138kv Gis Compact Substation Gas Insulating Switchgear

Function: Circuit-Breaker Failure Protection
Certification: ISO9001-2000
Samples:
US$ 100000/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
ZF1
Production Capacity
1000

Product Description

138kv Gis Compact Substation Gas Insulating Switchgear
e. GENERAL CONDITIONS OF SERVICE FOR 138 kV-  
e.1 Type of Installation Exterior Exterior
e.2 Nominal Voltage 138 kV. 138 kV.
e.3 Number of phases 3 3
e.4 Reference schematic diagram See Annex 3 and present the bid See Annex 3 and present the bid
e.5 Nominal frequency 60 Hz 60 Hz
e.6 Voltages of control and heating equipment 125VDC - 220VAC 125VDC - 220VAC
e.7 Mounting altitude 3000 m.s.n.m 3000 m.s.n.m
  Room temperature
e.8 Maximum 40 °C 40 °C
Minimum 0 °C 0 °C
e.9 Solar radiation ≤1000 W/m2 ≤1000 W/m2
e.10 Seismic Degree 0,5 g 0,5 g
e.11 Degree of protection IP 65 IP 65
       
  GENERAL CONDITIONS OF SERVICE FOR 46 kV.
e.12 Type of Installation Exterior Exterior
e.13 Nominal Voltage 46 kV. 46 kV.
e.14 Number of phases 3 3
e.15 Reference schematic diagram See Annex 3 and present the bid See Annex 3 and present the bid
e.16 Nominal frequency 60 Hz 60 Hz
e.17 Voltages of control and heating equipment 125VDC - 220VAC 125VDC - 220VAC
e.18 Mounting altitude 3000 m.s.n.m 3000 m.s.n.m
e.19 Room temperature    
Maximum 40 °C 40 °C
Minimum 0 °C 0 °C
e.20 Solar radiation ≤1000 W/m2 ≤1000 W/m2
e.21 Seismic Degree 0,5 g 0,5 g
e.22 Degree of protection IP 65 IP65
       
       
 
 F. EQUIPMENT SPECIFICATIONS
f.1 Construction features Common compartment Common compartment
f.2 Type of compartment For three phases For three phases
f.3 Material Aluminium alloy Aluminium alloy
f.4 Minimal thickness 8mm 8mm
f.6 Sealing device
Material EPDM (Ethylene Propylene Diene type M ASTM) EPDM (Ethylene Propylene Diene type M ASTM)
f.7 Type Ring type O Ring type O
f.8 Fixed auxiliary circuits Cuba aluminum alloy: 5
Welded aluminum tank: 3
Cuba aluminum alloy: 5
Welded aluminum tank: 3
f.9 Auxiliary circuits Moving parts Cuba aluminum alloy: 5
Welded aluminum tank: 3
Cuba aluminum alloy: 5
Welded aluminum tank: 3
   

 
 

g         EQUIPMENT WEIGHTS
g.1 Three-phase Simple Bar Indicate 5500KG/BAY
g.2 Support box Indicate 500KG
g.3 Control Cubicle Indicate 500KG
g.4 SF6 Gas Weight Indicate 50KG
       
h. NOMINAL LEVELS OF INSULATION FOR 138 kV.  
h.1 Voltage supported with nominal power frequency
Common value 275 kV 275KV
Through the isolation distance 325 kV 325 kV
Through CB open 325 kV 325 kV
h.2 BIL
Internal value 650 kV 650 kV
Through the external insulation distance 750 kV 750 kV
Through open CB 750 kV 750 kV
       
  NOMINAL LEVELS OF INSULATION FOR 46 kV.
  Voltage supported with nominal power frequency
h.3 Common value 275 kV 275 kV
Through the isolation distance 325 kV 325 kV
Through CB open 325 kV 325 kV
  BIL    
h.4 Internal value 650 kV 650 kV
Through the external insulation distance 750 kV 750 kV
Through open CB 750 kV 750 kV

 
     
       
i. BUSHINGS COMPONENTS FOR 138kV.  
i.1 Nominal Voltage 138 kV 138 kV
i.2 Nominal Current 2000 A 2000 A
i.3 Voltage supported with nominal power frequency 325 kV 325 kV
i.4 Voltage supported by BIL 750 kV 750 kV
i.5 Partial discharge level, ≤ 5 pC 92 kV 92 kV
i.6 Voltage level of radio interference <2500 μV 92 kV 92 kV
i.7 Voltage supported by power frequency, 15 min at 100 kPa / 20 ° C 92 kV 92 kV
i.8 Material Silicone resin Silicone resin
       
  COMPONENTS OF BUSHINGS FOR 46 Kv.
i.9 Nominal Voltage 138 kV 138 kV
i.10 Nominal Current 2000 A 2000 A
i.11 Voltage supported with nominal power frequency 325 kV 325 kV
i.12 Voltage supported by BIL 750 kV 750 kV
i.13 Partial discharge level, ≤ 5 pC 92 kV 92 kV
i.14 Voltage level of radio interference <2500 μV 92 kV 92 kV
i.15 Voltage level of radio interference <2500 μV
Voltage supported by power frequency, 15 min at 100 kPa / 20 ° C
92 kV 92 kV
i.16 Material Silicone resin Silicone resin
       
       



j. Classification of Currents
 
j.1 Rated continuous current 2000 A 2000 A
j.2 Rated continuous current 40 kA 40 kA
j.3 Nominal current supported in short time ≥ 3 s ≥ 3 s
j.4 Nominal peak current supported 100 kA 100 kA


k. TRANSFORMER OF PROTECTION CURRENT
k.1 Quantity 2 at each end of each circuit breaker per position. 2 at each end of each circuit breaker per position.
k.2 Transformation relation 2000/5 A 2000/5 A
k.3 Precision Class 5P20 5P20
k.4 Nominal Power 25 VA 25 VA
k.5 Rated voltage 138 kV 138 kV


l. MEASURING CURRENT TRANSFORMER
l.1 Quantity 1 at each end of each circuit breaker per position. 1 at each end of each circuit breaker per position.
l.2 Transformation relation 2000/5 A 2000/5 A
l.3 Precision Class
 
0.3 ANSI / 0.2 IEC 0.3 ANSI / 0.2 IEC
l.4 Nominal Power 25 VA 25 VA
l.5 Rated voltage 138 Kv 138KV


m.         VOLTAGE TRANSFORMER FOR 138 KV.
m.1 Quantity 1 in each income of the transmission line 1 in each income of the transmission line
m.2 Primary / Secondary Voltage
 
138 / √3 (Primary) / 0.115 / √3 (Secondary- Protection) /
0.115 / √3 kV. (Secondary- Measurement)
138 / √3 (Primary) / 0.115 / √3 (Secondary- Protection) /
0.115 / √3 kV. (Secondary- Measurement)
m.3 Class 0.5 / 3P (Protection) and 0.3 (Measurement) 0.5 / 3P (Protection) and 0.3 (Measurement)
m.4 Security factor < 10 < 10
m.5 Nominal Power 25 VA 25 VA
m.6 Voltage factor 1.2/cont;      1.5/30s 1.2/cont;      1.5/30s
  Standard IEC 60044-5 IEC 60044-5
       
  TRANSFORMADOR DE VOLTAJE PARA 46 kV.
m.7 Quantity 1 in each income of the transmission line 1 in each income of the transmission line
m.8 Primary / Secondary Voltage 46 / √3 (Primary) / 0.115 / √3 (Secondary- Protection) /
0.115 / √3 kV. (Secondary- Measurement)
46 / √3 (Primary) / 0.115 / √3 (Secondary- Protection) /
0.115 / √3 kV. (Secondary- Measurement)
m.9 Class 0.5 / 3P (Protection) and 0.3 (Measurement) 0.5 / 3P (Protection) and 0.3 (Measurement)
m.10 Security factor < 10 < 10
m.11 Nominal Power 25 VA 25 VA
m.12 Voltage factor 1.2/cont;     1.5/30s 1.2/cont;     1.5/30s
  Standard IEC 60044-5 IEC 60044-5
       


n.


GAS SF6
 




 
n.1 Annual gas leak <0,5 % <0,5 %
       
o. SWITCH    
o.1 Frequency 60 Hz 60 Hz
o.2 Maker Indicate Indicate
o.3 Catalogue Indicate Indicate
o.4 Rated current 2000 A 2000 A
  Operation characteristics
o.5 Operation cycle CO - 0,3 s - CO - 180s - CO CO - 0,3 s - CO - 180s - CO
Opening time ≤60 msec ≤60 msec
Closing time ≤100 msec ≤100 msec
SF6 gas pressure Indicate 0.58MPA
Maximum allowable SF6 gas pressure Indicate 0.65MPA
Minimum permissible pressure of SF6 gas Indicate 0.5MPA
o.6 Characteristics short circuit
Nominal current of short circuit supported 40 kA 40 kA
Peak short circuit rated current 100 kA 100 kA
Short circuit duration ≥3 s ≥3 s
VRT peak for terminal faults 2.0 x 138 / √3 and 2.0 x 46 / √3 for 46kV 2.0 x 138 / √3 and 2.0 x 46 / √3 for 46kV
VRT lifting range 40/4 40/4
First polo factor 1.5 1.5
Current short circuit fault switch 100 kA 100 kA
Peak Current 100 kA 100 kA
o.7 Minimum number of operations at rated current 2000 2000
o.8 Minimum number of mechanical operations 10000 10000
  Maximum operating current
o.9 Load 50 A 50 A
Charging cable 160 A 160 A
o.10 Number of switches per phase 1 1
o.11 Type of operation mechanism Spring Spring
o.12 Type of interruption Fixed tripolar Fixed tripolar
o.13 Extinguishing medium of the arch SF6 SF6
o.14 Type of operation Mechanical connection Mechanical connection
o.15 Nominal potential of closing coil Indicate Indicate
  Number of auxiliary contacts
o.16 Normally open 20 20
Normally closed 20 20
Adjustable 20 20

 
     
p. ROD
p.1
Number of bars
1 1
p.2 Rated current 2000 A 2000 A
p.3 Short circuit current 40 kA 40 kA
p.4 Peak current 100 kA 100 kA
p.5 Short circuit duration ≥ 3 s 3S

q. SPECIFICATIONS CONSTRUCTION GIS
 
q.1 Compartment pressure range Indicate (MPa) 0.58 (MPa)
q.2 Maximum compartment temperature Indicate 40ºC
q.3 Maximum discharge time of SF6 gas from Cuba 0.5 hours 0.5 hours
q.4 Maximum vacuum pressure for gas handling -133 Pa -133 Pa
q.5 Weight of the transport unit Indicate 6000KG
q.6 Overall dimensions of the table Indicate 5.5X1.3X1.3M

r. SECTIONER FOR 138kV. And 46 kV.
 
r.1 Maker Indicate BK
r.2 Rated current 2000 A 2000 A
r.3 Short circuit current 40 kA 40 kA
r.4 Peak current 100 kA 100 kA
r.5 Short circuit duration ≥ 3 s ≥ 3 s
r.6 Operating capacity with load 1600 A 1600 A
r.7 Operating mechanism Motor, Manual Motor, Manual
r.8 Operation times
Opening time max / min ≤ 2000
 
≤ 2000
 
Closing time max / min ≤ 2000
 
≤ 2000
 
  Power coil closure
r.9 Voltage max / min DC125V DC125V
Currents max. 2.5A 2.5A
Power indicate indicate
  Feeding opening coil
r.10 Min voltage DC125V DC125V
Corrientes max 2.5A 2.5A
Power indicate 550
r.11 Auxiliary contacts
Normally open 8 8
Normally closed
                                
8 8
Adjustable 16 16
r.12 Disconnectors test report certificate Indicate YES
r.13    No. Mechanical operations 10000 10000


s. GROUND DISCONNECTOR FOR 138kV. And 46 kV.
s.1 Maker Indicate BK
s.2 Short circuit current 40 kA 40 kA
s.3 Peak current 100 kA 100 kA
s.4 Short circuit duration ≥ 3 s ≥ 3 s
s.5 Operating mechanism Motor, Manual Motor, Manual
s.6 Auxiliary contacts
Normally open 8 8
Normally closed 8 8
Adjustable 16 16
s.7 Disconnector test report certificate Indicate YES
s.8       No. Mechanical operations 10000 10000
       

t. GENERAL CHARACTERISTICS OF THE EQUIPMENT
 
t.1 Test Report Certificate. Present internationally recognized Laboratory Test Reports of all equipment YES
t.1 Lifetime certificate ≥ 15 years Present YES
t.2 Conditions of switches and disconnectors Hermetically sealed in pressurized gas YES
t.3 Closures and cuts Resistant to corrosion YES
t.4 Motorized mechanisms Auto lubricants YES
t.5 Filters Absorption of moisture and decomposition products YES
t.6 Nuts and bolts Resistant to corrosion YES
t.7 Circuit breaker module Of the Encapsulated type YES
t.8 Carcasses Of the compact and robust type YES
t.9 Arc interruption unit On the principle of self-compression YES
t.10 Environmental Protection Against pollution and environmental effects YES
t.11 Motorized equipment Manual and automatic operation YES
t.12 Maximum dimensions of the equipment 8m x 18m YES
t.13 Surface paint Indicate YES