Application: | Instrument |
---|---|
Type: | Voltage Transformer |
Phase: | Single |
Operation Condition: | Outdoor |
Usage: | Protection, Measurement |
Winding Form: | Multilayer Honeycomb Type |
Customization: |
---|
Suppliers with verified business licenses
1 | Manufacturer | HEMG |
2 | Designation Standard |
Outdoor single phase Oil-paper Inductive IEC60044-2:2003 |
3 | Type | JDCF-145TAW2 |
4 | Designation test certificate: 1. Issuing institute 2. Number and data |
Attached in the bid 1.KEMA 2.07-1005, 2007-08-03 |
5 | Rated primary voltage | 132/√3 kV |
6 | Rated secondary voltage, 1.Measuring core (1) 2.Protection core (2) |
1.0.11/√3 kV 2.0.11/√3 kV |
7 | Rated frequency, | 50 Hz/60HZ |
8 | Impulse withstand voltage 1.2/50μs impulse wave, | 650kV peak |
9 | Power frequency withstand voltage, primary windings | 275kV |
10 | Power frequency withstand voltage, secondary windings | 3kV |
11 | Rated secondary output 1.Measuring core (1) 2.Protection core (2) |
) 50VA ) 75VA |
12 | Accuracy Class ) For measuring ) For protection |
) 0.2 ) 3P |
13 | Voltage factor at rated voltage: ) Continuous ) 30 seconds |
) 1.2 ) 1.5 |
14 | Thermal limit burden | 2000 VA |
15 | Normal temperature rise ) Winding ) Oil |
) 30ºC ) 30ºC |
16 | Maximum temperature rise under short-circuit conditions ) Winding ) Oil |
) 50ºC ) 30ºC |
17 | Total height | As per drawing |
18 | Minimum phase spacing, | 2500 mm |
19 | Minimum clearance | 1460 mm |
20 | Minimum creepage distance, ) Normal ) Extended |
) 3850 mm ) 3850 mm |
21 | Size and section of terminal bolt (attach drawing) | As per drawing |
22 | Weight of oil per pole | 165kg |
23 | Total weight per pole | 720kg |
24 | Type of oil and reference specifications ) Oil density at 25ºC ) Oil viscosity at 25ºC |
IEC60296 ) 0.895 g/ml ) ≤13 cs (40ºC) |
25 | Permissible secondary short circuit current | 1058A |
26 | Partial discharge level | ≤5 pC (under 1.2Um/√3kV) |
Suppliers with verified business licenses