Protection and Control and Metering PCM Panel of Different Protion for Power Transformer up to 230kv

Application: Power, Instrument
Phase: Three
Certification: ISO9001-2000, ISO9001
Usage: Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer
Frequency Characteristics: High Frequency
Transport Package: Carton with Wooden
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
PCM
Specification
33KV/72.5KV/123KV/132KV/145KV
Trademark
HEMG/ABB/SIMENS
Origin
China
Production Capacity
100000

Product Description

No. DESCRIPTION TION UNID. VALUE REQUIRED VALUE OFFERED
         
1.0.0 GENERAL DATA      
1.1.0 Maker     ABB/SAC
1.2.0 Model     RET650
1.3.0 Country of manufacture     Sweden/China
         
2.0.0 CONSTRUCTIVE ASPECTS      
2.1.0 Frequency Hz 60 50/60Hz
2.2.0 Weight Kg Indicate 300
2.3.0 Approximate Dimensions (Height, Width, Depth) (,,) Mm Indicate 2260*800*600mm(H*W*D)
2.4.0 Mounting   Yes Yes
2.5.0 Operating temperature ° C -10 to +55 -25 to +55ºC
2.6.0 Storage temperature ° C -40 to +70 -40 to +85ºC
2.7.0 Relative Humidity Range % 10 to 90 <93%
3.0.0 TENSION AND CURRENT ANALOGUE INPUTS      
  Number of analog inputs   24 12
3.1.0 Voltage inputs      
  - Number of entries   Referring to Fig.  
  - Rated voltage (Vn) Vac 110 110V
  - Operating margin Vac 0 - 340  
  - Maximum permanent voltage Vac 420 420V rms
  - Maximum tension for 10 seconds Vac 450 450V rms
  Burden GOES <.02 To 110 Vac <0.05 VA
3.2.0 Current Inputs      
  - Number of entries   fifteen 6
  - Rated current (In)
(IN)
Amp. 1 1/5A
  - Operating margin Amp. (0-100) x In  
  - Maximum permanent current Amp. 4 In 20A
  - Maximum current for 1 sec. Amp. 100 In 500A
  Burden GOES <0.02 to 1A <0.05 VA
 
4.0.0 DEPARTURES AND BINARY ENTRIES   Yes Yes
4.1.0 Programmable Trip and Signaling Outputs      
  - Number of contacts (minimum)
-()
No. 24 24
  - Maximum operating voltage
-
Vac / Vdc 250 Vac, Vdc 250 Vac, Vdc
  - Test voltage at the open contact, for 1 min.
-,1.
Vrms 1000 Meet
  - Permanent current carrying capacity
-
TO Referring to Fig. 5A
  - Current carrying capacity for 1 sec
- 1s
TO 10 10A (3s)
10A (0.5s)
  - Cutting capacity TO 110 V / 0.4 A 48V / 0.5 A
110V / 0.1 A
220V / 0.04 A
125V / 0.35A
  - Closing capacity TO 30 A (for 0.2 s) 10 A (per 1.0 s) Meet
4.2.0 Inputs      
  - Programmable input contacts   Yes Yes
  - Number of input contacts (minimum)
()
No. 32 Max.50
  - Voltage range V 24 - 250 24...250 V DC
  - Power consumption per input W 0.2 W to 125 V <0.3 W
4.3.0 LED's of signaling   Yes Yes
  - relay status   3 Meet
  - the performance of the protection functions
-
  15 (6 red and 9 yellow)
15(69)
15
4.5.0 Interfaces      
  - Large HMI on the relay front panel
HMI
  Yes Yes
  - Front Ethernet port, PC connection
-,PC
  1 port, RJ45 1 port, RJ45
  - Ethernet optical port for remote communication   1 port, ST Meet
4.6.0 Remote Communication      
  - Communication protocol   IEC 61850 IEC 61850
  - Communication speed MBps 100 100 MBits/s
5.0.0 AUXILIARY SUPPLY      
5.1.0 Auxiliary Rated Voltage Vcc 90 to 250 88...300 V DC
5.2.0 Tolerance % ± 20% 15%
5.3.0 Typical Consumption      
  - In normal operating condition
-
W fifty 30W
5.4.0 Auxiliary insertion power TO <5 A, for 0.1 sec <5 A, for 0.1 sec
6.0.0 SPECIAL TESTS      
6.1.0 EMC Immunity (IEC 60255-22; 22-1; 22-2; 22-3; 22-4)
(IEC 60255-22;22-1;22-2;22-3;22-4)
  Yes Yes
6.2.0 EMC Emission (IEC 60255-22, IEC 61000-4, IEEE / ANSI C37.90)
(IEC 60255-22,IEC 61000-4,IEEE / ANSI c37.90)
  Yes Yes
6.3.0 Insulation (IEC 255-5)
(IEC 255-5)
  Yes Yes
6.4.0 Mechanical Efforts IEC255-21, IEC68-2
iec255-21,iec68-2
  Yes Yes
6.5.0 Environmental Testing IEC60068, IEC68-2
iec60068,iec68-2
  Yes Yes
7.0.0 PROTECTION FUNCTIONS      
7.1.0 List of included functions      
  Transformer Differential (87T)   Yes Yes
  Distance between phases and ground phase (21 / 21N)
(21/21 n)
  Do not No
  Phase overcurrent and ground phase (50/51, 50 / 51N)   Yes Yes
  Directional phase and ground phase overcurrent (67 / 67N)   Yes Yes
  Minimum and maximum voltage (27/59)
(27 / 59)
  Yes Yes
  Bay controller up to 30 devices (6 switches)
30(6)
  Do not Do not
  Switch failure (50BF)
(50bf)
  Yes Yes
  Overexcitation (24)
(24)
  Yes Yes
  Synchronization check (25)
(25)
  Yes Yes
  Thermal Overload (49)
(49)
  Yes Yes
  Frequency (81)
(81)
  Yes Yes
  Fault Recording and Oscillographs (RF / RO)   Yes Yes
7.2.0 Transformer Differential (87T) (87t)      
  - Operation characteristic
-
  Adaptable Yes
  - Precision In ± 2.0%, for I <Ir ± 1.0% of Irr for I < Ir
± 1.0% of I for I > Ir
  - Sensitive base function In 10-60% (4.0-100.0)% of IBase
  - Unrestricted differential current limit In 100-5000 90-6000
  - Second Harmonica Restriction fundamental 5.0 - 100%  
  - Fifth Harmonica Restriction fundamental 5.0 - 100%  
  - Connection type of each winding   Y, star or D, Delta Y
  - Phase shifting between the High Dev W1 and each of the W2, and W3 windings
 
notation 0 - 11  
Time
  - Operating time, restricted function Ms 25, t Ipeak of 0 to 2 x Id 25 ms typically at 0 to 10 x IdMin
7.3.0 Phase and ground phase instantaneous overcurrent (50 / 50N) (50/50N)      
  - Adjustment steps (minimum)   1  
  - Operating current range Ibase (1 to 2500)% Ibase  
  - Operation time Ms 25 ms (0 to 2 Iset)  
10 ms (0 to 10 Iset)  
  - Replacement time
 
Ms 25 ms (0 to 2 Iset)  
35 ms (0 to 10 Iset)  
7.4.0 Phase overcurrent phase (51/67) and ground phase (51N / 67N) (51 / 67)(51n / 67n)      
  - Adjustment steps
 
  4  
  - Operating current range % In (1 to 2500)% Ibase (5-2500)% of lBase
  - Minimum operating current   (1-100)% Ibase Meet
  - Characteristic angle of relay 51/67 Degrees -70 to -50 Meet
  - Maximum forward angle Degrees 40-70 Meet
  - Minimum forward angle Degrees 75 to 90 Meet
  - Characteristic angle of the relay 51N / 67N Degrees -180 to 180 Meet
  - Blocking per second harmonic % (5-100%) of the fundamental Meet
  - Timing Sec 0 to 60 0 to 60
  ANSI timing curves
ANSI
  ANSI (Extremely Inverse, Very Inverse, Normal Inverse, Moderately Inverse, Extremely Inverse of Long Time, Very Inverse of Long Time, Inverse of Long Time)
ANSI(,,,,,,)
Meet
  IEC Timing Curves
IEC
  IEC (Normal Inverse, Very Inverse, Inverse, Extremely Inverse, Extr. Inverse Long time Inverse Short Time, Inverse Long Time)
IEC(,,,,.,)
Meet
  - Operating time, start function
-,
Ms 25 (from 0 to 2 Iset) 20 ms typically at 0 to 2 x Iset
  - Reset time, start function
-,
Ms 25 (2 to 0 Iset) 35 ms typically at 2 to 0 x Iset
7.5.0 Minimum voltage (27)      
  - Number of adjustment steps
 
  2 Meet
  - Low and high setting range for operating voltage UBASE 1 -100 (1-100)% of UBase
  - Setting range for absolute hysteresis UBASE 0 -100 0 -100
  - Low and high setting range for internal lock level UBASE 1 -100 1 -100
  - Timing

 
S Definite Time (0-60) sec (0.00 - 6000.00) s
Programmable Curves Yes
  - Operating time for start-up function
 
Ms 25, t Ipeak 2 to 0 x Uset 30 ms typically at 2 to 0.5 x Uset
  - Reset time for start-up function
 
Ms 25, t Ipeak from 0 to 2 x Uset 40 ms typically at 0.5 to 2 x Uset
7.6.0 Maximum voltage (59) and Maximum residual voltage   Yes Yes
  - Number of adjustment steps
-
  2 2
  - Low and high setting range for operating voltage
-
% U base 1 - 200 (1-200)% of UBase
  - Setting range for absolute hysteresis
 
UBASE 0 - 100 0 - 100
  - Timing
 
  Definite Time (0-60) sec (0.00 - 6000.00) s
Programmable Curves Yes
  - Operating time for start-up function
 
Ms 25, t Ipeak from 0 to 2 x Uset 30 ms typically at 0 to 2 x Uset
  - Reset time for start-up function
 
Ms 25, t Ipeak 2 to 0 x Uset 40 ms typically at 2 to 0 x Uset
7.7.0 Switch failure (50BF)      
  - Phase current adjustment range % (5-200)% Ibase (5-200)% of lBase
  - Residual current adjustment range % (2-200)% Ibase (2-200)% of lBase
  - Timers Sec 0 to 60 (0.000-60.000) s
  - Operating time for current detection (typical)
()
Ms 10 35 ms typically
  - Reset time for current detection (maximum)
()
Ms fifteen 10 ms maximum
7.8.0 Overexcitation (24) (24)      
  - Operating setting range for start up UBase / fn (100-180)% (100-180)% of (Ubase/frated)
  - Setting range of operation for alarm Ubase (0-100)% (50-120)% of start level
  - Operating setting range for high level
-
UBase / fn (100-200)% (100-200)% of (Ubase/frated)
  - Alarm timing S (0.000 - 60.000) (0.000-60.000) s
7.9.0 Synchronization check (25) (25)   Yes Yes
  - Bar angle offset and line degrees -180 to 180 -180 to 180
  - Ubarra / Uline tension ratio % (0.40 - 5.00)% of UBASE (0.40 - 5.00)% of UBASE
  - Setting range of the line-to-line frequency difference limit Hz 0.003 - 1 0.003 - 1
  - Range adjustment of the line angle difference limit bar-line degrees (5.0 to 90.0) (5.0 to 90.0)
  - Bar-line voltage difference limit adjustment range % (2.0 - 50.0)% of UBASE (2.0 - 50.0)% of UBASE
  - Output timing for synchronization S (0.000 - 60.000) (0.000 - 60.000)
  - High voltage limit setting range % (50-120)% of UBASE (50-120)% of UBASE
7.10.0 Thermal Overload (49) (49)      
  - Base Current Setting Range I base (30-250)% (30-250)% of IBase
  - Alarm setting % I shot (50-99)% (50-99)% of heat content trip value
  - Operating current adjustment range I base (50-250)% (50-250)% of IBase
7.11.0 Frequency (81) (81)      
  - Number of steps
 
  6 Meet
  - Frequency Functions
 
  M INIMA Frequency  
About Frecuencia  
Derived from Frequency  
  - Adjustment range
-
Hz (35.00 - 75.00) (35.00-75.00) Hz
  CONSTRUCTIVE ASPECTS Hz / s (-10,000 - 10.00) steps 0.01 Meet
  Frequency Ms 100 Meet
  Weight S (0.000 - 60.000) 300kg
  Approximate Dimensions (Height, Width, Depth)
(,,)
S Yes  
  Mounting   Yes  
7.12.0 Operating temperature   Yes  
  Storage temperature S 0.05 - 1 -40...+85ºC
  Relative Humidity Range S 0.1 - 10 <93%
  TENSION AND CURRENT ANALOGUE INPUTS
 
S 0.5 - 10 1A/5A
  Number of analog inputs No. 96 10~20
  Voltage inputs No. 40  
  - Number of entries
-
Sample / cycle twenty  
  - Rated voltage (Vn)
(V)
Hz 5 - 300  
  - Operating margin No. 100  
8.0.0 - Maximum permanent voltage      
8.1.0 - Maximum tension for 10 seconds      
  Burden   Yes  
  Current Inputs   Yes  
8.2.0 - Number of entries
-
     
  - Rated current (In)
(IN)
  Yes  
  - Operating margin   Yes  
8.3.0 - Maximum permanent current      
  - Maximum current for 1 sec.   1000  
  Burden   Yes  
  DEPARTURES AND BINARY ENTRIES No. 96  
  Programmable Trip and Signaling Outputs No. 40  
  - Number of contacts (minimum)
-()
Ms 1  
8.4.0 - Maximum operating voltage
-
  YES  
8.4.1 - Test voltage at the open contact, for 1 min.
-,1.
     
  - Permanent current carrying capacity
-
  Yes  
 
No. DESCRIPTION TION UNID. VALUE REQUIRED VALUE OFFERED
1 GENERAL DATA      
1.1 Country of manufacture     Sweden/China
1.2 Maker     ABB/SAC
1.3 Model     REC650
1.4. Kind   multifunction ng NG multifunction
1.5 Internal processing unit   Microprocessors Microprocessors
1.6 Installation height (m) ()   1000  
1.7 Rule   IEC 60255 Meet
      IEC 61000 Meet
      IEC 60297 Meet
      ENV 50204 Meet
1.8 Working temperature range ° C -10 to +50 -25...+55oC (continuous)
1.9 RH % 90 <93%, non-condensing
1.1 Mounting   Horizontal Horizontal
1.1 Phases   03 phases + earth3  
1.1 Dimensions and weight      
  * Width Mm   220 mm
  * Depth Mm   265.9 mm (6U)
  * Height Mm   249.5 mm
  * Weight Kg   <10 kg (6U)
1.1 Consumption GOES   35W
1.1 Digital programming --- Yes Yes
1.2 Modular architecture --- Yes Yes
1.2 Oscillographs --- Yes Yes
1.2 Sensitivity MA 1 Meet
1.2 Degree of protection   IP52 Front side:IP40
Rear side, connection terminals:IP20
Front and side:IP42
1.2 Test voltage at 60Hz (1min) KV 2 Meet
1.2 Immunity to electrical and electromagnetic interference --- Yes Yes
1.2 Special Tests      
  EMC Immunity IEC 255-22; 22-1; 22-2; 22-3; 22-4) --- Yes Yes
  EMC Emission EN50081-2; EN55011 class A --- Yes Yes
  Insulation (IEC 255-5) (IEC 255-5) --- Yes Yes
  Mechanical Efforts IEC255-21 IEC68-2 --- Yes Yes
         
2 NOMINAL DATA      
  Frequency Hz 60 50/60Hz
  Rated current TO 1 and 5 1A/5A
  Change of CT signal polarity via software
CT
--- Yes Yes
  Nominal voltage (between phases) autorang
()autorang
Vca 100 to 120 ± 15% 100,110,120,220,240 V AC
  Maximum permanent voltage Vca 2Vn 420 V rms
  Maximum voltage for 1 minute
1
Vca 3.5Vn 420 V(10s) rms
  Overload capacity for current circuit (ms)   4 x In continuous  
      100 x In for 1sec  
  Auxiliary voltage, autorang
,autorang
Vcc 110-250 ± 20%  88...300 V DC
3 PROTECTION FUNCTIONS      
3.1 AVAILABILITY OF PROTECTION      
  * Neutral Isolated
*
  Yes Yes
  *Neutral Grounded Rigorously   Yes Yes
  * Neutral Artificial using a ZIG-ZAG transformer
ZIG-ZAG
  Yes Yes
3.2 PROTECTION CLOSURE ON FAILURE      
  Dead Line Detection Voltage Range V (1 to 100)% Vn (1 to 100)% Vn
  Dead Line Detection Current Range TO (1 to 100)% In (1 to 100)% In
  Enablement time Msg <200 <200
3.3 TIMER OVERLOADING (51 / 51N)      
  Number of stages for function 51 No. ínimo 2 4
  Number of stages for function 51N No. ínimo 2 4
  Setting current range % In 10 to 2500 Meet
  Inverse Characteristic Curves, defined
,
--- IEC, ANSI and User Defined IEC, ANSI
3.4 INSTANTANEOUS OVERLOADING
(50 / 50N)
     
  Number of stages for function 50 No. ínimo 2 4
  Number of stages for the 50N function No. ínimo 2 4
  Setting current range % In 10 to 4000 Meet
  Delay time range Seconds 0.02 to 15 Meet
3.5 DIRECTIONAL OVERCURRENT (67 / 67N)
(67 / 67n)
     
  Number of stages for function 67 No. ínimo 2 4
  Number of stages for function 67N No. ínimo 2 4
  Polarization by zero / negative sequence --- Specify  
  Polarization angle º Specify  
  Setting current range % In 10 to 3000 Meet
  Inverse Characteristic Curves, defined --- IEC, ANSI and User Defined IEC, ANSI
3.6 TENSION PROTECTION (59/27)      
  Number of steps No. ínimo 3 59:2 steps;
27:2steps
  Maximum voltage range Vn 80 to 150 Meet
  Minimum voltage range Vn 10 to 100 Meet
  Delay time range Seconds 0 to 60 0 to 60
3.7 PROTECTION FAULT SWITCH      
  Operating Current TO (5-500)% In (5-500)% In
  Delay Time Trigger Seconds 0 to 60 0 to 60
  Current detection for operating time msec. <10 Meet
3.8 OTHER PROTECTIONS AND FUNCTIONS      
  Negative Sequence (46)
(46)
--- Yes Yes
  Trip Circuit Supervision --- ínimo 2 2
  Monitoring of the current circuit --- Yes Yes
  Voltage circuit supervision --- Yes Yes
  Switch Condition Monitoring --- Yes Yes
  Number of adjustment groups --- 4 4
         
4 CONTROL      
4.1 AUTOMATIC RECEPTION      
  Number of steps No. ínimo 5 5
  Criteria for initiation --- Configurable Configurable
  Blocking / Inhibition Criteria
/
--- Configurable Configurable
  Dead time setting Seconds 0.20 to 100 0.20 to 100
  (Steps of 0.01 s) 0.01s
  Synchronism check capability at recloser --- YES Yes
  Discrimination time Seconds 0 to 10.00 0 to 10.00
  (Steps of 0.01) (Steps of 0.01)
4.2 SINCROCHECK      
  Angle Range ° (-180 to 180) (-180 to 180)
  Bar-line voltage limit range V (0.5-5.0)% Vn (0.5-5.0)% Vn
  Frequency difference limit range Hz (0.003-1.000) (0.003-1.000)
  Angle difference limit range ° (5-90) (5-90)
  Voltage difference limit range V (2-50)% Vn (2-50)% Vn
  Function evaluation time Seconds (0.0 - 60.0) 0~60s
  Function operation time Msg 200 Meet
4.3 EQUIPMENT CONTROL FUNCTIONS      
  Control and control via the LCD display with position indication LCD No. ínimo: 2 switches, 3 disconnectors 8
  Status indication of non-controllable equipment No. Specify According to the requirement.
  Local / remote front button
/
--- Yes Yes
  Alternative selection of Local / Remote via binary input
/
--- YES Yes
  Automation and Control Buttons No. ínimo 5 According to the requirement.
5 PLC CONFIGURATION AND PROGRAMMING --- Yes Yes
  Programming via matrix logic --- YES Yes
  Programming through block diagram (graph)
()
--- YES Yes
6 AUXILIARY CONTACTS      
6.1 OUTPUT      
  Shooting Contacts      
  Number of contacts (minimum) No. Referring to Fig. According to the requirement.
  Operating Voltage You 125 ± 20% Meet
  Permanent Intensity TO Referring to Fig. Meet
  Intensity 3 sec TO fifteen Meet
  Intensity at 0.5 sec TO 30 Meet
  Programmable output contacts --- YES Yes
  Number of contacts (minimum) No. Referring to Fig. According to the requirement.
  Operating Voltage You 125 ± 20% Meet
  Permanent Intensity TO 5 Meet
  Intensity 3 sec TO 10 Meet
  Intensity at 0.5 sec TO fifteen Meet
6.2 INPUT      
  Programmable Input Contacts --- YES Yes
  Number of input contacts (minimum) No. 2. 3 According to the requirement.
  Voltage range You 24-250 24-250
7 MONITORING AND REGISTRATION      
7.1 MEASUREMENTS      
  Instantaneous values --- Yes Yes
  Voltages, currents, frequency, power and power factor
,,,
--- YES Yes
  Primary and secondary voltages and currents (phase and angle)
()
--- YES Yes
  Positive, negative and zero sequence currents and voltages
,
--- YES Yes
  Active and reactive power --- YES Yes
  Real-time monitoring of measurement parameters --- Yes Yes
  Voltage signal input for calculation of measurement parameters --- Yes Yes
  Status of controlled equipment (open, closed, undefined)
(,,)
--- YES Yes
7.2 OSCILOGRAPHY RECORDER      
  Number of binary signals No. 64 Meet
  Number of physical analog signals No. 30 Meet
  Number of analogue signals calculated No. 10 Meet
  Sample Rate Sample / cl 4,8,16,32 or 64 Meet
  Bandwidth Cycles 600 600
  Pre-fault time Ms 10 to 3000 10 to 3000
  Post-failure time Ms 100 to 10000 100 to 10000
  Number of registered oscillographs No. ínimo 100 Meet
  Total recorder capacity Cycles 1 Mbyte 1 Mbyte
  Drive by internal and external signals --- Yes Yes
  Real-time monitoring of relay inputs and outputs --- Yes Yes
  File format   COMTRADE Yes
  In case of power interruption, the events will be Stored in the volatile memory,   Yes Yes
7.3 EVENT RECORDER      
  Registered event numbers (available for extraction)
()
No. 1000 1000
  Stores sequentially, with date, time, second and millisecond indication ,,, --- YES Yes
7.4 FAULT RECORDER      
  Number of records No. 100 100
  Pre-fault and current and voltage failure value --- YES Yes
7.5 TROUBLESHOOTING --- YES Yes
8 LOCAL AND REMOTE COMMUNICATION      
8.1 Open communication protocol      
  * IEC 61850 --- Yes Yes
  Native (no mappings or converters)
()
--- Yes Yes
  KEMA Certification
KEMA
--- Yes Yes
  Messaging Goose     Yes
  Digital Signs --- Yes Yes
  Analog Signals --- Yes Yes
  Class   P1  
  Kind   A1  
  Signal Transfer Speed Ms <2.5 Meet
  * DNP 3.0 TCP / IP --- Yes No
  * Modbus --- Optional Optional
8.2 Ports of communication      
  * RJ-45 Ethernet --- YES, Front Yes
  * RJ-45 Ethernet --- Yes, Later Yes
  * Ethernet Fiber Optic
*
--- Yes, Later Yes
  * Stand-alone port for synchronization --- Yes, (IRIG B) IRIG-B
9 OPERATION INTERFACE      
9.1 LOCAL INTERFACE      
  Front display and keypad --- Yes Yes
  Interface with control systems --- Yes Yes
  Remote communication --- Yes Yes
  Input and outputs for telemetering --- Yes Yes
  Self-diagnosis or self-supervision --- Yes Yes
  Phase indication triggered --- Yes Yes
  Signal sending signal --- Yes Yes
  Signal reception --- Yes Yes
9.2 WEB-BASED INTERFACE Web      
  Embedded web server --- Yes Yes
  Changing Web Protection Settings --- Yes Yes
  Download Oscillographs via web --- Yes Yes
  Events Download Via web --- Yes Yes
  Resetting of Indications and Alarms via web --- Yes Yes
  Security system --- Yes Yes
10 LED SIGNALING      
  * Visual indicator --- Yes Yes
  * Minimum number of configurable LEDs No. Four. Five 15
  * Shooting start --- Yes Yes
  * Shooting --- Yes Yes
  * Relay Status --- Yes Yes
  * Activated by external contact or internal function --- Yes Yes
  * Activation by protection function --- Yes Yes
9 SOFTWARE      
  *Configuration software (with license) --- Yes Yes
  * Environment   Windows Windows 7
  * Security level (Password) --- Yes Yes
  * Download information --- Yes Yes
  * Oscillograph analysis software --- Yes Yes
  * Local programming --- Yes Yes
  * Remote programming --- Yes Yes
  * Relay communication cables - computer --- Yes Yes
  * Operation and configuration manual:
:
--- Yes Only English
Spanish, English (original printed and in magnetic file pdf)
,(PDF)
  * Factory Certified Trainers --- Yes Yes
  * One Relay Simulator Module per person --- Yes Meet
  * Assistants No. 10 According to the requirement.
  * Level Operator Duration days 1 1
  * Duration Level Programmer days 2 2
  * Factory Certification for attendees --- Yes Yes
  * Printed and digital documentation --- Yes Yes
 
TECHNICAL DATA TABLE DIGITAL TYPE ALARM ANNOUNCER
° DESCRIPTION TION UNID. VALUE REQUIRED VALUE OFFERED
1 Digital Alarm Announcer      
2 For application in monitoring of alarms and signaling of Power Substations      
3 Quantity Und 1 1
4 Signaling Digital Type Yes Yes
5 Identification of failures and alarms in form   Visual and audible Visual
6 Feeding You Range 18 to 80 Vdc Meet
7 Control voltage for identification circuits and alarm reset, obtaining from the power supply, You   Meet
Referring to Fig. Internal You 48 Vdc +/- 20%. Meet
Referring to Fig. Internal contact voltage   48 Vdc +/- 20%. Meet
10 Internal contact current: MA mA +/- 20%. Meet
eleven Alarm Channel Capacity : Und 16 units. Min. 16
12 Activating channels using contacts
 
  NO (normally open) or NC (normally closed) NO
13 Reset Delay Times
:
  ms, 20 ms, 100 ms, 1 s, 5 s, 20 s, 60 s or 160 s. Meet
14 Manufacturing standard: IEC 660255-5, IEC 60255-6, IEC 60068-2-3   IEC 660255-5, IEC 60255-6, IEC 60068-2-3 Meet
fifteen For front panel mounting   Yes Yes
16 Selection and configuration of parameters from front panel or via serial interface.
.
  Yes Yes
17 Self-monitoring system that allows system availability and reliability
.
  Yes Yes
18 Code ASCII transmission mode, 4800 or 9600 Bd transfe
ASCII,48009600BDr.
  Yes Yes
19 Operating Temperature: ° C to 55 ° C Meet
twenty Degree of protection: IP 54.   IP 54 Meet
twenty-one Includes Equipment Manual and accessories for front panel mounting. .   Yes Yes
 
TABLE OF TECHNICAL DATA MULTIFUNCTION METER
° DESCRIPTION TION UNID. VALUE REQUIRED VALUE OFFERED
         
1 MULTIFUNCTION METER      
1 Maker     Alster
1 Team model     AC1700
1 Operating Temperature: :   -20 ° C - + 70 -40ºC~+70ºC
1 Number of Threads:4   4 threads 3-phase 3-wire,3-phase 4-wire
1.1 Rated current TO 1 to 5 5-6A, 5-10A, 1-2A, 1-1.2A
1.1 Voltage: Autorango V (ln) 57V to 347V 57.5 - 240V (3 ph 4 wire)
100 - 415V (3 ph 3 wire)
1.1 Power Supply   85-240 Vac ± 10% 70~265V AC/DC
1.1 Frequency Hz 60 50Hz or 60Hz
1.1 Class of Metrology   IEC600687 0.2s or 02.S IEC62053-22 IEC 62053 - 22
1.1 Four Squares   yes  
1.1 Information preservation without auxiliary power
 
  Minimum 30 d ies30 Meet
1.1 Circular mass memory   Minimum 60 d ies Meet
1.1 Load Profile Option   yes Meet
1.1 Number of Recording Channels, Minimum ,   Referring to Fig. According to the requirement.
1.2 Number of Recording Channels, optimal ,   or 8 8 channels
1.2 Digital Inputs   yes Yes
1.2 Outputs for relays and control functions   yes Yes
1.2 Analog I / O Option   yes Yes
1.2 Programming of any parameter or condition for control and alarm functions   yes Yes
1.2 Instant Instrumentation Values   V, I, kW, kVAr, kVA, kWh, kVarh, frequency, FP V, I, kW, kVAr, kVA, kWh, kVarh, frequency, FP
1.2 Bidirectionality   yes Yes
1.2 Frozen readings option   yes Yes
1.2 Phasor diagram generation   yes Yes
1.2 External communication RS485, switchable with RS232 RS485RS232,   yes Yes
1.3 Communication protocol   DNP 3.0 / Modbus Serial DNP3.O, Modbus and IEC 61850 thernet Flag IEC 62056-21 (formerly 61107)
1.3 Internal Modem Option   yes Yes
1.3 Event Logging and Handling   yes Yes
1.3 Power and Demand Channels   yes Yes
1.3 Redundant Font   yes Yes
1.3 RTC (Real Time Clock)
RTC()
  Upgradable GPS RTC
1.3 POWER AND ENERGY DEMAND      
  Voltage and current unbalance   yes Pls.refer to AC1700 manual.
  Frequency, power factor, apparent power, reactive and real power ,,,,   yes Yes
  Export and import of bidirectional energy   yes Yes
1.3 PQ ANALYSIS      
  SAG / SWELL wave monitoring /   yes Pls.refer to AC1700 manual.
  Symmetrical components: Zero, Positive and Negative :,,   yes Pls.refer to AC1700 manual.
  Individual harmonics and total harmonic distortion greater than the 63rd 63   yes Pls.refer to AC1700 manual.
  Detection of transients greater than 17 us
17
  yes Pls.refer to AC1700 manual.
  Sequence of Events   yes Pls.refer to AC1700 manual.
  Samples per cycle, above 1.0241024   yes  
  Registry of Flicker and Harmonics of voltage according to NTCSE Peruana ntcse   yes Pls.refer to AC1700 manual.
1.3 DATA AND RECORDS OF WAVES      
  Waveform recording of up to 214,000 continuous cycles with 16 samples per cycle.
214000,16.
  yes Pls.refer to AC1700 manual.
  Point-driven: external signal and programs
:
  yes Pls.refer to AC1700 manual.
  Maximum / minimum records for any parameter
/
  yes Pls.refer to AC1700 manual.
  Historic records, maximum number of characters
,
  32 Pls.refer to AC1700 manual.
  Resolution in seconds Samples per cycle, up to 1,024
,1024
  yes Pls.refer to AC1700 manual.
  Time Synchronization with GPS
GPS
  yes Pls.refer to AC1700 manual.
1.3 COMMON PORTS AND EXPANDABLE ENTRY / DEPARTURE /      
  Ports RS-232/485 switchable RS-232/485   1 Meet
  RJ 45 port
RJ 45
  1 Meet
  Slave Ports Modbus RTU Serial, Ethernet, Modem, I / R
Modbus RTU,,,I/R
  yes Yes
  Ports DNP 3.0, Modem and I / R
DNP 3.0,I/R
     
  Data transfer gateway modem / direct Ethernet network for RS-485
RS-485
  yes Yes
  Analog outputs with expandable input / output
/
  4 inputs / 4 outputs Pls.refer to AC1700 manual.
  Digital status, input counter
,
  Referring to Fig. Pls.refer to AC1700 manual.
  Digital relay outputs (control / pulse)
(/)
  7 m ínimo Pls.refer to AC1700 manual.
  Sync port   If (IRIG B or NTP SERVER) Yes
1.4. SEVEN POINTS FOR CONTROL AND ALARM      
  Setting, mínimum response time   sec or 1/2 cycle sec
  Linearization of mathematical, logical and logarithmic formulas
,
  yes Yes
  Simple and multi - alarm alarms   yes Yes
  Remote Alarm Notification   yes Yes
1.4. INCOME OF MEASUREMENTS      
  Standards for accuracy: ANSI C12,60   yes Yes
  ANSI standard C12,20 0.2   yes Yes
  Standard IEC 60687 0,2 S   yes IEC 60687
  IEC 60687 standard, accuracy class 0,2 S   yes Yes
  Line Loss and Transformer Compensation   yes Yes
  Multiple annual scheduling, Hourly activity profiles ,   yes Yes
  software   yes Yes
 
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now