THE BIDDER INFORMATION | ||||||||
1. Name of offeror company | NINGBO HYUAN POWER INDUSTRY CO.,LTD | |||||||
2. Name Factory | NINGBO HYUAN POWER INDUSTRY CO.,LTD | |||||||
3. Country of Origin Factory | CHINA | |||||||
4. Name of contact person | TAILICHEN | |||||||
5. Contact phone | 008613805895904 | |||||||
6. Contact Email | [email protected] | |||||||
Technical data | Unity | Specification | offered | Observations | ||||
1) Technical data | ||||||||
1.1 | Brand | (*) | HEMG | |||||
1.2 | Model | (*) | CJ | |||||
1.3 | rated torque: 1000 | NM | Required | 1000 | ||||
1.4 | Operating frequency: 60 | Hz | Required | 60 | ||||
1.5 | Operating Voltage: 125 ± 10% | vdc | Required | 125VDC+/-10% | ||||
1.6 | Type of operation | |||||||
1.6.1 Electric | Required | ELECTRIC | ||||||
1.6.2 Manual crank | Required | MANUAL CRANK | ||||||
1.7 | keypads | |||||||
1.7.1 Opening: Green Color | Required | GREEN COLOR | ||||||
1.7.2 Close: Color Red | Required | RED COLOR | ||||||
1.8 | Wiring contact closing and opening available in borneras | Required | YES | |||||
1.9 | Position selector | |||||||
1.9.1 Local | Required | LOCAL | ||||||
1.9.2 Remote | Required | REMOTE | ||||||
1.9.3 Maintenance | Required | MAINTENANCE | ||||||
1.10 | Motor Voltage: 125 | Vdc / Vac | Required | 125VDC | ||||
1.10.1 Operating voltage range: | vdc | 80 to 150 | 80-150 | |||||
1.11 | Control coils 125 | vdc | Required | 125VDC | ||||
1.11.1 Operating voltage range: | vdc | 80 to 150 | 80-150 | |||||
1.12 | Limit (Limit Swich) Adjustable: | Degrees | 90 and 180 | 90/180 | ||||
1.13 | Direction of rotation for opening: Schedule | Required | ANTICLOCKWISE | |||||
1.14 | Breaker protection shot Auxiliary Contact | Required | YES | |||||
1.15 | Heating | Required | ||||||
1.16.1 Heating Voltage: 120 | Vac | Required | 120VAC | |||||
1.16.2 Adjustable Temperature: | ° C | ≥30;≤55 | ≥30;≤55 | |||||
1.17 | contacts | |||||||
1.17.1 normally open contact 10 | c / u | Required | 10 | |||||
1.17.2 Contact normally closed 10 | c / u | Required | 10 | |||||
1.18 | Block wiring contacts available on terminal blocks | Required | YEW | |||||
1.19 | Lamp for indoor lighting | |||||||
1.19.1 Lamp type: LED | Required | YES | ||||||
1.19.2 Lamp power | W | (*) | 10W | |||||
1.20 | The lower cap must be removable and smooth. | Required | YES | |||||
1.21 | Set in block control terminals, power and signaling | Required | YES | |||||
1.22 | Landing site | Required | ||||||
1.22.1 Landing Holes: 2 | c / u | Required | 2 | |||||
1.23 | DC Contactor: 2 | c / u | Required | 2 | ||||
1.23.1 force contacts NA: 4 | c / u | Required | 4 | |||||
1.23.2 auxiliary contacts NC: 2 | c / u | Required | 2 | |||||
1.23.3 auxiliary contacts: 2 | c / u | Required | 2 | |||||
1.24 | Lock system | |||||||
1.24.1 Lockout | Required | YES | ||||||
1.24.2 Mechanical lock | Required | YES | ||||||
1.25 | Degree of protection: IP55 | Required | IP55 | |||||
1.26 | Manufacturing material: aluminum or stainless steel | Required | ||||||
1.27 | Fixing brackets 4 5/8 holes in galvanized steel bar | Required | STAINLESS STEEL | |||||
1.28 | Disconnector opening time: | Sec. | ≤9 | <=9 | ||||
1.29 | Construction standards: IEC 62271-102, 62271-1 | Required | IEC62271-102,IEC62271-1 | |||||
1.30 | Or latchkey lock: Handle with possibility to type padlocked | Required | YES | |||||
1.31 | Control planes: | Required | YES | |||||
2) testing and factory testing | ||||||||
2.1 | IEC 62271-1, 60255-5 and 62271-102 a) Insulation Resistance Motor b) opening and closing speed c) Rotation d) electrical and mechanical lock e) Test torque | Required | YES | |||||