earth | 110 | 185 | 260 | |||||||||||||||||||
Break to break |
125 | 200 | 300 | |||||||||||||||||||||
7 | Lightning impulse withstand voltage(effective value) (kV) | To earth | 185 | 350 | 550 | |||||||||||||||||||
Break to break |
215 | 385 | 630 | |||||||||||||||||||||
8 | Terminal static mechanical load (N) | horizontal longitudinal |
1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||||||||||||||||
horizontal cross |
750 | 750 | 750 | 750 | 750 | 750 | ||||||||||||||||||
Vertical force | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||||||||||||||||||
9 | bus-transfer current switching by disconnectors in gis (A) | 504 | 1000 | 1280 | 1600 | 504 | 1000 | 1280 | 1600 | 504 | 1000 | 1280 | 1600 | |||||||||||
10 | Radio jamming degree | Not more than 2000μV | ||||||||||||||||||||||
11 | Mechanical life | 3000 times | ||||||||||||||||||||||
No. | Type Rated parameter |
GW5-40.5 | GW5-72.5 | GW5-126 | ||||||||||||||
1 | Rated current | 630 | 1250 | 1600 | 2000 | 630 | 1250 | 1600 | 2000 | 630 | 1250 | 1600 | 2000 | |||||
2 | Break insulating distance at disconnect switch off (≥mm) | 400 | 650 | 1000 | ||||||||||||||
3 | Insulating distance of conductive part to earth (≥mm) | 400 | 650 | 900 | ||||||||||||||
4 | Resistance of main circuit (≤μΩ) | 200 | 150 | 115 | 90 | 220 | 155 | 120 | 100 | 245 | 170 | 135 | 110 | |||||
5 | Tryphase Switchin SYNCHRONISM of main knife≤mm) | 5 | 8 | 12 | ||||||||||||||
6 | Switchin time of distributing device | CJ6:3.75±1s | ||||||||||||||||
7 | Weight of single pole (kg) | 125 | 150 | 160 | 190 | 200 | 240 | |||||||||||
BOLTS OF STAINLESS STEEL | |
DIAMETER(mm) | FASTENING TORQUE(N·m) |
6 | 4.5 |
8 | 11 |
10 | 19 |
12 | 32 |
16 | 78 |
ZINC-PLATED BOLTS OF STEEL |
|
DIAMETER(mm) | FASTENING TORQUE(Nm) |
12 | 58 |
16 | 140 |
20 | 270 |
24 | 470 |