66kv/110kv/145kv 60Hz Tanque Vivo Interrupter

Product Details
Customization: Available
Transport Package: Wooden
Specification: 170KV
Still deciding? Get samples of US$ 20000/Piece
Request Sample
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
500 RMB
Plant Area
1001~2000 square meters
  • 66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
  • 66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
  • 66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
Find Similar Products

Basic Info.

Model NO.
LW
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description

 
1.General structure
The product of type LW-170 HV SF6circuit breaker , with single break structure, adopts self energy  arc interrupting principle in its interrupter . The operating mechanism is of three-phase  electrical group operation. The three poles are install on one frame and controlled by one  spring mechanism.
The upper of the product is interrupter and the middle is support insulator bushing and frame, and the spring mechanism is in the middle of the frame.
The electrical control device, density device  and the mechanism energy store device are in the mechanism box.
                       2.Technical data
Rated voltage                                           170kV
Rated frequency                                     50HZ
Rated current                                         3150A
Rated short circuit breaking current    31.5kA  ,40kA
Rated short time withstand current      31.5kA  , 40kA
Rated short circuit making current      80 kA   ,  100kA
Rated peak withstand current      80 kA   ,  100kA
Power frequency withstand voltage for 1 min       325 kV
Rated Lightning impulse withstand voltage   750 kV
Rated SF6 gas pressure(200C)      0.6MPa (Required 0.64MPa)
Total travel                                               180 MM
Circuit breaker distance                        145 MM
Operation mechanism                         type CT20-III(X)P spring mechanism






66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
TECHNICAL SPECIFICATIONS CIRCUIT BREAKER
ITEM CHARACTERISTICS UNIT TOTORAS (1) ESMERALDAS (1) PORTOVIEJO(1) OFFERED TECHNICAL SPECIFICATIONS
TYPE - C
1 TYPE OF CIRCUIT BREAKER REQUIRED      
1.1 Type (similar to)   170 MHM-20 C  LW-170
1.2 Detail type   Tank Live, Single-Phase in SF6 Tank Live, Single-Phase in SF6
1.3 Use   GeneraL GeneraL
1.4 Opening   Single-Phase Single-Phase
1.5 Arc extinguishing medium   SF6 SF6
2 REQUIRED QUANTITY   3 3
3 INSTALLATION   Outdoor Outdoor
4 CHARACTERISTICS OF CIRCUIT BREAKER      
4.1 Number of Poles   3 3
4.2 Nominal voltage kV 170 170
4.3 Dielectric strength and atmospheric impulse at sea level kVpic 750 750
4.4 Industrial frequency dielectric, a minute at sea level kV 325 325
4.5 Minimum distance of contouring (pollution level III) mm 3625 3625
4.6 Nominal frequency Hz 60 60
4.7 Rated normal current A 1250 1250
4.8 Nominal current interruption of line vacuum A 63 63
4.9 Nominal current interruption of cable in vacuum A 160 160
4.10 Rated short circuit interruption      
  -Effective value of the alternating component kArms 20 20
4.11 Opening of the first polo factor   1.3 1.3
4.12 Reason for increase of the recovery voltage to 100% of the rated breakig capacity kV/us 2 2
4.13 Nominal capacity of closing short kA 104 104
4.14 Rated operating sequence   O- 0.3"/CO- 3'-CO O- 0.3"/CO- 3'-CO
4.15 Rated duration of short circuit s 1 1
4.16 Rated interruption in discordance of Poles kA 10 10
4.17 Maximum total interrupt time ms 50 50
4.18 Mechanism of operation (closing - Shooting)   Engine - Spring Engine - Spring
4.19 Drive mechanism   Single-Phase Single-Phase
4.20 Number of circuits independent of firing 125 Vdc   2 2
4.21 Mechanical strength (standard IEC 62271-100) class   M2 M2
4.22 Kind of electrical resistance (standard IEC 62271-100)   E2 E2
4.23 Voltage control and engine VDC 125 125
4.24 Voltage of auxiliary services VAC 120 120
4.25 Terminal connector for AAC 1033 kcmil conductor YES/NO Yes Yes
4.26 Insulators material   Porcelain Porcelain
4.27 Metal support structure YES/NO Yes Yes

66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
66kv/110kv/145kv 60Hz Tanque Vivo Interrupter
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier