Customization: | Available |
---|---|
Application: | Instrument |
Type: | Combined Transformer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1.1 Combined Voltage and Current Transformer of 7.5-5-2.5 / 5 A and 10000/100 V, 2 TC class 0.2S and 2 TT class 0.2. | |||||
N° | SPECIFICATION | UNIT | REQUIRED | GUARANTEED | |
VOLTAGE COILS | |||||
1 | QTY OF COILS | 2 | 2 | ||
2 | POWER | VA | 15 | 15 | |
3 | Nominal voltage in the primary. | V | 10000 | 10000 | |
4 | Nominal voltage in the secondary. | V | 100 | 100 | |
5 | Precision. | 0.2 | 0.2 | ||
Winding of Current. | |||||
6 | Qty of coils | EACH | 2 | 2 | |
7 | Power. | VA | 15 | 15 | |
8 | Nominal current in the primary. | A | 7.5-5-2.5 | 7.5-5-2.5 | |
9 | Nominal current in the Secondary. | A | 5 | 5 | |
10 | Precision. | 0.2S (EXENTED RATIO) | 0.2s | ||
11 | Altitude of Installation. | msnm | 4500 | 4500 | |
12 | System frequency. | Hz | 60 | 60 | |
13 | Mounting. | Intemperie | outdoor | ||
14 | Connection type. | Delta | delta | ||
15 | Application | Medición | metering | ||
16 | Number of phases | 3 | 3 | ||
17 | Cooling type | ONAN | onan | ||
18 | Interior insulation level on the AT side | kV | 12/28/75 | 12/28/75 | |
19 | Interior insulation level on the BT side | kV | 0.72/3 | 0.72/3 | |
20 | Position and type of insulators | Over the covert, porcelain bushing | over the covert, porcelain bushing | ||
21 | Number of Isolators in MT: | ||||
Delta | each | 5 | 5 | ||
22 | Minimum exterior BIL | kV | 125 | 125 | |
23 | Minimum leakage line | mm | 450 | 450 | |
24 | Type of service | Continue | continue | ||
Minimum values of insulation: | |||||
25 | From AT-BT | M | 10 000 | 10000 | |
26 | AT-Mass | M | 10 000 | 10000 | |
27 | BT-Mass | M | 1 000 | 10000 | |
28 | Losses in current, voltage and total transformers | W | 20 | 20 | |
29 | Oil filling tube with built-in stopper that allows the impermeability of the dielectric oil with the environment. | yes | yes | ||
30 | Terminal for connection of earth in the tank of the transformer, being the pin of stainless steel. | yes | yes | ||
31 | Lifting ears. | yes | yes | ||
Dielectric oil with the following characteristics: | yes | yes | |||
32 | Mineral oil. | yes | yes | ||
33 | Discharge voltage not less than 45 kV according to ASTM D - 1816. | yes | yes | ||
34 | Exempt from PCB. | yes | yes | ||
35 | Faucet for emptying and extraction of oil samples with gradual opening. | yes | yes | ||
36 | Device for fixing in pole (suspension handles and clamps), must include clamps with their respective 5/8 "x 6" bolts and washers. | yes | yes | ||
37 | Bronze over pressure valve of 50 kPa. | yes | yes | ||
38 | Bases with "U" profiles for anchoring. | yes | yes | ||
39 | Indication in low or high relief of the relative polarity of the windings. | yes | yes | ||
40 | Metal box of terminals in low voltage with bolted cover (with IP 66 grade) and security key with the option of placing a security seal. Additionally it must include 01 padlock per team, eyelets for the padlock installation and its respective protector, both soldiers to the cover. | yes | yes | ||
41 | The tank, the lid, the clamps, among others, should be painted with epoxy zinc-chromate base paint and finished with epoxy enamel with a thickness greater than 150 microns. For the interior of the tank, it should only be painted with the base paint. | yes | yes | ||
42 | Pickling of the tank and lid should be with a system sandblasting in high pressure. | yes | yes | ||
43 | The tank must be manufactured with cold rolled steel sheet with a thickness of not less than 2 mm. | yes | yes | ||
44 | They must include all the necessary protections to provide a quality product. | yes | yes | ||
Type of terminal board and / or terminal board. | yes | yes | |||
45 | Connection scheme. | yes | |||
46 | Output terminals in the voltage and current circuits. | yes | yes | ||
47 | Disconnector or terminal blocks or short circuitable Ritz type for the current circuit. | yes | yes | ||
48 | Protection of the voltage circuit (Thermo magnetic switch). | yes | yes | ||
49 | Antiferroronantes resistors. | Not | not | ||
50 | Installation Manual and testing protocol of the manufacturer attached to the equipment. | Yes | yes | ||
51 | 8 "diameter brackets for MT 13/300 posts with 5 / 8x6" bolts with 2 flat washers and one pressure washer, both of which should be hot galvanized steel. | Yes | yes | ||
Bitmap
|
|||||
1.2 Combined Voltage and Current Transformer of 20-10 / 5 A and 10000/100 V, 2 TC class 0.2S and 2 TT class 0.2. | |||||
N° | SPECIFICATION | UNIT | REQUIRED | GUARANTEED | |
VOLTAGE COILS | |||||
1 | QTY OF COILS | 2 | 2 | ||
2 | POWER | VA | 15 | 15 | |
3 | Nominal voltage in the primary. | V | 10000 | 10000 | |
4 | Nominal voltage in the secondary. | V | 100 | 100 | |
5 | Precision. | 0.2 | 0.2 | ||
Winding of Current. | |||||
6 | Qty of coils | EACH | 2 | 2 | |
7 | Power. | VA | 15 | 15 | |
8 | Nominal current in the primary. | A | 20 to 10 | 20 TO 10 | |
9 | Nominal current in the Secondary. | A | 5 | 5 | |
10 | Precision. | 0.2S (EXENTED RATIO) | 0.2s | ||
11 | Altitude of Installation. | msnm | 4500 | 4500 | |
12 | System frequency. | Hz | 60 | 60 | |
13 | Mounting. | outdoor | outdoor | ||
14 | Connection type. | Delta | DELTA | ||
15 | Application | measure | MEASURE | ||
16 | Number of phases | 3 | 3 | ||
17 | Cooling type | ONAN | ONAN | ||
18 | Interior insulation level on the AT side | kV | 12/28/75 | 18/28/75 | |
19 | Interior insulation level on the BT side | kV | 0.72/3 | 0.72/5 | |
20 | Position and type of insulators | Over the cover, porcelain bushing | OVER THE COVER PORCELAIN BUSHING | ||
21 | Number of Isolators in MT: | ||||
Delta | each | 5 | 5 | ||
22 | Minimum exterior BIL | kV | 125 | 125 | |
23 | Minimum leakage line | mm | 450 | 450 | |
24 | Type of service | Continue | CONTINUE | ||
Minimum values of insulation: | |||||
25 | From AT-BT | M | 10 000 | 10000 | |
26 | AT-Mass | M | 10 000 | 10000 | |
27 | BT-Mass | M | 1 000 | 1000 | |
28 | Losses in current, voltage and total transformers | W | 20 | 20 | |
29 | Oil filling tube with built-in stopper that allows the impermeability of the dielectric oil with the environment. | yes | YES | ||
30 | Terminal for connection of earth in the tank of the transformer, being the pin of stainless steel. | yes | YES | ||
31 | Lifting ears. | yes | YES | ||
Dielectric oil with the following characteristics: | yes | YES | |||
32 | Mineral oil. | yes | YES | ||
33 | Discharge voltage not less than 45 kV according to ASTM D - 1816. | yes | YES | ||
34 | Exempt from PCB. | yes | YES | ||
35 | Faucet for emptying and extraction of oil samples with gradual opening. | yes | YES | ||
36 | Device for fixing in pole (suspension handles and clamps), must include clamps with their respective 5/8 "x 6" bolts and washers. | yes | YES | ||
37 | Bronze over pressure valve of 50 kPa. | yes | YES | ||
38 | Bases with "U" profiles for anchoring. | yes | YES | ||
39 | Indication in low or high relief of the relative polarity of the windings. | yes | YES | ||
40 | Metal box of terminals in low voltage with bolted cover (with IP 66 grade) and security key with the option of placing a security seal. Additionally it must include 01 padlock per team, eyelets for the padlock installation and its respective protector, both soldiers to the cover. | yes | YES | ||
41 | The tank, the lid, the clamps, among others, should be painted with epoxy zinc-chromate base paint and finished with epoxy enamel with a thickness greater than 150 microns. For the interior of the tank, it should only be painted with the base paint. | yes | YES | ||
42 | Pickling of the tank and lid should be with a system sandblasting in high pressure. | yes | YES | ||
43 | The tank must be manufactured with cold rolled steel sheet with a thickness of not less than 2 mm. | yes | YES | ||
44 | They must include all the necessary protections to provide a quality product. | yes | YES | ||
Type of terminal board and / or terminal board. | yes | YES | |||
45 | Connection scheme. | ||||
46 | Output terminals in the voltage and current circuits. | yes | YES | ||
47 | Disconnector or terminal blocks or short circuitable Ritz type for the current circuit. | yes | YES | ||
48 | Protection of the voltage circuit (Thermo magnetic switch). | yes | YES | ||
49 | Antiferroronantes resistors. | Not | NOT | ||
50 | Installation Manual and testing protocol of the manufacturer attached to the equipment. | Yes | YES | ||
51 | 8 "diameter brackets for MT 13/300 posts with 5 / 8x6" bolts with 2 flat washers and one pressure washer, both of which should be hot galvanized steel. | Yes | YES | ||
Bitmap
|
|||||
1.3 Combined Voltage and Current Transformer of 150-100 / 5 A and 10000/100 V, 2 TC class 0.2S and 2 TT class 0.2. | |||||
N° | SPECIFICATION | UNIT | REQUIRED | GUARANTEED | |
VOLTAGE COILS | |||||
1 | QTY OF COILS | 2 | 2 | ||
2 | POWER | VA | 15 | 15 | |
3 | Nominal voltage in the primary. | V | 10000 | 10000 | |
4 | Nominal voltage in the secondary. | V | 100 | 100 | |
5 | Precision. | 0.2 | 0.2 | ||
Winding of Current. | |||||
6 | Qty of coils | EACH | 2 | 2 | |
7 | Power. | VA | 15 | 15 | |
8 | Nominal current in the primary. | A | 150-100 | 150-100 | |
9 | Nominal current in the Secondary. | A | 5 | 5 | |
10 | Precision. | 0.2S (EXENTED RATIO) | 0.2S | ||
11 | Altitude of Installation. | msnm | 4500 | 4500 | |
12 | System frequency. | Hz | 60 | 60 | |
13 | Mounting. | outdoor | OUTDOOR | ||
14 | Connection type. | Delta | DELTA | ||
15 | Application | measure | MEASURE | ||
16 | Number of phases | 3 | 3 | ||
17 | Cooling type | ONAN | ONAN | ||
18 | Interior insulation level on the AT side | kV | 12/28/75 | 12/28/75 | |
19 | Interior insulation level on the BT side | kV | 0.72/3 | 0.72KV/3 | |
20 | Position and type of insulators | Over the cover, porcelain bushing | OVER THE COVER PORCELAIN BUSHING | ||
21 | Number of Isolators in MT: | ||||
Delta | each | 5 | 5 | ||
22 | Minimum exterior BIL | kV | 125 | 125 | |
23 | Minimum leakage line | mm | 450 | 450 | |
24 | Type of service | Continue | CONTINUE | ||
Minimum values of insulation: | |||||
25 | From AT-BT | M | 10 000 | 10000 | |
26 | AT-Mass | M | 10 000 | 10000 | |
27 | BT-Mass | M | 1 000 | 1000 | |
28 | Losses in current, voltage and total transformers | W | 20 | 20 | |
29 | Oil filling tube with built-in stopper that allows the impermeability of the dielectric oil with the environment. | yes | YES | ||
30 | Terminal for connection of earth in the tank of the transformer, being the pin of stainless steel. | yes | YES | ||
31 | Lifting ears. | yes | YES | ||
Dielectric oil with the following characteristics: | yes | YES | |||
32 | Mineral oil. | yes | YES | ||
33 | Discharge voltage not less than 45 kV according to ASTM D - 1816. | yes | YES | ||
34 | Exempt from PCB. | yes | YES | ||
35 | Faucet for emptying and extraction of oil samples with gradual opening. | yes | YES | ||
36 | Device for fixing in pole (suspension handles and clamps), must include clamps with their respective 5/8 "x 6" bolts and washers. | yes | YES | ||
37 | Bronze over pressure valve of 50 kPa. | yes | YES | ||
38 | Bases with "U" profiles for anchoring. | yes | YES | ||
39 | Indication in low or high relief of the relative polarity of the windings. | yes | YES | ||
40 | Metal box of terminals in low voltage with bolted cover (with IP 66 grade) and security key with the option of placing a security seal. Additionally it must include 01 padlock per team, eyelets for the padlock installation and its respective protector, both soldiers to the cover. | yes | YES | ||
41 | The tank, the lid, the clamps, among others, should be painted with epoxy zinc-chromate base paint and finished with epoxy enamel with a thickness greater than 150 microns. For the interior of the tank, it should only be painted with the base paint. | yes | YES | ||
42 | Pickling of the tank and lid should be with a system sandblasting in high pressure. | yes | YES | ||
43 | The tank must be manufactured with cold rolled steel sheet with a thickness of not less than 2 mm. | yes | YES | ||
44 | They must include all the necessary protections to provide a quality product. | yes | YES | ||
Type of terminal board and / or terminal board. | yes | YES | |||
45 | Connection scheme. | YES | |||
46 | Output terminals in the voltage and current circuits. | yes | YES | ||
47 | Disconnector or terminal blocks or short circuitable Ritz type for the current circuit. | yes | YES | ||
48 | Protection of the voltage circuit (Thermo magnetic switch). | yes | YES | ||
49 | Antiferroronantes resistors. | Not | NOT | ||
50 | Installation Manual and testing protocol of the manufacturer attached to the equipment. | Yes | YES | ||
51 | 8 "diameter brackets for MT 13/300 posts with 5 / 8x6" bolts with 2 flat washers and one pressure washer, both of which should be hot galvanized steel. | Yes | YES |