15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank

Product Details
Customization: Available
Type: Polypropylene Capacitor
Application: High Voltage
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
  • 15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
  • 15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
  • 15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
  • 15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
  • 15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
Find Similar Products

Basic Info.

Model NO.
TBB
Capacitance
50Mvar
Structure
Variable Capacitor
Manufacturing Material
Polypropylene
Electrolyte
Electrolytic
Usage
High Frequency Coupling
Tuning
Polystyrene Capacitor
Filter
Composite Paper Capacitor
Transport Package
Carton with Wooden
Specification
33KV/72.5KV/123KV/132KV/145KV
Trademark
HEMG
Origin
China
Production Capacity
50000PCS

Product Description

Capacitor bank 33kv-5MVAR
NO. Description Unit Specification QYY
Required Proposed
1 Capacitor bank 5MVA installed in container each bank consist of: bank      
1.1 HRC Fusse set      
  Rating current A 80 80  
  Voltage class KV 20/36 20/36  
  Rated braking current KA 40 40  
1.2 Inrush current limiting reactor Set      
  Rated voltage KV 36 36  
  Insulation level(BIL) KV 170 170  
  Inductance mH   50.5  
  Impedance Ω   15.8  
  Frequercy HZ 50 50  
  Rated current A   79  
  Rated short cct KA 2/1 Set 2/1 Set  
1.3 C.T BLANCED Pcs      
  Ratio   10/5 10/5  
  Burden AV 20 20  
  Class   SP20 SP20  
  Rated voltage KV 36 36  
  Short cct.rating KV 31.5 31.5  
1.4 Voltage Transformer Pcs      
  Rated voltage KV 33 33  
  Ratio KV 33/3/0.11/3 33/3/0.11/3  
  Burden VA 20VA 20VA  
 
 
 
 
 
 
 
NO. Description Unit Specification QYY
Required Proposed
1.5 Capacitor Cell PCS To be filled    
  Rated KVAR KVAR To be filled 334  
  Rated voltage KV To be filled 10.5  
  Rated frequency Hz 50 50  
  DIS CAHARE TIME Minut   5  
  Capacitance Μf   9.6*10-9  
  FUSING   internat Internal  
  Ambient temp
Absolute max
Absolute min
MAX.annual ave
 C°
 C°
 C°
+55°
-22°
+40°
+55°
-22°
+40°
 
1.6 SURGER ARRESTOR SET      
  Arrestor rating KV 39 39  
  IEC class   2 2  
  Housing   silicone silicone  
1.7 Isolator comlete with integral each switch set      
  Voltage rating KV 36 36  
  Insulatiom level (BIL) KV 170 170  
  Current Rating A 1250 1250  
1.8 Bus Bar Supported Insulator        
  Voltage Class KV 36 36  
  BIL KV 170 170  
2 Capacitor cells for spare parts       40 cells
  HRC Fuses for spare parts       20 Pcs
           
           
           
           
 
 
Capacitor bank 33kv-3.5MVAR
NO. Description Unit Specification QYY
Required Proposed
1 Capacitor bank 5MVA installed in container each bank consist of: bank      
1.1 HRC Fusse set      
  Rating current A 80 80  
  Voltage class KV 20/36 20/36  
  Rated braking current KA 40 40  
1.2 Inrush current limiting reactor Set      
  Rated voltage KV 36 36  
  Insulation level(BIL) KV 170 170  
  Inductance mH   212.26  
  Impedance Ω   66.65  
  Frequercy HZ 50 50  
  Rated current A   32.4  
  Rated short cct KA 2/1 Set 2/1 Set  
1.3 C.T BLANCED Pcs      
  Ratio   10/5 10/5  
  Burden AV 20 20  
  Class   SP20 SP20  
  Rated voltage KV 36 36  
  Short cct.rating KV 31.5    
1.4 Voltage Transformer Pcs      
  Rated voltage KV 33 33  
  Ratio KV 33/3/0.11/3 33/3/0.11/3  
  Burden VA 20VA 20VA  
 
 
 
 
 
 
 
NO. Description Unit Specification QYY
Required Proposed
1.5 Capacitor Cell PCS To be filled    
  Rated KVAR KVAR To be filled 389  
  Rated voltage KV To be filled 10.5  
  Rated frequency   50 50  
  DIS CAHARE TIME Minut   5  
  Capacitance Μf   11.2*10-9  
  FUSING   internat Internal  
  Ambient temp
Absolute max
Absolute min
MAX.annual ave
 C°
 C°
 C°
+55°
-22°
+40°
+55°
-22°
+40°
 
1.6 SURGER ARRESTOR SET      
  Arrestor rating KV 39 39  
  IEC class   2 2  
  Housing   silicone silicone  
1.7 Isolator comlete with integral each switch set      
  Voltage rating KV 36 36  
  Insulatiom level (BIL) KV 170 170  
  Current Rating A 1250 1250  
1.8 Bus Bar Supported Insulator        
  Voltage Class KV 36 36  
  BIL KV 170 170  
2 Capacitor cells for spare parts       6 cells
  HRC Fuses for spare parts       4 Pcs
           
           
           
 
 
 
Capacitor cells bank  30MVAR
NO. Description Unit Specification QYY
Required Proposed
1 Electrical specification for capacitor bank11KV 30Mvar set     2
1.1 Frequency HZ 50 50  
1.2 Highest voltage Kv 12 12  
1.3 Rated insulation level at power frequency KVr.m.s 28 28  
1.4 Peak with stand voltage
(1.2/50μs)
KV
Peak
75 75  
1.5 Bank installation   Out door Out door  
1.6 Capacitor bank power MVAR 30 30  
1.7 Ambient temp
Absolute max
Absolute min
MAX.annual ave
 C°
 C°
 C°
+55°
-22°
+40°
+55°
-22°
+40°
 
3 Unbalance C.T Pcs     6
3.1 Current ratio   10/5 10/5  
3.2 Burden VA 15 15  
4 Capacitor  cell   To be filled To be filled  
5 Suitable all necessary steal structure Pcs     2
6 Capacitor for spare parts       20 cells
 
 
 
1.Applicable in power system of AC three-phase industrial 50/60 Hz frequency and voltage class 6Kv, 10Kv and 35Kv, 66KV,132KV for improvement in power factor, enhancement in grid performance, and reduction in line loss occurred during transmission. The capacitor bank is characterized by compact, easy installation and safety operation.
2.Product characteristics:
 Consists of shunt capacitor, circuit breaker, reactor, surge arrester, discharge device, fuse, isolation contact knife switch and protection device, switching device and etc.
Internal and external fuse protection in case of element breakdown.
Back up protection: Open delta voltage protection, neutral unbalance current protection, differential voltage protection, bridge differential current unbalance protection for different wiring modes.
Protection for system abnormality: Over current protection, short circuit protection, over voltage protection, voltage-loss protection, over load protection, and single phase grounding protection.
3.Technical Parameters:
 Altitude  ≤2000 meters
 Capacitance tolerance  0%~+5%
 Rated output     900~60000 kvar
 Long term running under 1.1 times of Un
 Running under stable over current, highest value of which reaching 1.3 times of In caused by over voltage and high harmonic.
 Capacitance tolerance: ratio of actual capacitance and normal capacitance in each phase shall not exceed 0~+5%, the ratio of max and minimum capacitance in three phase shall not exceed 1.02.
4.Customized design:
We can provide design and manufacture according to customer requirements or samples and based on sufficient communica-tion with customer to satisfy the actual utilize requirements utmost when customer has a special technological requirement, for example the special requirement to D-Link capacitor and filter capacitor of EV, HEV, PHEV, Fuel cell power inverter, such as Current, Voltage, Power factor, external installation measure-ments, wiring terminal etc.
15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank
15kv/27kv/38kv/72.5kv/132kv 50Hz/60Hz Uo to 50Mvar Three Phase Substation Mounted Capacitor Bank

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier