• Line Fault Automatic Isolating Switch
  • Line Fault Automatic Isolating Switch
  • Line Fault Automatic Isolating Switch
  • Line Fault Automatic Isolating Switch
  • Line Fault Automatic Isolating Switch

Line Fault Automatic Isolating Switch

Type: High-voltage
Installation: Outdoor High-voltage
Operation: Electric
Grounding Mode: Grounding
Movement Mode: Oscillating Type
Number of Poles: Three Pole
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
FDZ
Grounding
Single Ground
Certification
ISO
Transport Package
Wooden
Specification
27KV 630A
Trademark
HEMG
Origin
China
Production Capacity
50000

Product Description


Line Fault Automatic Isolating Switch
Line Fault Automatic Isolating Switch
Line Fault Automatic Isolating Switch
Line Fault Automatic Isolating Switch
Line Fault Automatic Isolating Switch
Line Fault Automatic Isolating Switch
 
TECHNICAL SPECIFICATIONS
SWITCH SOLID POLYMER INSULATION THREEPHASE, 27 KV, BIL: 150 KV, 400 A, SF6, WITH ELECTRICAL CONTROL
Item Feature / description / parameter Specification requested Specification Offered
1 Quantity 3 3
2 Mark Indicate  HEMG
3 Model Indicate  FLW-27
4 Year of manufacture Not less 2015 2016
5 Origin Indicate  CHINA
6 Manufacturing Standards IEC60129 IEC62271-103 IEC62271-1 ANSI/IEEEC IEC-265-137.71 IEC
7 Certifications  Certificates of conformity of product or of compliance with standards required, in Spanish and/or English IN ENGLISH 
8 Operating Voltage Greater than or equal to 27kV 27KV
9 Operating Current Greater than or equal to 400A 400A
10 Frequency of Operation 60Hz 60HZ
11 Means of insulation Solid Polymer SOLID POLYMER
12 Means of interruption SF6  SF6
13 BIL 150kV for a voltage level of 27kV to 2800masl YES
14 Suitable to operate (opening and closing) with load current If YES
15 Close current asymmetric crest 31.0 kA RMS 31KA
16 Close current, effective asymmetrical 20.0 kA RMS 20KA
17 Operations Counter If YES
18 VISUAL INDICATOR OF CONTACT If YES
19 Short-circuit current 1 Must withstand a minimum 12.5kA for at least 3s 12.5KA
20 Protection IP 65 or higher PI65 FOR TANK
21 Number of Open/Close Operations Greater than or equal to 10 000 10000
22 Type of Installation With all the necessary accessories for mounting in concrete post POLE MOUNTED
23 Use Weather OUTDOOR
24 Operating Temperature -40 to 65°C (-40ºC TO 65ºC)
25 Type of Operation Manual and remote, through SCADA system YES
26 Engine Power to 48V 48VDC
27 CONTROL CABINET Stainless steel housing. With all the necessary accessories for mounting in concrete post. Protection to IP55 or higher. YES
Long battery life, with the backing of at least 48hs, and power to 48V. Battery status indicator. YES
Power 110…250V AC/DC. 125VDC/AC
Relay designed for remote control and monitoring, protection, failure indication, Power quality analysis and automation, fulfilling the protocols requested in item 24. You must have at least 6 voltage sensors (immersed in the tank) to measure voltage and Fase-Tierra Fase-Fase both in the load side as on the source; 3 current transformers with ability to measure currents of phase and waste. Language of visual inspection: Spanish and/or English. YES,IN ENGLISH
28 Weight Greater than or equal to 136kg 150KG
29 Counter of useful life. You must indicate the total number of open/close operations and wear of the contacts YES
30 Native COMMUNICATION INTERFACE Module or port to 10/100Mbps Ethernet TCP/IP RJ-45 Connector native to the computer (without converters assets or liabilities or similar) RJ45
31 Communication protocol for telecontrol and/or automation on the native communications interface DNP3i (TCP/IP), and optionally IEC 60870-5-104 DNP3.0
32 Integration Services to the SCADA system available to the EEQ If N/A
33 Training 2 days for installation, operation and maintenance for 20 people, and 3 days in processes of configuration and integration of SCADA protocols for 10 people N/A
34 Technical Warranty 4 Years YES
35 Catalog Attach catalog in Spanish and/or English IN ENGLISH 
36 Delivery Time 90 days from the date of signature of the contract YES
37 Test protocol type (Suppliers) The bidders appended to its offer by (the) test protocols type of material offered.  YES

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now