Reactive Power Regulator

Current Type: AC
Phase: Three Phase
Frequency Characteristics: Intermediate Frequency
Usage: Reactive Power Compensation
Frequency: Industrial Frequency
Size: Small
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
JKW
Transport Package
Carton
Specification
144X144
Trademark
HEMG
Origin
China
Production Capacity
1000000

Product Description

Reactive Power Regulator


Reactive Power Regulator
Operation Manual Instruction


 
  1. High compensation precision for counting capacity of capacitor by reactive power;
  2. High power factor of measuring precision, wide display area
  3. With automatic distinguish function, automatically keep the voltage signal and current signal in the same terminal;
  4. With two working modes of full-automatic and handwork set
  5. Friendly human-computer interface, easy to operate
  6. Different controlling parasmeter is adjustable in whole digit; it is easy to use at direct-viewing
  7. With two working modes of auto and manual operation
  8. With the protection function of overvoltage and overcurrent
  9. With the power down function,so the data cannot lose
  10. With low impedance (≤0.01)
1. Instruction
Reactive power regulator is suitable for self-adjusting capacitor compensating in low voltage distribution system and make power factor meet with presetting by user, therefore it will increase the efficiency of the power transformer, reduce line loss, and improve voltage quality. On the final it will increacse the econmic and social benefits.
2. Ambient conditions
  a. Altitude not more than 2500m
  b. Ambient temperature: -25ºC~50ºC
  c.Relative humidity: <50% at 40ºC and <90% at 20ºC
  d. On site where it has no correstive gases, condutive dusts, combustible explosive mediums
  e. On site where it has no severe vibration
3. Technical specifictions
   Rated working voltage:    AC380/415V 50Hz
   Rated working current:    AC 0~5A 50 Hz
   Rated output power:       AC 220V 7A 50Hz
   Displaying power factor:   Lag 0.001 ~ forward 0.001
   Working mode:           automatic selecting the best or loop switch
   Senitivity:               100 mA
   Protection class:           IP 40 (outer enclosure)
4. Characteristic of working mode
   Full auto working mode: Thiscontroller has already adjusted the work mode under the full-automatic mode before the factory, all parameters already been preset according to the most rational way, it will work normally so long as the user connect correctly.
   Manual set mode: It can be accurate control input and cutoff and no input and cutoff shaking of capacitor group, which is suitable for the occasions of all working environment especially light load with broad-minded capacitance of capacitor.
5. Advie for use
  The characteristics of full automatic working mode: This controller has been in the automatic mode befor leaving factory, All parameters have been preset according to the most reasonable method. It workes normally as long as users connect the wire correctly.
  The characteristics of handwork setting mode: when the load is light at servel fields, and the capacity is big, thecontroller goes on input and cut vibration continuously, under this condition, the handwork mode is suitalbe for using.
6. Menu operation
  Operation the Menu key in turn, the controller will enter into the menu of power factor, reactive power, Manual operation and parameter preset circularly. Note: only after entering into manual operation menu in 2 seconds, could the operation Key Menu be entered into parameter adjustment menu. Other menu haven't this limit.
The reactive power menu wil display the symbol AUTO under the full automatic mode.
The parameter preset menu has submenu 16 items under handwork mode. Operation the Menu Key in turn, enter into each of submenu separately. When operating the key of incresing and decreasing by degrees, the target data of each submenu can be preset, and the four-posiotion digitorn displays menu code and target data alternately. For example: PR-1 means menu code, 098 means target data. The parameter preset menu has submenu 4 items under full automatic mode, that is Power Factor Preset, Delay preset menu, over voltage Preset, loop preset (Preset menu of transformation ratio of public current mutual inductor).
7.  Displayed Contens of each menu under different working modes
Working Mode Power factor Reactive power Manual operation
Manual Mode Displaypower factor Displayreactive power Displaypower factor
Auto Mode Displaypower factor Display "RUR0" Display power factor
8. Debugging
Warning:During the proccess of adjustment,user should abide by the following adjus tment step.The one withis the controller is under handwork mode.
A:Assemble the compensating device according to the demand of connection diagram,and then make a detailed examination so as to remove the mistake that may coures setious potential safety hazard.
B:Switching in compensating device,the controller enters into automatic state.
  Note:If the compensating device is running under non-actual condition,before starting the machine,user should make sure that the current signal lagging voltage signal.
  • c.input the transformation ratio at site signal current mutual inductor,for the detail shown as Menu operation.
e.Operate Key Menu'to make the handwork operation indicator light,handwork operation acting as a measure of compensating device adjustment can be used for checking if the connection is correct or not.Operate Key increasing by grade',input caacitor group,operate Key decreasing by grade cut caacitor group.Note:The output terminal which the correspondent capacitor value is zero can't be conduct inputand cut action.Without indicator is permitted for the operation mentioned above,but the power factor displayed and reactive power value is meaningless.
F.In order to make the controller automatically input and cut capacitor group,besides user should put menu underside menu of Power Factor,Reactive Factor,the current signal lagging voltage signal and system voltage is not higher than overvoltage protective value and is not lower than undervoltage protective value which condition also is important.
9."Key" functions
Name Mark Contents
Menu key   Main menu,and submenu to select
Increase key   Increase the value at status of "Value setting",switch on the capacitor unit at the status of "Hand Operating"

Decrease key

 
Decrease the value at status of"Value setting",switch off the capacitor unit at the status of"Hand Operating"
On the status of "Power factor"display current
On the status of "Reactive Power "display voltage
10. Menu Operation
1.Parameter Adjustment step under auto mode:
Selection of being preset Parameter Code of
parameter
Lmplication of code Range of
Parameter
Adjustment of parameter
Enter"Menu"button,"
parameter preset"is ON
PR-1 COS preset   The parameter  will increase by pressing" "button; the parameter will reduce by pressing" "button
Press"Menu"button again PR-2 Time-delay preset  
Press"Menu"button again PR-3 Over-voltage preset  
Press"Menu"button again PR-4 Loop reset 1-12 loops
Pressing"△▽"button
to gether
At the same time
for 3seconds.
PR-5 Signal homonymy
end
Auto
Inentification
ON-OFF
Press"Menu"button again Store the being preset pararneter,enter into auto running state
2.Parameter Adjustment step under manual mode;
Selection of being
 preset Parameter
Code of
parameter
Lmplication
 of code
Range of
Parameter
Adjustment of parameter
Enter"Menu"button,"
Parameter preset"is ON
PR-1 COS preset 0.8-0.99




The parameter  willincrease by pressing" "button; the parameter will reduce by pressing" "button
Press"Menu"button again PR-2 Time-delay preset 1-250 second
Press"Menu"button again PR-3 Over-voltage preset 400-500V
Press"Menu"button again PR-4 CT ratio preset 50-6000
Press"Menu"button again   -01 Capacity of the first loop caacitor 0-150kvar
Press"Menu"button again   -02 Capacity of the first loop caacitor 0-150kvar
-------   --------   -------
Press"Menu"button again   -12 Capacity of the first loop caacitor 0-150kvar
Pressing"△▽"button
to getherAt the same time
for 3seconds.
PR-5 Signal homonymy end Auto identification ON-OFF
Press"Menu"button again Store the being preset pararneter,enter into auto running state

Note:
  • CT ratio reset value is the numerator value of signal current transformer ratio.For example: user's signal current transformer ratio is 500/5A,then,CT ratio preset value is 500,other than
  • The capacitance should be preset as"0"if it is not connected with output loop of capacitor. The output loop controller will not output controlling signalif the preset capacitance of capacitor is"0"
  • Signal homonymy end Auto identification means voltage and current signals are not at the homonymy end state owing to connecting reason;the process of controller adjusting.it at homonymy end state through judgment program in the way of software,two signal lines that is unnecessary to exchange current signal by manual.
  • If the signal homony my end auto identification parameter is"NO"adjusted by user,which means allow homonymy end to auto identify;and if OFF,which means forbidden to scope of controller.The power factor scope will lag 0.30 of selecting"ON";the power factor scope will lag 0.001 to lead 0.001.ifuser's on -site power factor has the possibility of lower 0.3,the manufacturer strongly require user to adjust this parameter as"OFF".If occurring non-homonymy end state,it is ok to exchange the two signal lines of power signal at manual
11.Explicit Declaration
Overvoltage state Under power factor,reactive power,manual operation menus.if the digital display unit display the same numerical value.that means the controller is overv oltage removal state.The dislayed value is system voltage value.
Cos¢ value      Dislaying0.985 means present power factor is lagging 0.985.
Displaying-.985 means present power factor is leading 0.985.
Undercurrent state Displaying[--0means undercurrent signal,the current is less than 100mA


12. Connection Diagram

13. Fault and Remove
   During using and installing the controller, for some easy overlook connection mistakes will result in compensating abnormally operating. The regular fault phenomena and its removel methods ad following:
  1. Input control head panel, indicating lamp lights, but AC contactor can't close. This phenom enon caused because the inside coil of AC controller have not been obtained power supply or not enough power. User should check whether the type of AC controller is the same as the drawing, fuse is perfect, power supply common on the terminal of AC controller and output common termianl of controller are connection on the same wiring, and connection is open circuit or not.
  2. With the charging abnormality and no changing of input power factor of capacitor, the former caused be cause of the uncorrected sampling of voltage or current signal. User should pay more attention to checking signal sampling. The latter caused because of the uncorrected position of use's signal mutual inductor inserted. The current mutual inductor should be in serted in the output position where shows total load current change(e.g Total cabinet bus line)
  3. The gauge outfit of controller always displays C-0, this phenomenon caused of the big or small signal current or no current mutual inductor is rational or not, current signal loop has open circuit or connected with other instruments in series and parallel or not.
  4. Oper group or two groups capaciteor never has input (input indicating lamp can's light) This phenomenon only will take place when in handwork operating working, but the common reasion is that the user not preset capacity or preset too big data when men ds parametes. In this case, as long as preset capacity of capacitor again.
  5. The reactive power value of controller has a wide gas with onsite valu This phenonmenon caused generally because of unconnected transformation ratio of current mutual inductor preset. User should check whether the transformation ratio of the signal current mutual is in correspondence with preset value or not.
  6. The power factor value of controller has a wide gas with onsite value. There are two possiblites for these phenomena: one is the unconnected sampling of voltage or current signals; the other is current signal exceed 5.5A (selecting the transformation ratio of current mutual inductor is unreasonbale)
  7. If there are same difficult problems and user dose not solve by himself, please contact with the local dealer or manufacturer.





 