SCHEDULE F |
|
|
No. |
Description |
|
Particulars |
OFFER |
|
|
|
|
|
400KV CIRCUIT BREAKER |
|
|
|
|
1 |
Normal current rating |
A |
2500 |
2500 |
2 |
Fault rating |
kA |
100 |
100 |
2.1 |
Making current |
kAp |
40 |
40 |
2.2 |
Breaking current under out of phase conditions |
kA |
10 |
10 |
2.3 |
Maximun overvoltage factor on any switching duty |
pu |
< 2.5 |
1.05 |
3 |
Operating sequence |
|
|
|
|
3.1 |
Normal |
|
0-10s-CO-3min-CO |
O-10S-CO-3MIN-CO |
3.2 |
Auto reclosing single phase |
|
0-0.3s-CO-3min-CO |
O-0.3S-CO-3MIN-CO |
3.3 |
Delayed three phase auto reclose cycle adjustable dead time range |
ms |
2-30 |
2-30MS |
3.4 |
High speed single phase auto reclose cycle adjustable dead time range |
s |
0.3-2.0 |
0.3-2.0 |
3.5 |
Number of closing operations under out of synchronous conditions |
pu |
2 |
2 |
4 |
Transient recovery voltage |
|
- |
|
4.1 |
First phase to clear factor |
pu |
1.3 |
1.3 |
4.2 |
Surge impedance for short line fault test |
ohms |
450 |
450 |
4.3 |
Minimum voltage to earth when switching capacitive currents,( 1.2 times rated phase to earth voltage ) |
kV |
291 |
291 |
4.4 |
Voltage across circuit breaker under out of phase |
|
|
|
|
|
switching conditions |
pu |
2 |
2 |
5 |
Electro mechanical performance |
|
|
|
|
5.1 |
Maximum total break time throughout complete rating , |
|
|
|
|
|
ie trip coil initiation to final arc extinction (applicable) only to 100% rating for oil break circuit breakers ) |
ms |
50 |
50 |
5.2 |
Maximum time interval between closure of first and last phase of three phase circuit breakers |
ms |
3 |
3 |
5.3 |
Maximum time interval between closure of interrupters of one phase of the circuit breaker |
ms |
2 |
3 |
5.4 |
Maximum time interval between opening of first and last phase of three phase circuit breaker |
ms |
3 |
3 |
5.5 |
Maximum time interval between opening of interrupters |
ms |
2 |
2 |
6 |
Insulation level ( IEC 694 ) |
|
|
|
|
6.1* |
Lightning impulse withstand ( 1.2/50 wave ) positive |
|
|
|
|
|
and negative |
|
|
|
|
|
a. To earth , closed contacts |
-kVp |
1425 |
1425 |
|
b. Across , open contacts |
-kVp |
1665 |
1665 |
6.2* |
Switching impulse withstand ( 250/2500 wave )- positive and negative Dry / wet |
|
|
|
|
|
a. To earth , closed contacts |
-kVp |
1050 |
1050 |
|
b. Across , open contacts |
-kVp |
1245 |
1245 |
6.3* |
Power frequency withstand Dry / wet |
|
|
|
|
|
a. To earth , closed contacts - 1 minute |
kV |
520 |
520 |
|
b. Across , open contacts - 1 minute |
kV |
610 |
610 |
7 |
Ancillary equipment |
|
|
|
|
7.1 |
Number of trip coils required |
|
2/pole |
2/POLE |
7.2 |
Number of closing coils required |
|
1/pole |
1/POLE |
7.3 |
Degree of protection |
|
IP 55 |
IP55 |
|
|
|
|
|
|
· For SF6 circuit breakers , insulation levels at minimum SF6 gas working pressure , at15 C. |
|
|
|
|
YES |
* Based tests ( Impulse + ACp ) , required on switchgear for 300kV and above . |
|
|
|
|
YES |
+ Wet tests are required on outdoor open-terminal switchgear . |
|
|
|
|
YES |