• Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin
  • Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin
  • Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin
  • Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin
  • Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin
  • Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin

Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin

Application: Power
Samples:
US$ 100000/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
PCM
Production Capacity
1000

Product Description

Protection Control and Measure of 138kv Substation Including of Power Transformer -Over Head Line-Distribution Panel From Brand Siemens-Schneider-Chin
CONTROL BOARD, PROTECTION AND MEASUREMENT OF THE POWER TRANSFORMER:
TABLERO DE CONTROL, PROTECCIÓN Y MEDICIÓN DEL TRANSFORMADOR DE POTENCIA:
Multifunction main protection equipment of the power transformer with the following protection functions
Equipo multifunción de protección principal del transformador de potencia con las siguientes funciones de protección:
87T   Protección diferencial de  TRANSFORMADOR
86   Disconnection relay and lock / Rele de disparo y bloqueo
21   Protección de distancia      
50/51   Protección de sobrecorriente instantánea / temporizada de fase 
50N/51N   Protección de sobrecorriente a tierra instantánea/temporizada   
67/67N   Protección de sobrecorriente direccional de fases / a tierra
27/59   Protección de Mínima y sobre tensión   
25   Función de chequeo de Sincronismo    
79   Función de Recierre      
81   Función de Frecuencia con 8 etapas   
50BF   Falla de Interruptor      
    Función de Derivada de Frecuencia y Umbral de Frecuencia 
RF   Registro de Falla      
RE   Registro de eventos      
LF   Localización de fallas      
OSC   Oscilografia        
Entradas análogas 1/5 A, puerto de comunicación frontal RJ45 
(Ethernet), protocolo de comunicación IEC 61850, DNP3, Ethernet RJ 45, serial RS232, IRIG-B.
Equipo multifunción de protección de respaldo del transformador de potencia con las siguientes funciones de protección:
21   Protección de distancia
50/51   Protección de sobrecorriente instantánea/temporizada de fase
50N/51N   Protección de sobrecorriente a tierra instantánea/temporizada
67/67N   Protección de sobrecorriente direccional  de fases/a tierra.
27/59   Protección de Mínima y sobre tensión
25   Función de chequeo de Sincronismo
79   Función de Recierre
81   Función de Frecuencia con 8 etapas
50BF   Falla de Interruptor
    Función de Derivada de Frecuencia y Umbral de Frecuencia
RF   Registro de Falla
RE   Registro de eventos
LF   Localización de fallas
OSC   Oscilografia
The equipment will have functions for sending data to a SCADA system, so it will have ports and communication protocol IEC61850.
El equipo tendrá funciones para envío de datos a un sistema SCADA por lo que tendrá puertos y protocolo de comunicación IEC61850. 
The equipment will have functions of bay controller with large digital mimic screen for control, command,
El equipo tendrá funciones de controlador de bahía con pantalla mímico digital grande para control, mando, 
indication of parameters and alarms in real time, sending data to a SCADA system so it will have communication ports and protocols.
indicación de parámetros y alarmas en tiempo real, envío de datos a un sistema SCADA por lo que tendrá puertos y protocolos de comunicación. 
Multi-tariff Active-Reactive Energy Meter with measurement functions: kWh, KVARh, KW, KVAR, A, V, with ETHERNET port (RS485), current input 1 (5) A;
Medidor de Energia Activa-Reactiva tipo Multitarifa con funciones de medición: kWh, KVARh, KW, KVAR, A, V, con puerto  ETHERNET (RS485), entrada corriente 1(5)A; 
Alarm panel / Panel de alarmas
CONTROL BOARD, PROTECTION AND MEASUREMENT OF 22.9 kV CELLS:
TABLERO DE CONTROL, PROTECCIÓN Y MEDICIÓN DE CELDAS DE 22.9 kV:
1 Equipo multifunción Protección de Celdas de llegada de 22.9 kV con las siguientes funciones de protección:    
50/51   Protección de sobrecorriente instantánea / temporizada de fase
50N/51N   Protección de sobrecorriente a tierra instantánea / temporizada
67/67N   Protección de sobrecorriente direccional  de fases / a tierra
27/59   Protección de Mínima y sobre tensión
25   Función de chequeo de Sincronismo
79   Función de Recierre
81   Función de Frecuencia con 8 etapas 
Funciones de Control
Control para 01 interruptor, cuchilla de PT y 01 seccionador, monitoreo de estados de posición, registro disturbios.
Incluye display  gráfico mímico para control y mando en tiempo real
Registro de Medida
Indicación de corriente y tensión trifásica y neutro, potencia y energía trifásica, fdp y frecuencia
Comunicación de Datos 
Un Puerto de comunicación frontal RJ45 (ETHERNET). Puertos de comunicación Posterior de Fibra Optica para IEC61850
4 Equipos multifunción Protección de Celda de salida de 22.9 kV con las siguientes funciones de protección:
50/51   Protección de sobrecorriente instantánea / temporizada de fase.
50N/51N   Protección de sobrecorriente a tierra instantánea / temporizada
67/67N   Protección de sobrecorriente direccional  de fases / a tierra
27/59   Protección de Mínima y sobre tensión
El equipo tendrá entradas análogas 1/5 A, puerto de comunicación frontal RJ45 (Ethernet), 
protocolo de comunicación IEC 61850, DNP3, Ethernet RJ 485, serial RS232, IRIG-B.
Funciones de Control
Control para 01 interruptor, cuchilla de PT y 01 seccionador, monitoreo de estados de posición, registro disturbios.
Incluye display  gráfico mímico para control y mando en tiempo real
Registro de Medida
Indicación de corriente y tensión trifásica y neutro, potencia y energía trifásica, fdp y frecuencia
Comunicación de Datos 
Un Puerto de comunicación frontal RJ45 (ETHERNET). Puertos de comunicación Posterior de Fibra Optica para IEC61850


 