DATA SHEET OF 3-Phase Charger Rectifier 220 Vac/ 48 Vdc, 750A/500A/250A | |||||
S/N | CHARACTERISTICS | UNIT | DATA FOR 750A | DATA FOR 500A | DATA FOR 250A |
1 | GENERAL CHARACTERISTICS | ||||
2 | Standards | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | |
3 | Principal characteristic | - | 3-Phase Charger Rectifier 220VAC/48 Vdc,750A | 3 PHASE CHARGER RECTIFIER,220VAC,48VDC,500A | 3 PHASE CHARGER RECTIFIER,220VAC,48VDC,250A |
4 | Type | - | FOR NI-CD BATTERY | FOR NI-CD BATTERIES | FOR NI-CD BATTERIES |
5 | Manufacturer | - | HEMG | HEMG | HEMG |
6 | Model | - | GZDH | GZDH | GDZH |
7 | Country | - | CHINA | CHINA | CHINA |
8 | Technology | - | Static rectifier controlled to Thyristors connected in parallel to the battery of accumulators of 48 Vcc | Static rectifier controlled to Thyristors connected in parallel to the battery of accumulators of 48 Vcc | Static rectifier controlled to Thyristors connected in parallel to the battery of accumulators of 48 Vcc |
9 | Digital, voltage, current | - | DIGITAL ,48VDC ,750A | DIGITAL,48VDC,500A | DIGITAL ,48VDC ,250A |
10 | INPUT VOLTATE | - | 3 PHASES ,220VAC | 3PHASE ,220VAC | 3PHASE ,220VAC |
11 | Altitude of operation | meters above sea level | 2800 | 2800 | 2800 |
12 | Humidity | % | 0% - 95% | 0%-95% | 0%-95% |
13 | Temperature | °C | Min 10 °C, Ave 26°C, Max 36 °C | MIN 10ºC,AVE 26ºC ,MAX 36ºC | MIN 10ºC,AVE 26ºC,MAX 36ºC |
14 | Manufacturing Standards | - | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 |
15 | ELECTRICAL FEATURES | ||||
16 | Phases | - | 3-phase | 3 PHASE | 3-PHASES |
17 | Input Voltage | Vac | 220VAC +/- 10% | 220VAC +/-10% | 220VAC +/-10% |
18 | Apparent net power consumption (power factor = 0.8) | VA | <=2880VA | <=1920VA | <=960VA |
19 | Maximum primary intensity | A | 1000A | 560A | 320A |
20 | Output voltage and range | Vdc | 48 Vdc +20%/-15% | 48VDC,(+20%/-15%) | 48VDC ,(+20%/-15%) |
21 | Frequency of input and operation | Hz | 60Hz +/- 10% | 60HZ(+/-10) | 60HZ(+/-10%) |
22 | Current regulation | % | <=2% | <=2% | <=2% |
23 | Efficiency (at nominal conditions) | - | ≥92% | ≥92% | ≥92% |
24 | |||||
25 | SOURCE OF RECTIFICATION TO "THYRISTOR" 100% (RECTIFIIER BRIDGE) | ||||
26 | Thyristor Rectifier | - | Thyristor Rectifier | Thyristor Rectifier | Thyristor Rectifier |
27 | Mixed | Recharge voltage dual loop control of recharging switching power supply technology, | Recharge voltage dual loop control of recharging switching power supply technology, | Recharge voltage dual loop control of recharging switching power supply technology, | |
28 | Maximum load current | Adc | 25 | 25A | 40A |
29 | Constant load voltage including the cooling element and the load regulating device | Vdc | 1000A | 560A | 320A |
30 | FILTER | ||||
31 | Ripple coefficient (% of load) crest - crest | % | <=1% | <=1% | <=1% |
32 | Form factor (% of load) | % | <= 1% | <=1% | <=1% |
33 | Floating maintenance voltage (Flotation voltage) | Vdc | 56VDC-58VDC | 56VDC-58VDC | 56VDC-58VDC |
34 | Equilibrium voltage | Vdc | 62VDC-64VDC | 62VDC-64VDC | 62VDC-64VDC |
35 | Manufacturer | - | HEMG | HEMG | HEMG |
36 | Catalogs, guide manual and brochures in Spanish | - | IN ENGLISH | IN ENGLISH | IN ENGLISH |
37 | ACCESORIES | ||||
38 | Thermomagnetic ignition switch | - | Yes | YES | YES |
39 | Thermomagnetic MCB switch with AC input | - | Yes | YES | YES |
40 | Main control board | - | Yes | YES | YES |
41 | Measuring instruments (voltmeter and ammeter) | - | Input voltage, battery voltage, consumer voltage, rectifier current, battery current | Input voltage, battery voltage, consumer voltage, rectifier current, battery current | Input voltage, battery voltage, consumer voltage, rectifier current, battery current |
42 | Event indicator card by optical indicators | - | Yes | YES | YES |
43 | Alarms and relay contacts | - | Low voltage AC fault (includes phase drop). High AC Voltage Fault. Positive or negative ground fault. Load Failure Short circuit failure Fault by low or high output voltage (over voltage). Deep discharge monitoring unit with automatic disconnection. High temperature disconnect unit. Rectification failure |
Low voltage AC fault (includes phase drop). High AC Voltage Fault. Positive or negative ground fault. Load Failure Short circuit failure Fault by low or high output voltage (over voltage). Deep discharge monitoring unit with automatic disconnection. High temperature disconnect unit. Rectification failure |
Low voltage AC fault (includes phase drop). High AC Voltage Fault. Positive or negative ground fault. Load Failure Short circuit failure Fault by low or high output voltage (over voltage). Deep discharge monitoring unit with automatic disconnection. High temperature disconnect unit. Rectification failure |
44 | Filters L.C. | - | Yes | YES | YES |
45 | Semi-controlled single-phase rectifier bridge | - | Yes | YES | YES |
46 | Main contactor | - | Yes | YES | YES |
47 | AC input transformer | - | Yes | YES | YES |
48 | Contactor including DC output fuses | - | Yes | YES | YES |
49 | DC output voltmeter | - | Yes | YES | YES |
50 | DC output ammeter | - | Yes | YES | YES |
51 | Output voltage control +/- 1% | - | Yes | YES | YES |
52 | Current limitation + 2% according to DIN 41 772 | - | Yes | YES | YES |
53 | Protection against Class G radio interference | - | Yes | YES | YES |
54 | Ripple 5% effective without batteries connected | - | Yes | YES | YES |
55 | DC output voltage monitoring unit "Very High / Very Low" | - | Yes | YES | YES |
56 | DC output voltage monitoring unit "deep discharge" with automatic disconnection | - | Yes | YES | YES |
57 | Main monitoring unit with signaling lamp and a free contact | - | Yes | YES | YES |
58 | Main monitoring unit with signaling lamp and a free contact | - | Yes | YES | YES |
59 | EMF counter cell, to limit voltage to user circuits 220 V ± 10% during charging and float, maximum 30 A to user circuits |
- | Yes | YES | YES |
60 | Tropicalized to operate in environments from 0 ° C to + 40 ° C | - | Yes | YES | YES |
61 | Metal cubicle with technical characteristics and identification | - | Yes | YES | YES |
62 | Cable entry via the floor | - | Yes | YES | YES |
63 | Terminals for measuring output voltage | - | Yes | YES | YES |
64 | Indicator Lamps | - | Yes | YES | YES |
65 | Indicating devices | - | Yes | YES | YES |
66 | Earth terminal | - | Yes | YES | YES |
67 | Connection terminal | - | Yes | YES | YES |
68 | Others needed | - | FUSE | FUSE | FUSE |
69 | OTHERS | ||||
70 | Cabinet Structure (type), Dimensions (mm) and color | - | 800X600X2260MM ,RAL7035 ,THICKNESS=2MM | 800X600X2260MM,RAL7035,THICKNESS=2.0 mm | 800X600X2260MM ,RAL7035,THICKNESS=2.0MM |
71 | Degree of protection | - | IP21 | IP21 | IP21 |
72 | Main equipment | - | 01 input thermomagnetic circuit breaker of 3x25 A, ABB 01 output thermomagnetic circuit breaker of 2x25A for charging, ABB 01 output thermomagnetic circuit breaker 2x25A for battery, ABB 02 32A fuse with signaling contact (one for battery and the other for charging) 01 filter with condenser 01 main microprocessor control board with LCD digital display and push buttons for navigation and programming |
01 input thermomagnetic circuit breaker of 3x25 A, ABB 01 output thermomagnetic circuit breaker of 2x25A for charging, ABB 01 output thermomagnetic circuit breaker 2x25A for battery, ABB 02 32A fuse with signaling contact (one for battery and the other for charging) 01 filter with condenser 01 main microprocessor control board with LCD digital display and push buttons for navigation and programming |
01 input thermomagnetic circuit breaker of 3x25 A, ABB 01 output thermomagnetic circuit breaker of 2x25A for charging, ABB 01 output thermomagnetic circuit breaker 2x25A for battery, ABB 02 32A fuse with signaling contact (one for battery and the other for charging) 01 filter with condenser 01 main microprocessor control board with LCD digital display and push buttons for navigation and programming |
73 | Protection | - | 3-phase circuit breaker of 10 kA under 380 Vac Maximum current opening devices for protection against overloads and against short circuits. Switches with auxiliary contacts for signaling of untimely opening |
3-phase circuit breaker of 10 kA under 380 Vac Maximum current opening devices for protection against overloads and against short circuits. Switches with auxiliary contacts for signaling of untimely opening |
3-phase circuit breaker of 10 kA under 380 Vac Maximum current opening devices for protection against overloads and against short circuits. Switches with auxiliary contacts for signaling of untimely opening |
74 | Bars | - | Nude in electrolytic copper (working at above temperature of 30 ° C) in 380-220 Vac and 110 Vcc and 48 Vcc. With transparent mica for protection against inspections or maintenance | Nude in electrolytic copper (working at above temperature of 30 ° C) in 380-220 Vac and 110 Vcc and 48 Vcc. With transparent mica for protection against inspections or maintenance | Nude in electrolytic copper (working at above temperature of 30 ° C) in 380-220 Vac and 110 Vcc and 48 Vcc. With transparent mica for protection against inspections or maintenance |
75 | Operation modes | Automatic (as a charger) and Manual (as a source). | Automatic (as a charger) and Manual (as a source). | Automatic (as a charger) and Manual (as a source). | |
76 | MTBF | 250,000 hours | 250,000 hours | 250,000 hours | |
77 | Automatic start | After an incident occurs in the input power (partial or total loss of power supply) | After an incident occurs in the input power (partial or total loss of power supply) | After an incident occurs in the input power (partial or total loss of power supply) | |
81 | Spare Parts | - | FUSE | FUSE | FUSE |
82 | Tests | - | The price includes the tests specified in the spec sheet. | The price includes the tests specified in the spec sheet. | The price includes the tests specified in the spec sheet. |
83 | Electrical danger sign decal type | - | Yes | YES | YES |
84 | WARRANTY | ||||
85 | Of the equipment | - | 2 years | 2YEARS | 2 YEARS |
86 | Of spare parts | - | 2 YEARS | 2YEARS | 2 YREARS |
87 | COMMERCIAL CONDITIONS | ||||
88 | Delivery time | days | 115DAYS CFR GUAYAQUIL SEAPORT | 115DAYS CFR GUAYAQUIL ECUADOR SEAPORT | 115DAYS CFR GUAYAQUIL SEAPORT |
89 | Payment terms | % | 30% TT IN ADVANCE ,70% BEFORE SHIPMENTS | 30% TT IN ADVANCE,70% BEFORE SHIPMENTS | 30% TT IN ADVANCE ,70% BEFORE SHIPMENT |
90 | Place of delivery | - | GUAYAQUIL .ECUADOR | GUAYAQUIL ,ECUADOR | GUAYAQUIL |
92 | Note: The rectifier must be implemented to work with the battery bank of nickel cadmium |
- | Yes | YES | YES |
93 | The equipment has a minimum of 2 dry contact relays, programmable by the operator for the remote indication to be defined. | - | Yes | YES | YES |
94 | THE COMMUNICATION SYSTEM FOR REMOTE ALARMS WILL BE BY MODBUS RTU | BY PORT RS232 BY MODUBUS PROTOCOOL | BY PORT RS232,BY MODBUS PROTOCOOL | BY PORT RS232 BY MODBUS PROTOCOOL | |
DATA SHEET OF 3-Phase Charger Rectifier 220 Vac/ 48 Vdc, 750A/500A/250A | |||||
S/N | CHARACTERISTICS | UNIT | DATA FOR 750A | DATA FOR 500A | DATA FOR 250A |
1 | GENERAL CHARACTERISTICS | ||||
2 | Standards | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | |
3 | Principal characteristic | - | 3-Phase Charger Rectifier 220VAC/48 Vdc,750A | 3 PHASE CHARGER RECTIFIER,220VAC,48VDC,500A | 3 PHASE CHARGER RECTIFIER,220VAC,48VDC,250A |
4 | Type | - | FOR NI-CD BATTERY | FOR NI-CD BATTERIES | FOR NI-CD BATTERIES |
5 | Manufacturer | - | HEMG | HEMG | HEMG |
6 | Model | - | GZDH | GZDH | GDZH |
7 | Country | - | CHINA | CHINA | CHINA |
8 | Technology | - | Static rectifier controlled to Thyristors connected in parallel to the battery of accumulators of 48 Vcc | Static rectifier controlled to Thyristors connected in parallel to the battery of accumulators of 48 Vcc | Static rectifier controlled to Thyristors connected in parallel to the battery of accumulators of 48 Vcc |
9 | Digital, voltage, current | - | DIGITAL ,48VDC ,750A | DIGITAL,48VDC,500A | DIGITAL ,48VDC ,250A |
10 | INPUT VOLTATE | - | 3 PHASES ,220VAC | 3PHASE ,220VAC | 3PHASE ,220VAC |
11 | Altitude of operation | meters above sea level | 2800 | 2800 | 2800 |
12 | Humidity | % | 0% - 95% | 0%-95% | 0%-95% |
13 | Temperature | °C | Min 10 °C, Ave 26°C, Max 36 °C | MIN 10ºC,AVE 26ºC ,MAX 36ºC | MIN 10ºC,AVE 26ºC,MAX 36ºC |
14 | Manufacturing Standards | - | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 | IEC 60146 - IEC 60439 - IEC 61000-6-2 - IEC 61000-6-4 |
15 | ELECTRICAL FEATURES | ||||
16 | Phases | - | 3-phase | 3 PHASE | 3-PHASES |
17 | Input Voltage | Vac | 220VAC +/- 10% | 220VAC +/-10% | 220VAC +/-10% |
18 | Apparent net power consumption (power factor = 0.8) | VA | <=2880VA | <=1920VA | <=960VA |
19 | Maximum primary intensity | A | 1000A | 560A | 320A |
20 | Output voltage and range | Vdc | 48 Vdc +20%/-15% | 48VDC,(+20%/-15%) | 48VDC ,(+20%/-15%) |
21 | Frequency of input and operation | Hz | 60Hz +/- 10% | 60HZ(+/-10) | 60HZ(+/-10%) |
22 | Current regulation | % | <=2% | <=2% | <=2% |
23 | Efficiency (at nominal conditions) | - | ≥92% | ≥92% | ≥92% |
24 | |||||
25 | SOURCE OF RECTIFICATION TO "THYRISTOR" 100% (RECTIFIIER BRIDGE) | ||||
26 | Thyristor Rectifier | - | Thyristor Rectifier | Thyristor Rectifier | Thyristor Rectifier |
27 | Mixed | Recharge voltage dual loop control of recharging switching power supply technology, | Recharge voltage dual loop control of recharging switching power supply technology, | Recharge voltage dual loop control of recharging switching power supply technology, | |
28 | Maximum load current | Adc | 25 | 25A | 40A |
29 | Constant load voltage including the cooling element and the load regulating device | Vdc | 1000A | 560A | 320A |
30 | FILTER | ||||
31 | Ripple coefficient (% of load) crest - crest | % | <=1% | <=1% | <=1% |
32 | Form factor (% of load) | % | <= 1% | <=1% | <=1% |
33 | Floating maintenance voltage (Flotation voltage) | Vdc | 56VDC-58VDC | 56VDC-58VDC | 56VDC-58VDC |
34 | Equilibrium voltage | Vdc | 62VDC-64VDC | 62VDC-64VDC | 62VDC-64VDC |
35 | Manufacturer | - | HEMG | HEMG | HEMG |
36 | Catalogs, guide manual and brochures in Spanish | - | IN ENGLISH | IN ENGLISH | IN ENGLISH |
37 | ACCESORIES | ||||
38 | Thermomagnetic ignition switch | - | Yes | YES | YES |
39 | Thermomagnetic MCB switch with AC input | - | Yes | YES | YES |
40 | Main control board | - | Yes | YES | YES |
41 | Measuring instruments (voltmeter and ammeter) | - | Input voltage, battery voltage, consumer voltage, rectifier current, battery current | Input voltage, battery voltage, consumer voltage, rectifier current, battery current | Input voltage, battery voltage, consumer voltage, rectifier current, battery current |
42 | Event indicator card by optical indicators | - | Yes | YES | YES |
43 | Alarms and relay contacts | - | Low voltage AC fault (includes phase drop). High AC Voltage Fault. Positive or negative ground fault. Load Failure Short circuit failure Fault by low or high output voltage (over voltage). Deep discharge monitoring unit with automatic disconnection. High temperature disconnect unit. Rectification failure |
Low voltage AC fault (includes phase drop). High AC Voltage Fault. Positive or negative ground fault. Load Failure Short circuit failure Fault by low or high output voltage (over voltage). Deep discharge monitoring unit with automatic disconnection. High temperature disconnect unit. Rectification failure |
Low voltage AC fault (includes phase drop). High AC Voltage Fault. Positive or negative ground fault. Load Failure Short circuit failure Fault by low or high output voltage (over voltage). Deep discharge monitoring unit with automatic disconnection. High temperature disconnect unit. Rectification failure |
44 | Filters L.C. | - | Yes | YES | YES |
45 | Semi-controlled single-phase rectifier bridge | - | Yes | YES | YES |
46 | Main contactor | - | Yes | YES | YES |
47 | AC input transformer | - | Yes | YES | YES |
48 | Contactor including DC output fuses | - | Yes | YES | YES |
49 | DC output voltmeter | - | Yes | YES | YES |
50 | DC output ammeter | - | Yes | YES | YES |
51 | Output voltage control +/- 1% | - | Yes | YES | YES |
52 | Current limitation + 2% according to DIN 41 772 | - | Yes | YES | YES |
53 | Protection against Class G radio interference | - | Yes | YES | YES |
54 | Ripple 5% effective without batteries connected | - | Yes | YES | YES |
55 | DC output voltage monitoring unit "Very High / Very Low" | - | Yes | YES | YES |
56 | DC output voltage monitoring unit "deep discharge" with automatic disconnection | - | Yes | YES | YES |
57 | Main monitoring unit with signaling lamp and a free contact | - | Yes | YES | YES |
58 | Main monitoring unit with signaling lamp and a free contact | - | Yes | YES | YES |
59 | EMF counter cell, to limit voltage to user circuits 220 V ± 10% during charging and float, maximum 30 A to user circuits |
- | Yes | YES | YES |
60 | Tropicalized to operate in environments from 0 ° C to + 40 ° C | - | Yes | YES | YES |
61 | Metal cubicle with technical characteristics and identification | - | Yes | YES | YES |
62 | Cable entry via the floor | - | Yes | YES | YES |
63 | Terminals for measuring output voltage | - | Yes | YES | YES |
64 | Indicator Lamps | - | Yes | YES | YES |
65 | Indicating devices | - | Yes | YES | YES |
66 | Earth terminal | - | Yes | YES | YES |
67 | Connection terminal | - | Yes | YES | YES |
68 | Others needed | - | FUSE | FUSE | FUSE |
69 | OTHERS | ||||
70 | Cabinet Structure (type), Dimensions (mm) and color | - | 800X600X2260MM ,RAL7035 ,THICKNESS=2MM | 800X600X2260MM,RAL7035,THICKNESS=2.0 mm | 800X600X2260MM ,RAL7035,THICKNESS=2.0MM |
71 | Degree of protection | - | IP21 | IP21 | IP21 |
72 | Main equipment | - | 01 input thermomagnetic circuit breaker of 3x25 A, ABB 01 output thermomagnetic circuit breaker of 2x25A for charging, ABB 01 output thermomagnetic circuit breaker 2x25A for battery, ABB 02 32A fuse with signaling contact (one for battery and the other for charging) 01 filter with condenser 01 main microprocessor control board with LCD digital display and push buttons for navigation and programming |
01 input thermomagnetic circuit breaker of 3x25 A, ABB 01 output thermomagnetic circuit breaker of 2x25A for charging, ABB 01 output thermomagnetic circuit breaker 2x25A for battery, ABB 02 32A fuse with signaling contact (one for battery and the other for charging) 01 filter with condenser 01 main microprocessor control board with LCD digital display and push buttons for navigation and programming |
01 input thermomagnetic circuit breaker of 3x25 A, ABB 01 output thermomagnetic circuit breaker of 2x25A for charging, ABB 01 output thermomagnetic circuit breaker 2x25A for battery, ABB 02 32A fuse with signaling contact (one for battery and the other for charging) 01 filter with condenser 01 main microprocessor control board with LCD digital display and push buttons for navigation and programming |
73 | Protection | - | 3-phase circuit breaker of 10 kA under 380 Vac Maximum current opening devices for protection against overloads and against short circuits. Switches with auxiliary contacts for signaling of untimely opening |
3-phase circuit breaker of 10 kA under 380 Vac Maximum current opening devices for protection against overloads and against short circuits. Switches with auxiliary contacts for signaling of untimely opening |
3-phase circuit breaker of 10 kA under 380 Vac Maximum current opening devices for protection against overloads and against short circuits. Switches with auxiliary contacts for signaling of untimely opening |
74 | Bars | - | Nude in electrolytic copper (working at above temperature of 30 ° C) in 380-220 Vac and 110 Vcc and 48 Vcc. With transparent mica for protection against inspections or maintenance | Nude in electrolytic copper (working at above temperature of 30 ° C) in 380-220 Vac and 110 Vcc and 48 Vcc. With transparent mica for protection against inspections or maintenance | Nude in electrolytic copper (working at above temperature of 30 ° C) in 380-220 Vac and 110 Vcc and 48 Vcc. With transparent mica for protection against inspections or maintenance |
75 | Operation modes | Automatic (as a charger) and Manual (as a source). | Automatic (as a charger) and Manual (as a source). | Automatic (as a charger) and Manual (as a source). | |
76 | MTBF | 250,000 hours | 250,000 hours | 250,000 hours | |
77 | Automatic start | After an incident occurs in the input power (partial or total loss of power supply) | After an incident occurs in the input power (partial or total loss of power supply) | After an incident occurs in the input power (partial or total loss of power supply) | |
81 | Spare Parts | - | FUSE | FUSE | FUSE |
82 | Tests | - | The price includes the tests specified in the spec sheet. | The price includes the tests specified in the spec sheet. | The price includes the tests specified in the spec sheet. |
83 | Electrical danger sign decal type | - | Yes | YES | YES |
84 | WARRANTY | ||||
85 | Of the equipment | - | 2 years | 2YEARS | 2 YEARS |
86 | Of spare parts | - | 2 YEARS | 2YEARS | 2 YREARS |
87 | COMMERCIAL CONDITIONS | ||||
88 | Delivery time | days | 115DAYS CFR GUAYAQUIL SEAPORT | 115DAYS CFR GUAYAQUIL ECUADOR SEAPORT | 115DAYS CFR GUAYAQUIL SEAPORT |
89 | Payment terms | % | 30% TT IN ADVANCE ,70% BEFORE SHIPMENTS | 30% TT IN ADVANCE,70% BEFORE SHIPMENTS | 30% TT IN ADVANCE ,70% BEFORE SHIPMENT |
90 | Place of delivery | - | GUAYAQUIL .ECUADOR | GUAYAQUIL ,ECUADOR | GUAYAQUIL |
92 | Note: The rectifier must be implemented to work with the battery bank of nickel cadmium |
- | Yes | YES | YES |
93 | The equipment has a minimum of 2 dry contact relays, programmable by the operator for the remote indication to be defined. | - | Yes | YES | YES |
94 | THE COMMUNICATION SYSTEM FOR REMOTE ALARMS WILL BE BY MODBUS RTU | BY PORT RS232 BY MODUBUS PROTOCOOL | BY PORT RS232,BY MODBUS PROTOCOOL | BY PORT RS232 BY MODBUS PROTOCOOL | |