• 33kv/11kv 15mva Three Phase Two Winding Power Transformer
  • 33kv/11kv 15mva Three Phase Two Winding Power Transformer
  • 33kv/11kv 15mva Three Phase Two Winding Power Transformer
  • 33kv/11kv 15mva Three Phase Two Winding Power Transformer
  • 33kv/11kv 15mva Three Phase Two Winding Power Transformer
  • 33kv/11kv 15mva Three Phase Two Winding Power Transformer

33kv/11kv 15mva Three Phase Two Winding Power Transformer

Application: Power
Phase: Three
Core: Core-type Transformer
Cooling Method: Oil-immersed Type Transformer
Winding Type: Two-winding Transformer
Certification: ISO9001
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
SZ11
Usage
Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer
Frequency Characteristics
High Frequency
Transport Package
Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Trademark
HEMG
Origin
China
Production Capacity
10000

Product Description



33kv/11kv 15mva Three Phase Two Winding Power Transformer
33kv/11kv 15mva Three Phase Two Winding Power Transformer
33kv/11kv 15mva Three Phase Two Winding Power Transformer

33kv/11kv 15mva Three Phase Two Winding Power Transformer
33kv/11kv 15mva Three Phase Two Winding Power Transformer


 

 

TECHNICAL DATA SHEET

FOR 15MVA, 33/11kV

DISTRIBUTION POWER TRANSFORMER

 

ITEM

DESCRIPTION

UNIT

REQUIRED

GAURANTEED

1.

Manufacturer

HEMG

2.

Country of manufacture

 

CHINA

3.

Type of transformer

 

Three Phase Step Down Power Transformer

Three Phase Step Down Power Transformer

4.

Standard and tolerances

 

IEC 60076

IEC 60076

5.

Installation

 

Outdoor

Outdoor

6.

Insulation fluid

 

Mineral oil (type NYNAS 10 GBX)

Mineral oil (type NYNAS 10 GBX)

7.

Type of preservation

 

Conservator with air breather

Conservator with air breather

8.

Type of cooling

 

ONAN

ONAN

9.

Type of core (shell type/core type)

 

Core Type

Core Type

10.

Rated power (ONAN/ONAF)

MVA

15

15

11.

Rated voltages at no-load - HV side - LV side

kV kV

33 / 11

33 / 11

12.

Rated frequency

Hz

50

50

13.

Type of tap changer on HV side

 

On-load (ABB type UZ)

On-load (ABB type UZ)

14.

Type of regulation

 

CFR

CFR

15.

Number of taps

 

17 (+,-8 x 1.25%)

17 (+,-8 x 1.25%)

16.

Vector group

 

YD1

YD1

17.

Temperature rise: - Top oil - Windings - Hot spot

K K K

45 55 68

45 55 68

18.

Impedance voltage

%

10% at 15MVA, 33/11kV base

10% at 15MVA, 33/11kV base

19.

No load loss at rated voltage

KW

13

13

20.

Load loss at nominal tap

KW

76

76

21.

Auxiliary loss

KW

N/A

N/A

22.

Flux density at nominal tap

T

<1.72

<1.72

23.

No load current at nominal tap

%

0.22

0.22

24.

Lightning Impulse test voltage - Full wave (peak) (Acc. To IEC 60076-3) - HV winding - HV Neutral - LV winding

kVp kVp kVp

650 - 170

650 - 170

25.

Short-duration induced AC withstand voltage - HV - LV

kV

70, 22

70, 22

26.

Separate source AC withstand voltage test, (Acc. to IEC 60076-3) - HV winding - LV winding

kV

38 70

38 70

27.

Sound Pressure level (ONAN/ONAF)

dB

62

62

28

Overload/Fault current capability

kA

Accr. to IEC 354

Accr. to IEC 354

29.

Basic Insulation level

M

LI 650 AC 170 / 75 (Phase)

LI 650 AC 170 / 75 (Phase)

30.

Short Circuit Impedances: Lowest tap Highest tap

/phase

/phase

After Placement of Order

After Placement of Order

31.

Physical Dimensions

W x L x H

4650*3700*4000MM

32.

Total Quantity of Oil required

kg

8650KG

33.

Filling Medium of Tank for shipment If oil, state the quantity required

Ltrs

Transformer will be shipped with oil

34.

Total capacity of conservator

Ltrs

 

35.

Total weight of Transformer

kg

32500KG

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.