FAILURE INDICATORS FOR AEREAL LINES 6-66 KV | ||||
Nº | DESCRIPCION | UNIDAD | REQUERIDO | GARANTIZADO |
I. | MEDIUM VOLTAGE FAILURE INDICATORS | |||
1.0 | Country of origin | Indicate | CHINA | |
2.0 | Maker | HEMG | ||
3.0 | Model | ESI | ||
4.0 | Manufacturing Standard and Testing | ANSI/IEEE 495: 2007 | ANSI/IEEE 495:2007 | |
5.0 | Type of Installation | Exterior | OUTDOOR | |
6.0 | Opening System | Monofásico | SINLE SYSTEM | |
7.0 | Type of operation | Automática y manual | AUTOMATION AND MANUAL | |
8.0 | Installation Altitude | m.s.n.m. | Hasta 4500 | 4500 |
9.0 | Operating range (system voltages) | kV | 7 - 66 | 7-66 |
10.0 | Operating range (system currents) | Amp | 1 - 600 | 1-600 |
11.0 | Operating Frequency | Hz | 60 | 60/50HZ |
12.0 | Operating temperature | ºC | -40 a +85 | (-40 TO 85) |
13.0 | IP Protection Index | IP67 | IP67 | |
14.0 | Terms of Use | Continuo | CONTINUOUS | |
- Signal Type Signal | Luminosa: Estroboscópica de alta densidad | BRIGHT | ||
- Angle of visibility | Grados | 360 | 360 | |
- Continuous display time | horas | ≥ 700 | >=700 | |
- Indicator life | años | ≥ 10 | 10 | |
- weight | kg | ≤ 1 | 0.75 | |
15.0 | Indication, minimum visibility distance during sunny day | m | 100 | 100 |
16.0 | Identification of Transient and Permanent Failure | Obligatorio | YES.COMPLAY | |
17.0 | Conductor section range | mm² | 25 a 240 | 25 TO 240 |
Short-term current | KA | 25 | 25 | |
18.0 | Current Sensor | |||
- Model | CT | |||
- Precision | Indicar | (+/-3%) | ||
19.0 | Voltage sensor | |||
- Model | BY CT | |||
Indicar | SELF-SUITABLE | |||
20.0 | Auxiliary Power System - Signal | |||
- Internal Battery | Litio | Lithium | ||
- Rated Voltage | Vdc | Indicar | 3.6V | |
- Useful life | años | ≥ 10 | 10 | |
21.0 | Programmable Parameters for Performance | |||
- Trip current range for the indication of the short-circuit current. | Corriente de disparo: Rango de programación de corriente para la indicación de cortocircuito: Desde 10 hasta 1500 A. | YES.COMPLAY | ||
Corriente de disparo: Autoajustable para fallas a tierra: 5 A a 100A (paso de 5 A) | YES.COMPLAY | |||
- Inrush current lock | Si | YES.COMPLAY | ||
- Transient fault indication time | Si, indicar | <=40MS | ||
- Permanent fault indication time | Si, indicar | 4/8/12/24 HOURS OPTIONAL | ||
- Flash Interval | Si, indicar | 5S | ||
- Flash duration | Si, indicar | >=50MS | ||
- Replacement by Current | Si | YES.COMPLAY | ||
- Replacement by Voltage | Si | YES.COMPLAY | ||
- Manual Reset | Si | YES.COMPLAY | ||
- Remote Reset | Si | YES.COMPLAY | ||
22.0 | Metal parts exposed to the weathering of the fault indicator shall be hot dip galvanized in accordance with ASTM A153 | Sí | YES.COMPLAY | |
23.0 | Accessories for Fault Indicator Assembly | |||
-Monitor for the validation of the operation of the Fault Indicator | Sí | YES.COMPLAY | ||
II. | FAULT INDICATOR COMMUNICATION SYSTEM | |||
1.0 | Wireless Local Communication between the Fault Indicator and a physical interface to external RTU or directly to external RTU that acts as a local hub | Sí | YES.COMPLAY | |
2.0 | Bidirectional communication between fault indicator and physical interface to external RTU or directly to external RTU | Sí, Indicar la distancia máxima posible de comunicación "bidireccional" que ofrece | YES,MAX 50M | |
3.0 | Medium of "local communication" | -Indicar medio y características técnicas (Radio frecuencia, Bluetooth, otro medio) -Indicar la frecuencia de trabajo del Indicador de Falla, si es Libre o licenciada. |
YES,RADIO FREQUENCY/433MHZ,FREE | |
4.0 | - Minimum sending signals of the fault indicator by local communication to the RTU that acts as a local hub | |||
Transient failure | Si | YES | ||
Permanent failure | Si | YES | ||
Absence of Tension | Si | YES | ||
Presence of Voltage | Si | YES | ||
Line Current Measurement | Si | YES | ||
Measurement of Voltage | Opcional | YES FOR BATTERY | ||
III | REMOTE TERMINAL UNIT (RTU) | |||
1.0 | Manufacturing and Testing Standard | IEC 61326-1, EN 55022, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-8 | IEC 61326-1, EN 55022, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-8 | |
2.0 | Powered by battery embedded in the RTU | Sí | YES | |
3.0 | Battery Type | Primary cells Lithium Thionyl Chloride (LiSOCl2) | YES | |
4.0 | Battery life | Años | 10 | 10 |
5.0 | Embedded GPRS Modem | Sí | YES | |
6.0 | Real-time synchronization (RTC) | Sí | YES | |
7.0 | Type of SIM card, provided by the User. | Sim Card (Indicar tipo NanoSIM o microSIM) | SIM CARD | |
8.0 | Degree of protection | IP66 | IP66 | |
9.0 | Minimum number of digital inputs for fault indicators | 12 | 12 | |
10.0 | Allows remote configuration of fault indicator | Sí, herramienta para la validación del funcionamiento | YES | |
11.0 | Permanent dispatch capacity to the SCADA of the Companies of the Distriluz Group; Directly or through the virtual platform of management of all the data received from the fault indicator | Si, indicar sí es posible el envío directamente o a través de la plataforma virtual | YES,POSSIBLE BY DIRECTLY OR BY VIRTUAL PLATEFORM | |
12.0 | Ability to store latest faults | >= 10 | Si | 10 |
13.0 | Mounting Accessories | |||
- Boxes with clamps for mounting in post of concentrators according to the manufacturer's recommendations. | Si | YES | ||
IV | REMOTE CONTROL OF FAULT INDICATORS (1) | |||
1.0 | Allows you to make configuration settings in the Field Fault Indicator | Sí | YES | |
2.0 | Stores settings to be applied in the field | Sí | YES | |
3.0 | Allows you to download equipment configurations in the field | Sí | YES | |
4.0 | Connects to a PC to download stored data | Opcional | NO | |
V | VIRTUAL INFORMATION MANAGEMENT PLATFORM | |||
1.0 | CPU and monitor for implementation in the control center | Sí/No (2) | YES | |
2.0 | Management Software for windows 8 or higher operating system | Sí | YES | |
3.0 | Includes Unlimited Software Management License and its update for a minimum period of 10 years. | Sí | YES | |
4.0 | Communication interface with the SCADA of the companies of the Distriluz Group | Sí | YES | |
5.0 | Allows user and password access | Sí | YES | |
6.0 | Configurable environment by the User | Sí | YES | |
7.0 | Set of sound and visual alarms (mimic diagram) | Sí | YES | |
8.0 | Allows the configuration of alerts via Email and SMS | Sí | YES | |
Allows the download of information stored in EXCEL format | Sí | YES |