ITEM | DESCRIPTION | UNIT | PETE Require-ments | Bidder Specification | |
1 | Manufacturer reputation / skills / quality check | HEMG/CHINA | |||
2 | ISO 9001 certificate | Yes | |||
3 | Type of circuit breaker | Vacuum type | vacuum | ||
4 | Type designation | VS1X1-24 | |||
5 | Rated frequency | Hz | 50 | 50 | |
6 | Rated voltages: | ||||
a) Highest system voltage | KV | 24 | 24 | ||
b) Minimum service voltage | KV | 20 | 20 | ||
7 | Rated normal current at 50oc ambient temperature | ||||
a) For outgoing bay | A | NA | 1250 | ||
b) For incoming bay | A | >1250 | 1250 | ||
8 | Rated breaking current capacity | ||||
a) Symmetrical KA ( rms ) | KA ( rms ) | >25 | 25 | ||
b) D.C.component % | % | 20 | |||
9 | Rated peak:making current | KA (peak) | > 62.5 | 63 | |
10 | Rated peak short-circuit curren | KA (peak) | 63 | ||
11 | Rated short time current | ||||
a)1 sec | KA ( rms ) | >25 | |||
b)3 sec | KA ( rms ) | 25kA/4s | |||
12 | Rated line charging breaking current | A | 10 | ||
13 | Rated cable charging breaking current | A | 50 | ||
14 | Rated small inductive breaking current | A | 1250 | ||
15 | Rated breaking current under out of phase conditions | KA | 25 | ||
16 | Restricting voltage: | ||||
a) Rate of rise ( RRRV ) |
KV /microsecond |
0.47 | |||
b) Peak | KV(peak ) | 41 | |||
17 | First pole to clear factor |
1.5 | |||
ITEM | DESCRIPTION | UNIT | PETE Requirem-ents |
Bidder Specification | |
18 | One minute power frequency withstand voltage | ||||
a) Phase to earth | KV ( rms ) | ≥ 50 | 50 | ||
b) Across open contacts | KV ( rms ) | ≥ 50 | 50 | ||
19 | Lightning impulse withstand voltage 1,2/50 microsecond | KV(peak ) | ≥ 125 | 125 | |
20 | Rated operating sequence | O-0.3s-CO-180s-CO | |||
21 | Capacity to make | ||||
High speed three phase auto recluse | 63KA | ||||
22 | Minimum time between each successive break/make operation | Sec. | Acc. to IEC | Yes,≥0.3 | |
23 | Opening time( until separation of the arcing contacts ) | ||||
a) Without current | ms | 25 | |||
b) With 100% rated breaking current |
ms | 30 | |||
24 | Maximum total break time ( until total are extinction ) | ms | 35 | ||
25 | Maximum time interval between opening of the first and the last phase | ms | less than 1 | ||
26 | Maximum time interval between opening of the interrupters of one phase ( if any ) |
ms | ≤60 | ||
27 | make time: | ||||
a) Without current | ms | 50 | |||
a) With 100% rated Making current |
ms | 56.5 | |||
28 | Maximum total make time ( closing initiation to latching of circuit breaker in fully closed position ) | ms | 58 | ||
29 | Maximum time between closing of first and last phase | ms | less than 1 | ||
30 | Maximum time interval between closing of interrupters of one phase | ms | 60 | ||
31 | Dead time | ms | ≤ 300 | 300 | |
32 | Maximum peak value of switching over voltage when interrupting rated line charging current | KV (peak) | 19.4 | ||
33 | Radio influence voltage(RIV) measured at rated voltage to earth 2000UV | Micro V | 2000uV |
||
34 | Devices used to limit transient recovery voltages1.2UM | 1.2UM | |||
35 | Creepage distance: | ||||
a) To earth | mm | 400 | |||
b) Across terminals | mm | 600 | |||
36 | Operating mechanism: | ||||
a) Type | Spring | ||||
b) Operating voltage Rated / range . |
VDC % |
220,110 -20 +10 |
DC 220/110 -20% +10% | ||
c) Rated power | W | 100 | |||
37 | Closing release coil: | ||||
a) Rated operating voltage | VDC | 220 , 110 | DC 220/110 | ||
b) Minimum operating voltage |
% | -20 % | -20% | ||
c)Maximum operating Voltage |
% | +10 | +10% | ||
Rated power | W | 370 | |||
38 | Trip release coil: | ||||
a) Rated operating voltage | VDC | 220 , 110 | DC 220/110 | ||
b) Minimum operating voltage |
% | -30 % | -30 % | ||
c)Maximum operating Voltage |
% | +10 % | +10 % | ||
d) Rated power | W | 370 | |||
39 | Distance : | ||||
a) Between phases ( between the centers of the two phases "e8" in the attached drawing ) | mm | 275 | 130 | ||
b) Between alive part and earth |
mm | acc. to IEC 56 | 60 | ||
40 | Weight of circuit breaker: | ||||
a) Total | Kg | 150 | |||
b) Heaviest part to be lifted during maintenance or repair producer |
Kg | 100 | |||
41 | Type test certificate details: | ||||
a) Testing station/authority | XIHARI | ||||
b) Certificate number | 07920 | ||||
c) Applied standards | IEC | ||||
The technical specification doesn't mention the supply of C.B. cradle . | |||||
Item | Description | Unit | REQUIRMENTS |
OFFER VALUE |
20 kV | 20 kV | |||
1 | Manufacturer / country | |||
2 | ISO 9001 certificate | Yes/No |
Should be submitted |
Yes |
3 | Type designation | LDZC-24(Ring) | ||
4 | Highest system voltage | kV | 24 | |
5 | Insulation material | cast -resin | ||
6 | Rated insulation levels : | |||
6.1 | Lightning impulse withstand voltage - 1,2/50 micro-sec | kV (peak) | 125 | |
6.2 | One minute power frequency withstand voltage | kV (rms) | 50 | |
7 | Rated primary current : | |||
a) For outgoing feeder bay |
A A |
NA 1200-600 /5/5 1200-600 /1/1 |
1200-600 /5/5 1200-600 /1/1 |
|
b) For incoming feeders | A |
|||
8 | Rating of secondary windings : | |||
a) - Rated current | A | 5 | 5 | |
b) - Rated output/accuracy class : - core 1 (measuring) - core 2 (protection) - core 3 (protection) |
VA VA VA |
15VA 15VA 15VA |
||
9 | Overload capacity at 45 °C ambient temperature | % | > 120 | > 120 |
10 | Cree page distance | mm | 400 | |
11 | Flash-over distance | mm | 180 | |
12 | Dimensions: (width x height ) and inner and outer diameter |
mm | SEE SCHEDULE (2) | 120x210x130 |
For incoming feeder | mm |
120x210x130 | ||
13 | Total weight | Kg | 20 | |
14 | Applied standard specifications | GB1208 | ||
15 | Turns ratio - Core 1 - Core 2 |
1200-600/1A 1200-600/1A |
Item | Description | Unit | PETE REQUIRMENTS |
OFFER VALUE | |
1 | Manufacturer / country * | HEMG/CHINA | |||
2 | ISO 9001 certificate | Yes/No |
Should be submitted |
Yes | |
3 | Type |
GIS |
GIS | ||
4 | Rated voltage | kV | 20 | 24 | |
5 | SF6 gas pressure SF6 | bar | 1.4 | ||
6 | Standard specifications | IEC62271 | |||
7 | Material of cubicles | Steel | Steel | ||
8 | Thickness of sheet | mm | > 2* | ≥2 | |
9 | Dimensions of the cubicles : | ||||
a) - Width | mm | 600 | |||
b) - Depth | mm | 1700 | |||
c) - Height | mm | 2000 | |||
10 | Bus bars : |
|
|||
a) - Material | Copper | Copper | |||
b) - Cross-section per phase | Sq.mm | Not less than 1200 | ≥1200 | ||
c) - Minimum clearance between phases | mm | 130 | |||
d) - Minimum clearance to earth | mm | 60 | |||
e) - Space between bus-bars supports | mm | 170 | |||
f) basbar insulation | air /resin with silicon rubber Insulated bus bar | /resin with silicon rubber Insulated bus ba | |||
11 | Connectors |
|
|||
a) - Material | RESIN | ||||
b) - Cross-section per phase : - incoming feeder - Outgoing feeder |
sq.mm |
|
1962 | ||
- -Minimum clearance between phases |
mm | 100 | |||
d) - Clearance to earth | mm | 60 | |||
12 | Maximum allowable current density at site worst conditions (for maximum ambient temperature 50°C) | ||||
a) - For busbars | A/sq.mm | 1375 | |||
b) - For connectors | A/sq.mm | 1375 | |||
13 | Dynamic short-circuit current | kA | > 62.5* | 63 | |
14 | Thermal short-circuit current | kA | > 25* | 25 | |
15 |
Segregated compartments per cubicle ( 20 ) kV equipment |
Yes/No | Yes | ||
16 | The cubicle with well protection against fire risks and contact with live parts |
Yes/NO | YES | Yes | |
Item |
Description |
Unit | PETE REQUIRMENTS |
OFFER VALUE | |
17 | Enclosures : a) Phase egregated or three phase b) Material c) Overall diameter d) Wall thickness |
Yes/NO |
Yes | ||
18 | Type of pressure relief device | ||||
19 | Rated insulation levels at normal as pressure : |
||||
Power frequency ( 1 ) minute withstand voltage | kV | ≥ 50 | 50 | ||
Lighting impulse withstand voltage | kV | ≥ 125 | 125 | ||
20 | Insulating gas pressure a) a) Maximum b) b) Normal c) c) Minimum |
1.6bar 1.4bar 1.2bar |
|||
21 | - Degree of protection - Internal high voltage equipment, gas enclosure - External enclosure |
IP IP |
≥ 64 ≥ 3x |
64 3X |
|
22 | B Does the cubicle have plug in or Bolted cable termination | Yes/NO |
Should be provided according to quantities in financial schedules | Yes | |
23 | Copy of the newest edition for relevant |
Yes / No | Yes | ||
24 | Type test certificate details a) - Testing station b) - Certificate numbers c) - Applied standard specifications |
XIHARI 07919 IEC298 |
|||
Item |
Description |
Unit |
PETE |
OFFERER VALUE |
20 kV | 20kV | |||
1 | Manufacturer name / country | HEMG/CHINA | ||
2 | ISO 9001 certificate | Yes/No |
Should be submitted |
Yes |
3 | Type of circuit breaker | Vacuum type | VACUUM | |
4 | Type designation | VS1X1-24 | ||
5 | Rated frequency | Hz | 50 | 50 |
6 | Rated voltages : | |||
a) - Highest system voltage | kV | 24 | 24 | |
b) - Minimum service voltage | kV | 20 | 20 | |
7 | Rated normal current at 40°C ambient temperature :40 | |||
Incoming feeder | A | 1250 | 1250 | |
Sectionalizer | A | 1250 | 1250 | |
Outgoing feeder | A | 630 | 630 | |
Incoming feeder for capacitor bank | A | NA | N/A | |
8 | Rated breaking current capacity | |||
a) - symmetric |
KA (rms) |
25 | 25 | |
b) - D.C. component | % | 20 | ||
9 | Rated peak making current | KA (peak) | >62.5 | 63 |
10 | Rated peak short-circuit current | KA (peak) | >62.5 | 63 |
11 | Rated short-time current | |||
a) - 1 sec. | KA (rms) | > 25 | 25kA/4s | |
b) - 3 sec. | KA (rms) | |||
12 | Rated line-charging breaking current | A | 10 | |
13 | Rated cable - charging breaking current | A | 50 | |
14 | Rated small inductive breaking current | A | 1250 | |
15 | Rated breaking current under out-of-phase conditions | KA | 25 | |
16 | Restricting voltage : | |||
a) - rate-of-rise (RRRV) | kV / micro sec | 0.47(T100) | ||
b) - peak | kV (peak) | 41(T100) | ||
17 | First-pole-to-clear factor | 1.5 | ||
18 | One minute power frequency withstand voltage : | |||
a) - Phase to earth | kV (rms) | > 50 | 50 | |
b) - Across open contacts | kV (rms) | 50 | ||
19 | Lightning impulse withstand voltage -1,2/50 micro sec | kV (peak) | > 125 | 125 |
20 | Rated operating sequence |
|
O-0.3S-CO-180S-CO |
|
21 | Capacity to make : | |||
a) High speed three phase auto extinguishing | 63KA | |||
22 | Minimum time between each successive break/make operation | sec. | > 0.3 | > 0.3 |
23 | Opening time (until separation of the arcing contacts) | |||
a) -Without current | ms | 25 | ||
b) -With 100%rated breaking current | ms | 30 | ||
24 | Maximum total break time (until total arc-extinction) | ms | 35 | |
25 | Maximum time interval between opening of the first and the last phase | ms | less than 1 | |
26 | Maximum time interval between opening of the interrupters of one phase (if any) |
ms | ≤60 | |
27 | Make time : | |||
a) - Without current | ms | 50 | ||
b) - With 100% rated making current | ms | 56.5 | ||
28 | Maximum total make time (closing initiation to latching of circuit breaker in fully closed position) | ms | 58 | |
29 | Maximum time between closing of first and last phase | ms | less than 1 | |
30 | Maximum time interval between closing of interrupters of one phase. | ms | ≤60 | |
31 | Dead time | ms | ≥300 | |
32 | Maximum peak value of switching over-voltage when interrupting rated line charging current | kV (peak) | 19.4 | |
33 | Radio influence voltage (RIV) measured at rated voltage to earth (RIV) |
micro V | 2000 | |
34 | Interrupting units in series per phase: | |||
a) - Number | 1 | |||
b) - Length of each break | mm | 13(VACUUM) | ||
35 | Devices used to limit transient recovery voltages | INTERRUPTER+SURAGE ARRESTER | ||
36 | Creepage distance : | |||
a) - To earth | mm | 150 | ||
b) - Across terminals |
mm | 150 | ||
37 | Operating mechanism : | |||
a) - Type | Spring | |||
b) - Operating voltage | DC 220/110 | |||
c) - Rated | VDC | 110/220* | DC 220/110 | |
d) - Range | % | ( -20% +10% ) | -20% +10% | |
e) - Rated power | W | 100(motor) | ||
f) - Operating pressure- normal/max/min. |
bar | 0.14/0.16/0.12 | ||
38 | Closing release coil | |||
a) - Rated operating voltage | VDC | 110 220* | 220 or 110 | |
b) - Minimum operating voltage | % | -20% | -20% | |
c) - Maximum operating voltage | % | + 10% | + 10% | |
d) - Rated power | W | 370 | ||
39 | Trip release coil | |||
a) - Rated operating voltage | VDC | 110 /220* | 220 or 110 | |
b) - Minimum operating voltage | % | -30% | -30% | |
c) - Maximum operating voltage | % | + 10% | + 10% | |
d) - Rated power | W | 370 | ||
40 | Clearances | |||
a) - Between phases | mm | 130 60 |
||
b) - Between alive part and earth | mm | |||
41 | Weight of circuit breaker | |||
a) - Total | Kg | 150 | ||
b) - Heaviest part to be lifted during maintenance or repair procedure |
Kg | 100 | ||
42 | Type test certificate details | |||
a) - Testing station/authority | XIHARI | |||
b) - Certificate numbe | 07920 | |||
c) - Applied standards | IEC 298,IEC 517,IEC 56 | |||
47 | Type of pressure monitoring device | DENSITY RELAY |
Item | Description | Unit | PETE REQUIRMENTS |
OFFER VALUE |
20 kV | 20 kV | |||
1 | Manufacturer / country | HEMH/china | ||
2 | ISO 9001 certificate | Yes/No |
Should be submitted |
Yes |
3 | Type designation | GBEA24RSS | ||
4 | Rated frequency | Hz | 50 | 50 |
5 | Highest system voltage | kV | 24 | 24 |
6 | Rated insulation level | |||
6.1 | Power frequency withstand voltage | kV | > 50 | 65 |
6.2 | Impulse 1,2/50 micro-sec withstand voltage | Kv (peak) | > 125 | 125 |
7 | Rated voltages : | |||
7.1 | Rated primary voltage | V | 20/ √3 | 20000 / √3 |
7.2 | Rated secondary voltage | V | 100/ √3 | 100/ √3 |
8 | Rated output/accuracy class Two coils |
> 50 / 0.5- 3P | 50/50 | |
9 | Voltage factor | 1.9Un | ||
10 | Rated ratio | 20 / √3/0.1/ √3/0.1/ 3kV | ||
11 | Ratio error with rated output and- 105% normal primary voltage105% - 5% normal primary voltage5% |
% | 0.5 3 |
|
12 | Ratio angle error with rated output and : - 105% normal primary voltage - 5% normal primary voltage |
Degree | 20 120 |
|
13 | Rated capacitance | pF | 0.5 | |
14 | Method of suppressing ferroresonance | CORE | ||
15 | Creepage distance | mm | 400 | |
16 | Flash-over distance | mm | 180 | |
17 | Main dimensions | mm | 148X295X602 | |
18 | Total weight | Kg | 50 | |
19 | Applied standard specifications | IEC60 |
Item | Description | Unit | PETE REQUIRMENTS |
OFFER VALUE |
20 kV | 20 kV | |||
1 | Manufacturer / country | HEMG/China | ||
2 | ISO 9001 certificate | Yes/No |
Should be submitted |
Yes |
3 | Type designation | LDZC-24(Ring) | ||
4 | Highest system voltage | kV | 24 | 24 |
5 | Insulation material | RESIN | ||
6 | Rated insulation levels : | |||
6.1 | Lightning impulse withstand voltage - 1,2/50 micro-sec | kV (peak) | ³ 125 | 125 |
6.2 | One minute power frequency withstand voltage | kV (rms) | ³ 50 | 50 |
7 | Rated primary current : | 50% 150-300/1/1 A 50% 200-400/1/1 A 5 A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles 100% 1200-600/1/1 |
50% 150-300/1/1 A 50% 200-400/1/1 A 5 A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles 100% 1200-600/1/1 |
|
a) For outgoing feeder bay |
A |
|||
b) For incoming feeder (30) MVA | A |
|||
d) For sectionalizer cubicles |
A | |||
8 | Rating of secondary windings : | |||
a) - Rated current | A | According to tender quantities for incoming feeder | 1250 | |
b) - Rated output/accuracy class : - core 1 (measuring) - core 2 (protection) - core 3 (protection) |
VA VA VA |
See single line diagram | 15VA 15VA 15VA |
|
9 | Overload capacity at 45 °C ambient temperature | % | > 120 | > 120 |
10 | Creepage distance | mm | 400 | |
11 | Flash-over distance | mm | 180 | |
12 | Dimensions | mm | 120x210x130 | |
13 | Total weight | Kg | 20 | |
14 | Applied standard specifications | IEC60 |
Item | Description | Unit | REQUIRMENTS |
OFFER VALUE |
20 kV | 20 kV | |||
1 | Manufacturer / country / | HEMG/China | ||
2 | ISO 9001 certificate | Yes/No |
Should be submitted |
Yes |
3 | Type designation | LDZC-24(Ring) | ||
4 | Highest system voltage | kV | 24 | |
5 | Insulation material | RESIN | ||
6 | Rated insulation levels : | |||
6.1 | Lightning impulse withstand voltage - 1,2/50 micro-sec- 1 / 50 | kV (peak) | 125 | |
6.2 | One minute power frequency withstand voltage | kV (rms) | 50 | |
7 | Rated primary current : | |||
a) For outgoing feeder bay a) |
A A |
50% 150-300/1/1 50% 200-400/1/1 |
50% 150-300/1/1 50% 200-400/1/1 5A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles 100% 1200-600/1/1 |
|
b) For incoming c) |
A |
5A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles |
||
d) Sectionalizer cubicles | 100% 1200-600/1/1 | |||
8 | Rating of secondary windings : | |||
a) - Rated current | A | According to tender quantities | 1250a | |
b) - Rated output/accuracy class : - core 1 (measuring) - core 2 (protection) - core 3 (protection) |
VA VA VA |
See single line diagram | 15va 15va 15va |
|
9 | Overload capacity at 45 °C ambient temperature45°C | % | > 120 | > 120 |
10 | Cree page distance | mm | 400 | |
11 | Flash-over distance | mm | 180 | |
12 | Dimensions: (width x height ):(×) and inner and outer diameter |
mm | SEE SCHEDULE NO ( 2 ) part two |
120x210x130 |
For outgoing feeder | mm | 120x210x130 | ||
For incoming feeder | mm | 120x210x130 | ||
13 | Total weight | Kg | 20 | |
14 | Applied standard specifications | |||
15 | Turns ratio - Core 1 - Core 2 - Core 3 |
1250A/5A 1250A/5A 1250A/5A |
Item | Description | Unit | REQUIRMENTS |
OFFER VALUE |
1 | Manufacturers / country/ | HEMG/China | ||
2 | Type and idetification | Plug in | Plug in | |
3 | Rated service voltage | 20kV | ||
4 | Principle insulation | Solid insulation | ||
5 | Material | Silicone rubber | ||
6 | Total external leakage distance | mm | 70 | |
7 | Method of connecting cable core sealing and terminal | /() | ||
8 | Material of fittings | Cleaning paper,silicone grease etc | ||
9 | Sealing ends dome | |||
10 | Base ring | |||
11 | Cross section for incoming feeder | mm2 | ≥ 3x2x300 CU | ≥ 3x2x300 CU |
12 | Cross section for outgoing | mm2 | 3 X1X 300 CU | 3 X1X 300 CU |
13 | Base plate | Flange | ||
14 | Dry withstand voltage ( 1min.power frequency routing test ) |
KV ( rms) |
65 | |
15 | Minimum wet withstand voltage 30 sec.power frequency type test on insulator only |
KV ( rms) |
50 | |
16 | Full wave withstand test impule voltage type test on complete terminal 1.50 micro sec1.50 | KV ( rms) |
125 | |
17 | Visible discharge test ( power frequency ) type test on insulator only() | KV | 26.5 |
Item | Description | Unit | PETE REQUIRMENTS |
OFFER VALUE | |||
1 | Manufacturer name /country | HEMG | |||||
2 | ISO 9001 certificate | Yes/No | Should be submitted | yes | |||
3 | Numerical type | Yes/No | yes | yes | |||
4 | Rated current For incoming cubicles() |
A |
5A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles |
5A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles |
|||
For other | A | 1A |
|||||
5 | Rated frequency | Hz | 50 | 50 | |||
6 | Setting range for pick up value | A | Adjustable | <=5% | |||
7-1 | Reset ratio: | % | >95% | >95% | |||
7-2 | Reset time: | ||||||
a-for inverse time element . | ms | 0-100000 | |||||
b-for definite time elements. | ms | 100-100000 | |||||
c- for high set instantaneous element | ms | 100-100000 | |||||
8 | Accuracy of current element (s) | % | ±5% | ||||
9 | Accuracy of time element (s) | % | ±2% | ||||
10 | Current reset ratio | % | |||||
11 | Drop - out time- | msec | |||||
12 | Consumption of measuring inputs | VA | 15 | ||||
13 | Overload rating : | ||||||
a) continuously | x In | 2 | |||||
b) for 1 sec. | x In | 40 | |||||
14 | Setting range of the current (ranges and steps) | ||||||
a-for inverse time O/C elements.O/C | x In | 0.1In~4In | |||||
b-For definite time overcurrent | x In | 0.2In~15In | |||||
c-For high set instantaneous O/C elements. | x In | 0.2In~15In | |||||
15 | Setting range of the time (ranges and steps)O/C relay at 5 IN .()/5. | |
|||||
a-for inverse time multiplier factor . | Sec | 0.05~10 | |||||
b-For definite time setting range.. | Sec | 0.05~10 | |||||
c- operating time of high set instantaneous | ms | 0-10s and 1ms | |||||
16 | Contacts number : | ||||||
- tripping | No. | 4 | |||||
- alarming at starting | No. | 1 | |||||
17 | Tripping contact rating : | ||||||
- making current | A | 8 | |||||
- continuous current | A | 5 | |||||
- breaking capacity | A | 15 | |||||
18 | Degree of protection | IP | > 50 | > 50 | |||
19 | Consumption on auxiliary supply | W | 28W Max | ||||
20 | Local signaling : | ||||||
- starting per phase | Yes/No | Yes | |||||
- tripping per phase | Yes/No | Yes | |||||
21 | Operational temperature range a) minimum temperature b) maximum temperature |
Co | -5 +50 |
-25ºC+55ºC | |||
22 | Test voltages : | ||||||
a) impulse withstand voltage 1.2/50 u sec1.2/50 U | kV peak | 5 | > 5 | ||||
b) power frequency withstand voltage | kV rms | 2 | > 2 | ||||
23 | Reference catalogue | No. | |||||
24 | How many stage dose this relay has for O/C (I>,I>>,I>>>) | 3 | |||||
25 | How many stage dose this relay has E/F (I E >,IE>>,IE>>>). | 3 | |||||
26 | Does the relay include an integral fault recorder | 80 | |||||
27 | Does the relay include a self- monitoring feature | Yes/No | Yes | ||||
28 | Does the relay include an integral event recorder.. | Yes/No | Yes | ||||
29 | Does the relay include facilities for communication with DCS equipment and what is the protocol .. | Yes/No | Yes | Yes | |||
30 | Does the relay have inverse characteristic for over current and earth fault : a) Standard inverse b) Very inverse c) Extremely inverse |
Yes/NoYes/No |
Yes Yes |
||||
31 | Does the relay have separate contact for self-monitoring function | Yes/No | Yes | ||||
32 | Does the relay have instantaneous function for EF and OC EFOC | Yes/No | Yes | ||||
33 | Supply voltage and tolerance | ±10V | |||||
34 | Type test certificate details : a) - Testing station b) - Certificate numbers c) - Applied standard specifications |
Yes | |||||
35 | the protection relay preferable to be plug-in type And self CT short circuiting when the relay withdrawble . |
YES/NO | YES | Yes | |||
36 | - hardware properties: - NO of optically isolated inputs - NO of output relays+ watchdog output relay - NO of fixed function LEDs and programmable LEDs - NO of setting groups - NO of front EIA(RS) 232 communication port (choice of protocol) - NO of Rear EIA (RS)485 communication port (choice of protocol |
optically isolated inputs; output relays+ watchdog output relay; fixed function LEDs and programmable LEDs; EIA(RS)232; IEA(RS)485; |
|||||
Item | Description | Unit | PETE
REQUIRMENTS |
OFFER VALUE | ||||||||||
1 | Manufacturer name / country | HEMG./China | ||||||||||||
2 | ISO 9001 certificate | Yes/No | Should be submitted | yes | ||||||||||
3 | Type reference | PD194E-9HY | ||||||||||||
4 | Rated value : | |||||||||||||
a) Frequency | Hz | 50 | 50 | |||||||||||
b) Voltage | V | 100/ √3 | AC100V,AC380V | |||||||||||
5 | Rated current For incoming cubicles |
A |
For incoming cubicles 5A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles For outgoing and ,coupling cubicles 1A for 100 % of cubicles |
For incoming cubicles 5A for 100 % of 220 vdc cubicles 1A for 75 % of 110 vdc cubicles 5A for 25 % of 110 vdc cubicles For outgoing and ,coupling cubicles 1A for 100 % of cubicles |
||||||||||
6 | Overload capacity ( continuous ) | % | 120% of rated value | |||||||||||
7 | Measuring accuracy | Yes/No | cl. 0.5 | U/I: 0.2; P,Q,PF:0.5 Harmonics:1; Active energy:0.5S; Reactive energy:1; |
||||||||||
8 | Temperature range | °C | ( -5, +50 ) | -10~70ºC | ||||||||||
9 | Test voltage : | |||||||||||||
10 | a) Impulse | kV | 5 | 5 | ||||||||||
11 | b) Power frequency ( 1 min. ) | kV | 2 | 2 | ||||||||||
12 | Power consumption : | |||||||||||||
13 | a) Voltage circuit | VA | <1VA(per phase) | |||||||||||
14 | b) Current circuit | VA | <0.4VA(per phase) | |||||||||||
15 | Dimensions | mm | Panel:96×96 | |||||||||||
16 | With remote communication facilities with SCADA level and switchgear level . | One RS-485,MODBUS-RTU protocol, communication speed:2400~9600bps | ||||||||||||
17 | Terminals | / | ||||||||||||
18 | Does the M.C have tarriff ( at least 3 tarriff ) . | Yes/No | Yes | yes | ||||||||||
19 | Does the M.C have output pulse . | Yes/No | Yes | yes | ||||||||||
20 | The measuring center should measure the following quantities (at least) : I) current , three phase II) voltage , three phase III) active power } ( import and export ) IV) reactive power} ( import and export ) V) active energy VI) reactive energy VII) power factor VIII) power quality ( up to 15 th harmonic voltage and current input IX) Max. demand X) Load profile |
Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No |
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes |
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes |
||||||||||
21 | Number of quantities which can be measured Reading values should be primary readings |
No. | > 10 | ≥10 | ||||||||||
22 | Accuracy for active energy measuring | Yes/No | 0.5 | 0.5 |