ITEM | FEATURES | UNITS | REQUESTED |
1 | Type of circuit breaker required | Dead tank - VACUUM | |
2 | Applicable standards | IEC62271-100 | |
3 | Installation Site | Outdoor, 1000 meters above sea level | |
4 | Circuit Breaker Characteristics | ||
4.1 | Number of poles | 3 | |
4.2 | Rated voltage | kV | 72.5 |
4.3 | Dielectric rigidity to atmospheric impulses at sea level | KVpk | 325 |
4.4 | Dielectric rigidity at industrial frequency at sea level | kV | 140 |
4.5 | Minimum leakage distance of the insulation | mm | 1842 |
4.6 | Nominal frecuency | Hz | 60 |
4.7 | Rated current | A | 1250 |
4.8 | Nominal line interruption current | A | 50 |
4.9 | Rated capacity of interruption of small inductive currents | A | 50 |
4.10 | Rated short circuit interruption capacity | kA | 40 |
a) Effective value of the alternating component | kArms | 40 | |
b) Effective value of the continuous component | % | 37 | |
c) "K" voltage factor | 1.21 | ||
4.11 | Opening factor of the first pole | 1.5 | |
4.12 | Rate for increasing the recovery voltage to 100% of the interruption capacity | kV/µs | 0.75 |
4.13 | Nominal short-circuit capacity | kA | 104 |
4.14 | Nominal sequence of operation | 0-0,3s-CO-15s-CO | |
4.15 | Nominal short circuit duration | s | 3 |
4.16 | Nominal interruption capacity in phase mismatch | kA | 2.5 |
4.17 | Maximum total interruption time | ms | 40 |
4.18 | Maximum dead time for high speed reclosing | ms | 300 |
4.19 | Adjustment range for reclosing | ms | 330 |
4.20 | Mechanism of operation (closing and firing) | motor - spring | |
4.21 | Mechanical endurance class | M2 | |
4.22 | Control voltage / motor voltage | 125 | |
4.23 | Insulators material | Porcelain | |
4.24 | Connector suitable for copper cable per pole: | AWG | 4/0 - 500 MCM |
5 | Bushing type current transformers | ||
5.1 | Number of transformers in each bushing | 2 | |
5.2 | Number of secondary windings in each transformer | 1 | |
5.3 | Maximum nominal nominal current | ||
b) For Transformer Circuit Breaker: Protection Measurement |
A | 1200 600 |
|
5.4 | Secondary nominal current | A | 5 |
5.5 | Nominal current of short duration 1s | % | 120 |
5.6 | kArms | 40 | |
5.7 | Dynamic current | kApk | 104 |
5.8 | Nominal capacity of output (burden) and accuracy class in: | ||
1) Secondary winding N1 precision / load (burden) | 20VA Cl. 5P20 | ||
2) Secondary winding N2 precision / load (burden) | 20VA Cl. 5P20 | ||
3) Secondary winding N3 precision / load (burden) | 20VA Cl. 5P20 | ||
4) Secondary winding N4 precision / load (burden) | 20VA Cl. 0,2 | ||
5.9 | Multiple relationship according to ANSI / IEEE C57.13: YES / NO | ||
b) For Transformer circuit breaker: (1200/1000/900/800/600/500/400/300/200/100/5 A) and (600/500/450/400/300/250/200/150/100 / 50/5 A) | YES | ||
6 | Local control panel | ||
6.1 | Degree of protection | IP55 | |
6.2 | Equipped with heating controlled by humidity detector (YES / NO) | YES | |
6.3 | Interior lighting (YES / NO), control by door switch | YES | |
6.4 | Opening and closing controls, electrical and mechanical | YES | |
6.5 | Terminals for signal acquisition for the SCADA system | YES | |
7 | Maximum dimensions | ||
a) Long | mm | 2300 | |
b) Wide | mm | 2125 | |
c) Height | mm | 3512 |
ITEM | FEATURES | UNITS | REQUESTED |
1 | Type of circuit breaker required | Dead tank - VACUUM | |
2 | Applicable standards | IEC62271-100 | |
3 | Installation Site | Outdoor, 1000 meters above sea level | |
4 | Circuit Breaker Characteristics | ||
4.1 | Number of poles | 3 | |
4.2 | Rated voltage | kV | 72.5 |
4.3 | Dielectric rigidity to atmospheric impulses at sea level | KVpk | 325 |
4.4 | Dielectric rigidity at industrial frequency at sea level | kV | 140 |
4.5 | Minimum leakage distance of the insulation | mm | 1842 |
4.6 | Nominal frecuency | Hz | 60 |
4.7 | Rated current | A | 1250 |
4.8 | Nominal line interruption current | A | 50 |
4.9 | Rated capacity of interruption of small inductive currents | A | 50 |
4.10 | Rated short circuit interruption capacity | kA | 40 |
a) Effective value of the alternating component | kArms | 40 | |
b) Effective value of the continuous component | % | 37 | |
c) "K" voltage factor | 1.21 | ||
4.11 | Opening factor of the first pole | 1.5 | |
4.12 | Rate for increasing the recovery voltage to 100% of the interruption capacity | kV/µs | 0.75 |
4.13 | Nominal short-circuit capacity | kA | 104 |
4.14 | Nominal sequence of operation | 0-0,3s-CO-15s-CO | |
4.15 | Nominal short circuit duration | s | 3 |
4.16 | Nominal interruption capacity in phase mismatch | kA | 2.5 |
4.17 | Maximum total interruption time | ms | 40 |
4.18 | Maximum dead time for high speed reclosing | ms | 300 |
4.19 | Adjustment range for reclosing | ms | 330 |
4.20 | Mechanism of operation (closing and firing) | motor - spring | |
4.21 | Mechanical endurance class | M2 | |
4.22 | Control voltage / motor voltage | 125 | |
4.23 | Insulators material | Porcelain | |
4.24 | Connector suitable for copper cable per pole: | AWG | 4/0 - 500 MCM |
5 | Bushing type current transformers | ||
5.1 | Number of transformers in each bushing | 2 | |
5.2 | Number of secondary windings in each transformer | 1 | |
5.3 | Maximum nominal nominal current | ||
b) For Transformer Circuit Breaker: Protection Measurement |
A | 1200 600 |
|
5.4 | Secondary nominal current | A | 5 |
5.5 | Nominal current of short duration 1s | % | 120 |
5.6 | kArms | 40 | |
5.7 | Dynamic current | kApk | 104 |
5.8 | Nominal capacity of output (burden) and accuracy class in: | ||
1) Secondary winding N1 precision / load (burden) | 20VA Cl. 5P20 | ||
2) Secondary winding N2 precision / load (burden) | 20VA Cl. 5P20 | ||
3) Secondary winding N3 precision / load (burden) | 20VA Cl. 5P20 | ||
4) Secondary winding N4 precision / load (burden) | 20VA Cl. 0,2 | ||
5.9 | Multiple relationship according to ANSI / IEEE C57.13: YES / NO | ||
b) For Transformer circuit breaker: (1200/1000/900/800/600/500/400/300/200/100/5 A) and (600/500/450/400/300/250/200/150/100 / 50/5 A) | YES | ||
6 | Local control panel | ||
6.1 | Degree of protection | IP55 | |
6.2 | Equipped with heating controlled by humidity detector (YES / NO) | YES | |
6.3 | Interior lighting (YES / NO), control by door switch | YES | |
6.4 | Opening and closing controls, electrical and mechanical | YES | |
6.5 | Terminals for signal acquisition for the SCADA system | YES | |
7 | Maximum dimensions | ||
a) Long | mm | 2300 | |
b) Wide | mm | 2125 | |
c) Height | mm | 3512 |